| Used 3X10500kW/10.5kV/50HZ Wartsila power plant (total running time 25000hr) Here in China 3 units of of Used of second hand 10500kW/10.5kV/50HZ Wartsila power plant (total running time 25000hr) in on floating on auction. Plant Specification
 Type of plant
 The power plant has been designed for base load application, intended for parallel operation with public supply system. The power generation part consists of a gen-set using a Wartsila VASA 12V46 diesel engine as a prime mover driving the generator generating the electrical power.
 The operation of the diesel generating set is carried out from the control room. The operation method is manual with automatic synchronizing, based on the operator’s push-button order. Auxiliary equipment are controlled from panels mounted close to the equipment.
 The equipment includes control equipment, meters and sensors ended for the operator to monitor the equipment and processes, to give alarm in case of abnormal conditions; to stop the diesel power plant operation in case of hazardous conditions occurs.
 The diesel power plant is designed for heavy fuel oil operation.
 
 The main systems of the power plant are:Electrical system
 Fuel system
 Lubricating oil system
 Compressed air system
 Cooling water system
 Charge air & exhaust gas system
 Steam system
 The total electrical power output is generated by three diesel generating set of the type Wartsila Vasa 12V46 at 500 rpm with the following electrical characteristics:
 Generator nominal output 13137kVA (cosø=0.8)
 Generator voltage 10500V, adjustment range ±5%
 Frequency 50HZ
 Auxiliary voltage 380VAC, 110VDC
 Site conditions
 The equipment is designed and constructed for operation at the following maximum site conditions:
 Max. ambient temperature 40�?BR>Min ambient temperature 0�?BR>Max. engine room air temp. 45�?BR>Altitude maximum 100m ASL
 Max. wet bulb temp. 32�?BR>Max. water temp. to charge air cooler 40�?BR>The layout drawing for 3x10500kW power plant attached.
 Main technical data for 3x10500kW/10500V HFO generatorThe gen-set consists of a Wartsila VASA 12V46 diesel engine and an ABB HSG1600K12 self-cooled three phase A.C. generator. The engine is mounted on rubber elements on a fixing rail bolted to the foundation, thus achieving a good vibration reduction.
 The flexible coupling ensures that the generator and the engine do not affect each other due to small deviations in alignment, temperature movements or dynamic free forces. All external piping systems are connected to the engine via flexible connections listed in the respective auxiliary systems.
 Main data for diesel engine
 The gen-set is using a Wartsila VASA 12V46B diesel engine as a prime mover to drive the generator. The Wartsila Vasa 12V46B is a four stroke, direct injected, turbocharged and intercooled design.
 Configuration Vee
 Number of cylinders 12
 Cylinder bore 460mm
 Stroke 580mm
 Speed 500rpm
 Mean piston speed 9.7m/s
 Mean effective pressure 22.5bar
 Piston displacement per cylinder 96.4l
 Number of valves per cylinder 2 inlet valves, 2 outlet valves
 Direction of rotation facing flywheel clockwise
 Engine nominal output 10860kWm
 Main data of generatorThe ABB HSG 1600K12 generator is a self-cooled, 3-phase, brushless, synchronous, two bearing type generator.
 Output 13137kVA
 Power factor 0.8
 Voltage 10500V
 Current 722A
 Frequency 50HZ
 Speed 500rpm
 Efficiency at 0.8p.f., 100% load 96.8%
 Insulation class/temp. rise F/F
 Protection IP21
 Standard EC34
 Bearings and shaft
 The generator is horizontally mounted and provided with two sleeve bearings.
 Cooling
 The generator is self cooled. A fan mounted on the generator shaft takes the cooling air from the ambient and blows it through the generator.
 Terminals
 The six stator winding ends are brought to the terminal boxes on the generator sides.
 Damper winding
 The generator is provided with a damper winding for operation with each other and separate grid.
 Brushless excitation system
 An exciter mounted on the generator supplies the excitation power for the brushless main machine through a diode bridge. The control power for the exciter is supplied through an automatic voltage regulator.
 Accessories
 The following accessories are included with the generator:
 Six PT-100 elements in stator windings
 PT-100 element for each bearing
 Anti condensation space heater
 Automatic voltage regulator
 Current transformer for AVR function
 Electrical systemMain switchgear
 The main switchgear is of the air insulated, metal enclosed type with single busbar system. The switchgear fulfills IEC298 standard.
 Enclosure IP3X exterior
 IP2X interior
 Rated values:
 Voltage 12kV
 Current for busbars 2500A
 Current for outgoing feeder cubicle breakers 2500A
 Current for generator cubicle breakers 1250A
 Current for station transformer feeder breaker 630A
 Short circuit strength Ith/1s 31.5kA
 Circuit breakers
 The circuit breakers are equipped with auxiliary contacts, charging motors, closing and shunt tripping coils.
 Current and voltage transformers
 The transformers have a rated burden to suit with connected measuring and protection devices.
 Accuracy class:
 Protection transformers 10P10
 Measuring transformers cl.0.5
 Fuel system
 HFO transfer pump unit
 The transfer pump unit is used to transfer the fuel oil from the HFO storage tanks to the HFO buffer tanks. The HFO transfer pump unit shall be in continuous operation (one pump working and one pump in standby).
 Design
 The main components in the transfer pump unit are:
 Transfer pump D01 and D02
 Capacity 10300l/h
 Pressure 4bar
 El. Motor 4kW
 Suction strainer 500microns
 Heat exchanger
   HFO separator unit3 sets of Alfa Laval FOPX 609 HFO separators
 Specifications and drawings attached.
   LFO transfer pump unitThe transfer pump unit is used to transfer the fuel oil from the LFO storage tank to the LFO day tank. The LFO transfer pump unit contains two pumps; one pump working and the other one in standby mode).
 Design
 The main components in the transfer pump unit are:
 Transfer pump D01 and D02
 Capacity 9100l/h
 Pressure 4bar
 El. Motor 3kW
 Suction strainer B01 and B02 0.25mm MESH
   Booster3 sets of AURAMARINE HFO booster modules
 Model: AMB-L 12000S
 Specifications and drawings attached.
   Lube oil systemLube oil separator
 3 sets of Alfa Laval LOPX 709 separators
 Test report for lube oil separator attached.
   Cooling systemLT radiator
 3 sets of APV M60 MGS-10 radiators
   HT radiator3 sets of APV M60 MGS-10 radiators
   Charge air & Exhaust gas system6 sets of intake air filters
 AAF automatic oil bath air filter
 Type: Multiduty size 6-104 with weather louver & plenum
 6 sets of charge air silencers
 TIO absorption silencer
 Type: HD 44/w
 3 sets of exhaust gas boilers
 3 sets of exhaust gas silencers
 Steam system
 One set of steam system delivered from China
 ·list of available of 6x12MW MAN Diesel Genset ·or other capacity of diesel generator power plant. ·3x10MW Wartsila Used Diesel Power Plant ·6-10MW Man B&W,Sulzer, Deutz Used Diesel plant ·226MW Used Sulzer 16ZAV40S Diesel Generators ·2x11.5MW Used Sulzer Genset ·3x10.5MW used Wartsila VASA 12V46 generator sets With my Best Regards,    Yang Chun Lin  China National Electric Wire&Cable Imp./Exp. Corp.  Add: Rm.803, Building D, Shengshijiayuan Langjiayuan, 98 Jianguo Rd. Beijing, China 100022  We are EPC contractor and supplier of global power generation, transmission and distribution  Tel: 0086-10-85805516 Fax: 0086-10-84568952 Mobile: 0086-13801218512  Email: [email protected] http://www.china-power-contractor.cn 
 
 |