Equipment Information As Basis for Systems Proposal For 2 sites in Malinao Municipality, Albay
I. Parameters (Turbine) Vera (Site 1) Cumagingking (Site 2)
1. Unit arrangement 2x150=300 KW 2x110=220 KW
2. Discharge 0.20 cubic meters 0.30 cms
per second ( cms)
3. Net Head H 192 meters(m.) 93 m.
4. Surge tank water El. 400.70 m. above El. 120.08 m. masl
Level mean sea level (masl)
5. Tailrace level El. 196 m. masl El. 20 m. masl
6. Length of headrace 539 m. long, 1,302 m. long
and diameter 600 miliimeter(mm.) 650 mm.
7. Length of penstock 1,646 m.long 203 m.long
And diameter 400 mm. 350 mm.
II. Generator
CAPACITY : As specified above
VOLTAGE : 480 VAC
FREQUENCY : 60 HZ
III. Governor : Please specify
IV. Excitor : Please specify
V. Transformer
• Primary Voltage : 480 V Delta Connection
• Secondary Voltage : 13.8 KV WYE Connection
• Capacity : Please specify the rating suitable for the output
of the Generator
• No. of Phase : 3 Phase
• Frequency : 60 HZ
VI. Valves : Please specify
Design by: Contractor:
Manuel M. Vergel III Roberto R. Masigan
VERGEL3 CONSULT Electrical Manager
February 28,2007 Measurement & Controls Technology Inc.