ZBM1460P(1825KVA,50HZ,400V) 3 gensets in total |
|
No. |
Designation |
Model |
Qty. |
Unit |
Production base |
Supplier |
Standard sales price |
|
Unit price |
Total price |
|
Diesel Genset configuration |
|
1 |
Engine |
12V4000G63 |
3 |
set |
Germany |
MTU |
$305,555 |
$916,665 |
|
2 |
Generator |
MX-1540-4 |
3 |
set |
China |
Marathon |
|
3 |
Controller |
DSE7320 |
3 |
PCS |
UK |
Deepsea |
|
4 |
Switch cabinet |
MTE32N |
3 |
set |
China |
Schneider |
|
5 |
Other accessories |
battery,elbow,flange,expansion joint,muffler,brochures,some fuel pipe,etc. |
3 |
set |
China |
ZGPT |
|
Oil tank system |
|
1 |
Oil tank |
3000L |
3 |
set |
China |
ZGPT |
$1,226 |
$3,678 |
|
2 |
Automatic oil filling system |
Electic oil pump, oil filling control box |
3 |
set |
China |
ZGPT |
$47 |
$141 |
|
Others |
|
1 |
Tool |
60T |
6 |
set |
China |
ZGPT |
$9 |
$54 |
|
TOTAL PRICE(FOB NINGBO) |
$920,538 |
|
Remark: |
|
1. Above is preliminary quotation for your inquire,the difference with other supplier maybe caused by different scope of supply, the final quotation will be confirmed after further design or negotiation; |
|
2. Delivery: 60-90 days after down payment received; |
|
3.Payment: 30% downpayment, balance be paid before delivery,the details could be confirmed after negotiating; |
|
4. Warranty: one year from delivery. We promised that the diesel generator are MTU certified and warranted brand New diesel generator, not refurbished or aftermarket diesel generator; |
|
5. Validity: 30 days from Nov.11.2011. |
Technical parameters of ZBM1460P diesel generator sets
|
Technical parameters |
|
Model |
ZBM1460P |
|
Dimension (L×W×H) mm |
6325×2195×2460 (radiator included) |
|
Weight (dry) kg |
12029 (radiator included) |
|
Prime power kVA/kW |
1825/1460 |
|
Standby power kVA/kW |
2025/1620 |
|
Rated voltage V |
400/230 |
|
Rated frequency Hz |
50 |
|
Rated power factor (lag) Cosφ |
0.8 |
|
Steady voltage regulation rate % |
�?/SPAN>±1 |
|
Voltage fluctuation rate % |
�?/SPAN>0.5 |
|
Frequency fluctuation rate % |
�?/SPAN>0.5 |
|
Load sudden frequency stable time s |
�?/SPAN>3 |
|
Load sudden voltage stable time s |
�?/SPAN>2 |
|
Waveform distortion rate THD |
�?/SPAN>5% |
|
Wire mode |
3-phase 4-wire (neutral point directly earthing) |
|
Control system |
micro-processor control system |
|
Damping system |
high-elasticity rubber damper |
|
Noise (1 meter) dB |
113 |
|
Engine |
|
Engine model |
12V4000G63 |
|
Dimension (L×W×H) mm |
2531×1660×2160 |
|
Weight (dry) kg |
6200 |
|
Power (prime\standby) kW |
1575/1750 |
|
Engine type |
12V, turbo-charge intercooler |
|
Oil type |
API CG |
|
Fuel type |
0#diesel |
|
Fuel consumption rate (100% load) (g/kWh)/(L/h) |
193/360 |
|
Oil consumption rate (100% load) (g/kWh)/(L/h) |
0.965/1.8 |
|
Start mode |
24V DC Electro-start |
|
Speed regulating mode |
ADEC (electronic management system) |
|
Cooling method |
Closed water circulation air cooled |
|
MEP (mean effective pressure) bar |
22.0 |
|
Piston speed m/s |
10.5 |
|
Charge air coolant flow m3/h |
29 |
|
Cylinder liner cooling water flow m3/h |
56 |
|
Intake flow m3/s |
1.8 |
|
Smoke flow m3/s |
4.5 |
|
Exhaust smoke temperature �?/SPAN> |
460 |
|
Compression ratio |
16.5:1 |
|
Combustion mode |
direct injection type |
|
Bore\Stroke mm |
170/210 |
|
Displacement, total L |
57.2 |
|
Flywheel interface size (flywheel shell\ flywheel) |
SAE00/21 |
|
Generator |
|
Model |
MX-1540-4 (single bearing) |
|
Dimension (L×W×H) mm |
2150×960×1300 |
|
Weight kg |
3905 |
|
Power (prime\standby) kW |
1540/1630 |
|
Rated voltage V |
400/230 |
|
Frequency Hz |
50 |
|
Type |
Rotating magnetic field, drops prevented structure |
|
Poles |
Four poles |
|
Automatic voltage regulator (DVR) |
DVR2000E |
|
Excitation system |
Brushless PMG |
|
Short-circuit current capability |
300%(3In):10s |
|
Protection |
IP21 |
|
Winding pitch |
2/3 |
|
Speed r/min |
1500 |
|
Working mode |
S1 |
|
Control system |
|
Control module |
Deepsea7320 (three-remote type) |
|
Displayed contents |
Mains supply AC phase\wire voltage, generation AC phase\wire voltage, generation three-phase current, mains supply frequency, generation frequency, generation speed, oil pressure, water temperature, active power, output power, battery voltage, power factor, operation time, fuel oil level (optional) |
|
Main functions |
Generation under\over voltage, overload, generation under\over frequency, under\over speed, charge fail, emergency stop, low oil pressure, high water temperature, failure shutdown, start failure, under\over battery voltage, low fuel alarm, signal of speed loss, mains supply under\over voltage, mains supply under\over frequency, self-start, ATS switching control, record of 15 emergency stop alarms |
For more on diesel generator sets as MTU, Cummins, perkins, doosan or MAN HFO diesel generator , please click.
|