Configuration Analysis sheet for 60MW HFO Power Plant
Inquiry:
We intend to extend our Power Station by the addition of four new 15 MW diesel engine generating units. This will involve the removal of two of the existing diesel generating units which have now reached the end of their useful life and no longer comply with the applicable environmental standards, and the demolition of the associated powerhouse building. The new engines will operate on heavy fuel oil, with the capability of changing to LNG fuel if this becomes available in the future, and will include the necessary engine cooling systems, fuel oil storage and treatment systems, control systems and exhaust gas stacks. The project will also include the construction of a new indoor 66 kV substation which will eventually replace the existing aging outdoor substation and will facilitate the upgrading of the main power distribution system to 132 kV.
Can you let them accept our following configuration with MAN 8730kw unit HFO sets, the reasons:
Configuration Analysis sheet for xxx 60MW HFO Power Plant |
No.
|
Description
|
MAN
|
Advantages of MAN unit compared with 15MW unit |
1 |
Type |
18V32/40 |
|
2 |
Engine power kW |
9000 |
|
3 |
Unit rated power kW |
8730 |
|
4 |
Nos of unit |
8 |
A. MAN 8 units to be supplied has high reliability, in case of one genset is failure or stopped for repair, the outage rate is only 12.5%. B.If 4X15MW is provided, and one genset is failure or stopped for repair, the outage rate is up to 25%, thus the reliability is much lower. |
5 |
Installed capacity MW |
69.84 |
|
6 |
Guaranteed net output MW |
66.7 |
|
7 |
Speed rpm |
750 |
|
8 |
bore × stroke mm |
320×400 |
|
9 |
Single cylinder displacement L |
32.17 |
|
10 |
Explosion pressure bar |
190 |
|
11 |
Unit overall
dimension: L×W×H
mm |
12750×3500×5240 |
Small in size, easy for transportation and maintenance |
12 |
Unit weight ton |
139 |
Light weight, easy to be transported |
13 |
Engine heat efficiency |
46.60% |
High heat efficiency |
14 |
Fuel quality |
LFO/HFO,
Max. viscocity :700CST |
700CST Unit Max.runable viscocity is 700CST
|
15 |
Overhall interval H |
36000 |
High reliability and durability, long service life, and maintenance-free during operation |
16 |
Performance |
MAN, as the world top brand, adopts Germany technology to manufacture reliable products with low consumption, which meets World Bank’s requirements.18V 32/40 model is widely used, 3475 units are under normal operation all over the world. |
As a manufacturer, having its features of timely delivery, competitive price, professional and immediate after-sales service. Its medium and high speed gensets are applied in more than 10 oversea power plants, the total EPC capacity is near 800MW. And have a very strong technical team and large manufacturing bases to guarantee its quality. As the MAN Licensee, we can share the 105 service representative offices and service stations worldwide. We also can provide the maintenance, repair, and operation service of a power plant. | |