BBS  Email&MSN: [email protected]
  
Homepage   |   Power Generation   |   Project Financing    |   Equipments   |   Transmission   |   Financing-Ebook   |   Contact    |   services   |   download   |   sitemaps   |   Spare Parts   |   BBS-Blog   |   Exclusive-Distributor   |   Exchange Link  

Mail List

E-mail:

Equipments
     Gas turbine & spare parts  
       GE 9FA 255mw Gas Turbine Generator  
       GE Licensed MS9001E Series Gas Turbine plant  
       42MW GE Gas Turbine Generator  
       PG6581B Gas Turbine Series Generator Plants  
       PG6581B Gas Turbine Set Supply Scope  
       Gas Turbine Spare Parts  
       Gas Turbine Generator Site Inspection  
       Quotationon Used PG6551B gas turbine plant  
       2MW Gas Turbine Generator  
       7mw-Siemens-SGT200-Gas-Turbine-Cogeneration-unit  
       10MW Gas Turbine Generator  
       Used Gas Turbine Generator Plant  
       Technical-Specification-PG6581B-Gas-Turbine  
       Supply-Scope-of-PG6581B-Gas-Turbine  
       Budgetary Cost for 108MW Gas Turbine Plant  
       Siemens Gas Turbine Generator  
       ABB-Siemens-ALSTOM-Gas-Turbine-Spare-Parts  
     HFO Diesel generator & Marine HFO Engine  
       8x8735kw MAN 18V32/40 HFO Diesel power Proposal  
       8x 4.1mw MAN 9L32/40 hfo power plant proposal  
       10x5.5MW MAN 12V32/40 HFO diesel plant proposal  
       3mw-9mw MAN 18V32/40 HFO Diesel generator  
       6 units 5.5mw MAN 12V32/40 hfo diesel plant  
       3x3.5mw MAN 8L 32/40 hfo diesel generator plant  
       1MW diesel generator   
       1.5MW Diesel Generator Set  
       2M Diesel Generator Plant  
       Sample Diesel Power Plant Proposal 9x2mw  
       Diesel power Plant List  
       Used Diesel Generator  
       Diesel Generator Pictures  
       Bio diesel generator power plant MW  
       Sample Pack List for 10x2MW HFO diesel power Plant  
       10kw-4000kw-Cummins-MTU-diesel-generator-set  
       HFO-diesel-generator-sets-running-on-biodiesel  
     MTU Cummins Perkins Volvo Diesel Generator  
       List of MTU Cummins PERKINS diesel generator  
       Leroysomer Siemens, Marathon Generator  
       MTU-Cummins-Perkins-diesel-generator-spare-parts  
       Germany-Deutz-diesel-generator-and-spare-parts  
     Spare Parts for Steam Turbine Power Plants  
     Power Plant Generator  
       Air Cooled Power Generator  
     Steam Turbine  
       Extraction Condensing Turbine  
       Condensing Steam Turbine  
       Recovery Turbine  
       Extraction Turbine  
       Required Data for Quotation  
       Alstom-Licensed-330MW-Steam-Turbine  
       Quotation-50MW-condensing-steam-turbine  
       Quotation-30MW-Condesing-Steam-Turbine  
     Boiler  
     Hydro Turbine  
     Engineering Machinery  
       Truck Mounted Crane Crawler  
       Trailer Concrete Pump  
       China track Bulldozer  
       China Crane  
       Benz Truck and Lorry from China  
       China-heavy-industry  
       China-outstanding-buses-and-coaches  
     Cable&Wire  
     Electric Motor  
     Transformer in MVA  
       Germany Certificates  
       Required Data for Quotation  
       Transformer Reference  
       Sample Inquiry  
     Wind Turbine Generator  
     Oil-Well-Drill-Bit  
       Oil-Well-Drill-Bit-Main-Products  
       Drill-product-series  
       Other-oilfield-products  
       Kingdream Rock Bits Catalouge 2011  
       IADC-CLASSIFICATION-OF-KINGDREAM-BITS  
       ROCK-BIT-COMPARISON-CHART  
     Drilling-Rig-for-Oil-Gas-Mining  
       Main-products-Directory-introduction  
     Best-Diamond-Brand-Cemented-Carbide  
     China-famous-steel-producers   
     China Largest Steam Turbine Producer  
       Harbin-Electric-Group-Spare-Parts  
     China-Best-Largest-Steam-Turbine-producers  
     Ingersoll Rand Air Compressor  
     Leading-farm-machinery-and-engineering-mechanical  
     Sawblade  

Diesel Generator Proposal

Power Plant Proposal

Home > Equipments > HFO Diesel generator & Marine HFO Engine - 5x2MW HFO power plant project design specifications part 2


 

5x2MW HFO power plant project design specifications part 2

5x2MW HFO power plant project design specifications part 2

4.10 Electrical system
4.10.1 H.V. system
Five 2MW/11kV HFO generators will work in parallel, supply electricity to one 11KV bus-bar and feed out through one outgoing panel.
11kV generator system
Five 2MW/11kV diesel generators are arranged for the power plant. For each one generator, the standard configure includes one switchgear for generator output and potential transformer, one control and operation panel (COP) and one local control desk (LCD).
All five generators are connected with a single bus-bar. An 11kV bus-bar PT panel is arranged for parallel operation. All 11kV H.V. panel adopt KYN28A-12 metal-enclosed removable switchgears, the switch for generator switchgear adopts VS1 vacuum circuit breaker (with truck), its rated current is 630A, and rated short-circuit breaking current is 25KA.
The generator bus-bar connects to one outgoing panel. The switch adopts VS1 vacuum circuit breaker (with truck), its rated current is 1600A, and rated short-circuit breaking current is 31.5KA.
 
Generator switchgear
The generator connects to the bus-bar by vacuum circuit breaker in the generator switchgear.
Major Components in generator switchgear:
1)            3 pole truck type DC/AC 220V electrically operated motor energized VS1 Vacuum Circuit Breaker
2)            Metering / Protection CT and PT
CT type: CT LZZBJ9-11 200/5A with two windings for each phase
Two CTs are installed in the generator switchgear. One CT is for current and power measuring (phase A and C) and excitation adjusting (phase B); another is for load sharing controller.
PT type: one REL-11/�?. 0.1/�?. 0.1/3kV with two windings for each phase
One group of windings in potential transformers is star connected for measuring and protection system. Another group of windings is triangularly connected for single phase earthing protection.
3)            Digital integrated relay
DMR-362 digital integrated relay is adopted for gen-set protection, which is used for alternator protection, switch control, monitoring, measuring and display.
The following functions and protection can be carried out on the relay:
-          Differential
-          Voltage locked over current
-          Reverse power
-          Over current
-          Single phase Earthing
-          Over voltage
-          Low frequency
-          Over frequency
-          Over load
-          Accurate measuring of all operation parameters such as power, voltage, current, frequency, power factor and others
-          Display the conditions of all switches
-          Running record and failure storage
4)            Local / Remote control selector
5)            VCB ON/OFF
6)            DSSX25 kWh and kVarh meter
 
11kV outgoing panel (feeder)
Major Components in switchgear:
1)    3 pole truck type DC/AC 220V electrically operated motor energized VS1 Vacuum Circuit Breaker.
2)    Metering / Protection CT
CT type: CT LZZBJ9-11 1600/5A with two windings for each phase
One group for current difference protecting between transformer’s input and output; one for current protection and power measuring
3)    Digital integrated relay
DMR-301 digital integrated protection relay is adopted for transformer protection, and its protection parameter and function are configurable. The relay can indicate all parameters and store operation and accident record for the running transformer.
The following protection can be carried out on the relay:
-          Differential current
-          Instant trip current
-          Over current
-          Over load
-          Gas
-          High Insulation oil temperature
-          High Insulation oil pressure
4)    Local / Remote control selector
5)    VCB ON/OFF indication
6)    DSSX25 kWh and kVarh meter
 
11kV Incoming panel for station transformer
Major Components in switchgear:
a)     3 pole truck type DC/AC 220V electrically operated motor energized VS1 Vacuum Circuit Breaker.
b)     Metering / Protection CT
CT type: CT LZZBJ9-11 50/5A with two windings for each phase
c)     Digital integrated relay
DMR-301 digital integrated protection relay is adopted for protection, and its protection parameter and function are configurable.
The following protection can be carried out on the relay:
-          Differential current
-          Instant trip current
-          Over current
-          Over load
d)     VCB ON/OFF indication
e)     DSSX25 kWh and kVarh meter
f)      Fixed PT installation truck with arrester.
PT type: one REL-11/�?. 0.1/�?. 0.1/3kV with two windings for each phase
One group of winding in potential transformers is star connected for measuring and protection system. Another group of winding is triangularly connected for single phase earthing protection.
 
4.10.2   L.V. system
A LV auxiliary panel is supplied for all auxiliary equipments including air compressors, radiators and water pumps, fuel unloading stations, HFO treatment equipment and others.
The L.V. electrical systems consist of auxiliary electrical system for generator, auxiliary electrical system for power plant.
The auxiliary equipments for generator include 5 radiators (33KWx5), 5 water pumps (15kWx5) and 3 air compressor motors (5.5kWx3).
 
4.10.2.1 L.V. power source for power plant
The electricity for the power plant is supplied by a 500KVA transformer from the 11kV bus-bar.
 
4.10.2.2 DC panel
The power supply of control plant, protection, signal, automatic device and trouble lighting adopts 200AH direct current electrical source system.
220/24V DC battery charger of suitable capacity along with Lead acid type rechargeable batteries (12 V DC) is used. Charger is fully automatic, with float and boost charging facility. One set of DC/DC transfer module with 60A capacity for 24V output.
Major Components in the DC panel
1)            Source inspect and change over module
2)            Chargers and booster module
3)            12V batteries and battery detect unit
4)            AC/DC ammeters, voltmeters
5)            LCD operation screen

Protections provided for Chargers

6)            Over load / short circuit / earth fault
7)            Over voltage
 
4.10.3   Control system
DG
For each one generator, one control and operation panel and one local control desk are supplied.
Gen-set control and operation panel
The control and operation panel in the control room provides necessary Monitoring, Control and Protection functions for the DG set. It controls the Gen-set running according to the program set in PLC. All Gen-set’s running parameters such as voltage, current, power, power factor, frequency, and speed can be displayed on it.
Major Component in console
1)    Control PLC
2)    Speed Governor controller
3)    Automatic Voltage Regulator
4)    Engine Frequency Monitoring Unit
5)    Meters
Ammeters (3 nos)
Voltmeter with selector switch
Power meter
Frequency meter
PF meter
Analog Excitation fundamental ammeter
Analog Excitation harmonics ammeter
Counter for running hours
6) Operation and indicators
Push buttons, change over switches
VCB engaged indication,
Engine start permission indication
Excitation change over switch
DG VCB ON/OFF
DG VCB Trip and alarm indication
Engine Idling/Rating
Engine start
Engine normal and emergency stop
7) AVR
The integral TWL-ND AVR is designed for the TFW generator specially. It configures with stability adjusting, voltage adjusting, and gen-set paralleling reactive power sharing adjusting.
Input capacity         AC 230V
Compare voltage      AC 100V from PT AC
Current signal         CT 5A from CT B
Max. Output           DC.100V, 10A
Trigger Type          Alternator exciter Remanence
Accuracy             ±1%
Am. Temp            -40~+60�?/DIV>
Reactive sharing      Auto regulating
8)            T4500 auto synchronizer
SELCO T4500 auto synchronizer is designed for automatic synchronization between generator and bus-bar in a minimum of time by controlling the speed via the electric servomotor on the governor.
The T4500 measures the voltage across two phases on either side of the circuit breaker in order to obtain data on voltage, frequency and phase difference for closing the circuit breaker at exact phase accordance.
The synchronization function will become active when the difference between the bus voltage and the generator voltage is within limits. The voltage difference is selectable between 2% to 10%.
When the synchronization function is active, the T4500 will automatically adjust the speed of the generator through the governor in order to match the frequency to the bus-bar.
The T4500 will continuously adjust the generator speed until the frequency difference is within limits. When the voltage and frequency difference are within limits, the closing signal will be activated just before the next phase accordance, anticipating the circuit breaker make time. The T4500 compensates for this make time so that the circuit breaker will close exactly at zero phase.
Specifications for the T4500:
Circuit breaker operating time               20~200mS
Frequency difference                       0.1~1Hz
Voltage difference                         10%
Reference voltage                         110/100V with voltage matching
Operating Temp                           -20~+70�?/DIV>
Contact rating                              AC: 380V, 2A, 250VA; DC: 110V, 2A, 100W
Auto synchronization system is adopted between generators and network and among generators. Manual synchronization system is supplied for standby.
9)            Load sharing
All generators can work in parallel; load can be equally shared among all generators automatically. Woodward programmable and configurable speed governor controller 2301D are adopted to control the engine, which can share or operate Gen-set in base load mode or isochronous mode.
Main functions on the control and operation panel:
-          Starting engine
-          Speedup
-          Speed-down
-          Generator switch ON/OFF
-          Voltage adjustment
-          Reactive power share
-          Synchronization
-          Voltage measuring changeover
-          Lube oil pressure
-          Water pressure
-          Voltage
-          Current
-          Frequency
-          Power
-          Excitation current
-          Speed
-          Alarm
 
Local Control Desk
Local Control Desk is provided for monitoring pressure and thermal parameters of the running engine. Also starting, stopping and speed control of engine is possible in local control operation mode. It is located near the engine.
Major Components in Local Control Desk
1)    Pressure gauges, switches
Lube oil filter inlet pressure
Lube oil filter outlet pressure
Lube oil in cylinder head inlet pressure
Cooling water pressure
2)    Temperature indication
Cylinders cooling water temperature scanner
   Cylinder cooling water outlet temperature measurement system with Cu50 thermo resistor for each cylinder and scanned by a multi-channel meter.
Engine exhaust temperatures scanner
   Pyrometric exhaust gas system with thermocouple for each cylinder and turbocharger, and scanned by a multi- channel meter.
Lube oil engine inlet /outlet temperature
Water engine inlet/outlet temperature
3)    Engine RPM indicator with cranking and over speed protection.
4)    Push buttons, indicating lamps, selector switches
- Common engine alarm
- Engine start permission
- Local / remote mode select
- Engine start / stop
- Flasher off
- Engine speed raise / low
- Emergency stop
 
4.10.4   Protection system
4.10.4.1  Diesel engine
The diesel engine will stop automatically in case of the following failures:
-          Very low lube oil pressure
-          Very high water engine outlet temperature
-          Engine over speed
The diesel engine will alarm automatically in case of the following failures:
-          Low lube oil pressure
-          Low water pressure
-          High lube oil temperature
-          High water temperature engine inlet
-          Alternator bearing temperature high
 
4.10.4.2   DG electricity system
The generator adopts digital integrated relay protection system for monitoring and protection.
A DMR362 digital integrated relay is installed on generator switchgear, which is used for alternator protection, switch control, monitoring, measuring, display and SOE record.
The following functions are configured on the relay:
-          Differential current
-          Reverse power
-          Instant trip current
-          Voltage locked over current:
-          Over current
-          Over load
-          Earth failure
-          Over voltage
-          Under voltage
-          Low frequency
-          Over frequency
 
4.10.4.3   11kV electrical system
One DMR301 digital integrated relay is installed on the outgoing panel, the following functions can be carried out on the relay:
-          Over current
-          Instant current trip
-          Running record and failure store
-          Controlling switch on site or on remote mode
 


 

5. Main equipments specifications
5.1 Diesel engine:

Model
GN8320ZD
Type
Inline, four-stroke, direct injection, turbocharged, and after cooled
Quantity
5 sets
Rated power
2206kw
Rated speed
600r/min
Bore/stroke
320/380mm
Starting method
Compressed air
Cooling system
Open water cooling
Dimension
5620x1620x2760mm
Weight
31000kg
Manufacturer
NB ZhongceDongl1 Co., Ltd

 
Main parts of GN8320ZD Diesel Engine
a.    ABB turbocharger
b.    GEA after cooler, lube oil cooler
c.    Flexible coupling
 
5.2 Alternator

Model
TFW-2000
Type
Brush-less synchronous alternator
Quantity
5 sets
Rated power
2500KVA
Rated speed
600r/min
Rated voltage
11000V
Frequency
50HZ
Power factor
0.8 lagging
Insulation class
F/F
Excitation
AVR
Weight
16000kg
Manufacturer
NB ZhongceDongl1 Co., Ltd

 


 

 
5.3 Air compressor

Model
CZ-20/30F
Type
Single row vertical, differential piston two-stage compression, air cooled
Exhaust capacity
Min. 20m3/h
Quantity
3 sets
Rating pressure
3MPa
Cylinder bore
1st stage: 102mm, 2nd stage: 90mm
Piston stroke
65mm
Exhaust temperature
Max. 85�?/DIV>
Rotary speed
1000r/min
Shaft power
<5kW
Motor
Y132S-6/5.5kW
Overall dimensions
970x440x700mm
Weight
155kg
Manufacturer
NB ZhongceDongl1 Co., Ltd Group Co., Ltd

 
5.4 Air receiver

Model
B500/3.24
Quantity
4 sets
Air inlet & outlet
�?3
Design pressure
3.24MPa
Working pressure
2.94Mpa
Max working temperature
�?0�?/DIV>
Volume
500L
Manufacturer
NB ZhongceDongl1 Co., Ltd Group Co., Ltd

 
5.5 Radiator

Model
3VI1250 H12 - 6150/2117 - 2CA2 S32D302 (HT) + 6CA4 S32D212 (LT)
Quantity
5 sets
Heat transfer
423.8kW for HT, 428.6kW for LT
Medium
Water
Mechanical power
11kWx3
Fan speed
960rpm
Sound level @ 2 m
85.6 ±3 dB(A)
Manufacturer
NB ZhongceDongl1 Co., Ltd Group Co., Ltd

 
5.6 S9-500/11/0.415 Station transformer

Model
S9-500/11/0.415
Rating
500KVA
Primary Volts
11KV
Secondary volts
0.415KV
Insulation level
Standard
Quantity
1 set
Manufacturer
NB ZhongceDongl1 Co., Ltd Group Co., Ltd

 
5.7 Station batteries and battery charger panel

Model
PGD7-�?180-220
AC input voltage
380Vac±20%
DC output voltage
24V, 220V
DC output current
A
Storage battery capacity
300Ah
Accuracy of voltage regulation
Max. ±0.2%
Accuracy of current regulation
Max. ±0.2%
Ripple factor
Max. 0.1%
Power factor
Min. 0.93
Efficiency
Min. 95%
Noise
50dB
Dielectric strength
2000V 1 min without breakdown
Operation environment
Temperatur:-10 to 45�? Relative humidity:not greater than 90% at 20±5�?/DIV>
Interface
RS485, RS232 & RS422
High frequency rectifier module
Emerson HD22020 3pcs
PLC
SIEMENS S7-200
LCD display screen
HITECH PWS 5.7�?/DIV>
Rectifier module
Emerson HD2205 3pcs
Maintenance-free lead-acid battery
A400-180/12V 18 pcs
Overall dimensions (LxDxH)
800x800x2200mm 3pcs
Manufacturer