4.12 Electrical system
The scope of electrical system consists of the electrical equipments inside of main building. The Buyer takes responsibility to transmit power from the feed-out panel to user position.
4.12.1 Generator switchgear
The generator switchgear is used to deliver electricity from alternator to busbar.
Major Components
1) 3 pole electrically operated Air Circuit Breaker (ACB)
2) Metering / Protection CT and PT
3) Meters, indicators
Metering devices
4) Ammeter for every phase
5) Voltmeter with selector switch
Indications
6) ACB ON
7) ACB OFF
8) ACB spring energized
Controls Possible
9) Manual ACB ON/OFF
Digital common protection relay
DMR-301P digital common relay is adopted for gen-set protection, which is used for alternator protection, switch control, monitoring, measuring, display and electrical failure record.
The following functions and protection can be carried out on the relay:
- Voltage locked over current
- Reverse power
- Over current
- Over voltage
- Low voltage
- Low frequency
- Over frequency
- Over load
- Accurate measuring of all operation parameters such as power, voltage, current, frequency, power factor and others
- Display the conditions of all switches
- Running record and failure storage
10) Control and operation functions
The generator switchgear provides necessary Monitoring, Control and Protection functions for the DG set.
Main functions for control and operation:
- Starting engine
- Speed control
- Voltage adjustment
- Load sharing mode select
- Voltage measuring changeover
- Current measuring
- Frequency indication
- Power indication
- Excitation current indication
- Speed indication
- Alarm
4.12.2 LV auxiliary panel
A LV auxiliary panel is supplied for all auxiliary equipments including air compressors, cooling towers, fuel unloading stations (provided by customer), HFO treatment equipment and others.
The L.V. electrical systems consist of auxiliary electrical system for generator, auxiliary electrical system for power plant.
The auxiliary equipments for generator include 1 cooling tower motors (5KW), 1 air compressor motors (5.5kW) and 1 booster motor (11kWx1).
The auxiliary equipments for power plant include 1 HFO unloading pump station (11KWx2), 1 DO unloading pump station (11KWx2), 1 HFO separator module (7.5kW), 2 boiler water feed pump motors (2.2kWx2) and one soft water pump motor (3kW).
Notes: customer provides fuel unloading pump stations and all fuel storages.
4.12.3 Control system
4.12.3.1 DG
For each one generator, one control and operation panel and one local control desk are supplied.
Gen-set control and operation panel
The control and operation panel in the control room provides necessary Monitoring, Control and Protection functions for the DG set. It controls the Gen-set running according to the program set in PLC. All Gen-set’s running parameters such as voltage, current, power, power factor, frequency, and speed can be displayed on it.
Major Component in console
1) Control PLC
2) Speed Governor controller
3) Automatic Voltage Regulator
4) Engine Frequency Monitoring Unit
5) Meters
Ammeters (3 nos)
Voltmeter with selector switch
Power meter
Frequency meter
PF meter
Analog Excitation fundamental ammeter
Analog Excitation harmonics ammeter
Counter for running hours
6) Operation and indicators
Push buttons, change over switches
VCB engaged indication,
Engine start permission indication
Excitation change over switch
DG VCB ON/OFF
DG VCB Trip and alarm indication
Engine Idling/Rating
Engine start
Engine normal and emergency stop
7) AVR
The integral TWL-ND AVR is designed for the TFW generator specially. It configures with stability adjusting, voltage adjusting, and gen-set paralleling reactive power sharing adjusting.
Input capacity AC 230V
Compare voltage AC 100V from PT AC
Current signal CT 5A from CT B
Max. Output DC.100V, 10A
Trigger Type Alternator exciter Remanence
Accuracy ±1%
Am. Temp -40~+60°C
Reactive sharing Auto regulating
1) T4500 auto synchronizer
SELCO T4500 auto synchronizer is designed for automatic synchronization between generator and bus-bar in a minimum of time by controlling the speed via the electric servomotor on the governor.
The T4500 measures the voltage across two phases on either side of the circuit breaker in order to obtain data on voltage, frequency and phase difference for closing the circuit breaker at exact phase accordance.
The synchronization function will become active when the difference between the bus voltage and the generator voltage is within limits. The voltage difference is selectable between 2% to 10%.
When the synchronization function is active, the T4500 will automatically adjust the speed of the generator through the governor in order to match the frequency to the bus-bar.
The T4500 will continuously adjust the generator speed until the frequency difference is within limits. When the voltage and frequency difference are within limits, the closing signal will be activated just before the next phase accordance, anticipating the circuit breaker make time. The T4500 compensates for this make time so that the circuit breaker will close exactly at zero phase.
Specifications for the T4500:
Circuit breaker operating time 20~200mS
Frequency difference 0.1~1Hz
Voltage difference 10%
Reference voltage 110/100V with voltage matching
Operating Temp -20~+70°C
Contact rating AC: 380V, 2A, 250VA; DC: 110V, 2A, 100W
Auto synchronization system is adopted between generators and network and among generators. Manual synchronization system is supplied for standby.
Main functions on the control and operation panel:
- Starting engine
- Speedup
- Speed-down
- Generator switch ON/OFF
- Voltage adjustment
- Reactive power share
- Synchronization
- Voltage measuring changeover
- Lube oil pressure
- Water pressure
- Voltage
- Current
- Frequency
- Power
- Excitation current
- Speed
- Alarm
Local Control Desk
Local Control Desk is provided for monitoring pressure and thermal parameters of the running engine. Also starting, stopping and speed control of engine is possible in local control operation mode. It is located near the engine.
Major Components in Local Control Desk
1) Pressure gauges, switches
Lube oil filter inlet pressure
Lube oil filter outlet pressure
Lube oil in cylinder head inlet pressure
Cooling water pressure
2) Temperature indication
Cylinders cooling water temperature scanner
Cylinder cooling water outlet temperature measurement system with Cu50 thermo resistor for each cylinder and scanned by a multi-channel meter.
Engine exhaust temperatures scanner
Pyrometric exhaust gas system with thermocouple for each cylinder and turbocharger, and scanned by a multi- channel meter.
Lube oil engine inlet /outlet temperature
Water engine inlet/outlet temperature
3) Engine RPM indicator with cranking and over speed protection.
4) Push buttons, indicating lamps, selector switches
- Common engine alarm
- Engine start permission
- Local / remote mode select
- Engine start / stop
- Flasher off
- Engine speed raise / low
- Emergency stop
4.12.4 Protection system
4.12.4.1 Diesel engine
The diesel engine will stop automatically in case of the following failures:
- Very low lube oil pressure
- Very high water engine outlet temperature
- Engine over speed
The diesel engine will alarm automatically in case of the following failures:
- Low lube oil pressure
- Low water pressure
- High lube oil temperature
- High water temperature engine inlet
- Alternator bearing temperature high
4.12.4.2 DG electricity system
The generator adopts digital integrated relay protection system for monitoring and protection.
A DMR362 digital integrated relay is installed on generator switchgear, which is used for alternator protection, switch control, monitoring, measuring, display and SOE record.
The following functions are configured on the relay:
- Differential current
- Reverse power
- Instant trip current
- Voltage locked over current:
- Over current
- Over load
- Earth failure
- Over voltage
- Under voltage
- Low frequency
- Over frequency
5. Main equipments specifications
5.1 Diesel engine:
Model |
GN8320ZD8 |
Type |
Inline, four-stroke, direct injection, turbocharged and after cooled |
Quantity |
1 set |
Rated power |
2206kw |
Rated speed |
600r/min |
Bore/stroke |
300/380mm |
Starting method |
Compressed air |
Cooling system |
Open water cooling |
Dimension |
5620x1620x2760mm |
Weight |
25000kg |
Manufacturer |
Nb Power ry Group Co., Ltd |
5.2 Alternator
Model |
TFW-900 |
Type |
Brush-less synchronous alternator |
Quantity |
1 set |
Rated power |
2500KVA |
Rated speed |
600r/min |
Rated voltage |
400V |
Frequency |
50HZ |
Power factor |
0.8 lagging |
Insulation class |
B/F |
Excitation |
AVR |
Dimension |
3480×2150×2150mm |
Weight |
16000kg |
Manufacturer |
Nb Power ry Group Co., Ltd |
5.3 Heavy fuel oil centrifuge
Model |
KYDB202SD-23 |
Quantity |
1 set |
Rating treatment L/h |
1000 |
Centrifuge Temperature |
90-98°C |
Light phase output pressure |
0.2MPa |
Motor power KW |
3P/400V/50Hz/7.5kw |
Complete machine weight |
2000kg |
Dimension |
2400*1250*1800 |
Material medium |
Heavy fuel oil (380CST) |
Manufacturer |
Nb Power ry Group Co., Ltd |
5.4 Common Circulating & Booster module
Model |
CRGD-1.0 |
Fuel feed capacity |
1 m3/h |
Fuel circulating capacity |
1.6m3/h |
Fuel supply pressure |
0.2Mpa |
Fuel feed pressure |
0.4Mpa |
Max. fuel temperature |
135°C |
Rated fuel temperature rise |
4-5°C/min |
Viscosity before engine inlet |
9-13 cSt |
Viscosity deviation |
±1.5cSt |
Viscosity steady time |
Max. 3.5 mins |
Viscosity control accuracy |
Max. 3% |
Primary filter |
80 mesh/inch2 |
Fine filter |
Max. 10-30µ |
Power source |
3P 380V 50HZ |
Power |
7.5kW |
Load |
5kW |
Manufacturer |
Nb Power ry Group Co., Ltd. |
5.5 Exhaust Gas Boiler
Model |
LFL67-0.7 |
Rate steam capacity: |
500kg/hr |
Quantity |
1 set |
Steam pressure: |
7Bar |
Steam temperature |
170°C |
Safe pressure |
0.75Mpa |
Heating area |
67m2 |
Boiler back pressue |
Max. 220pa |
Waste gas inlet temperature |
350°C |
Waste gas outlet temperature |
200°C |
Overall dimensions LxWxH |
Ø1316x3430mm |
Weight |
3000kg |
Manufacturer |
Nb Power ry Group |
5.6 Air compressor
Model |
CZ-20/30F |
Type |
Single row vertical, differential piston two-stage compression, air cooled |
Exhaust capacity |
Min. 20m3/h |
Quantity |
1 set |
Rating pressure |
3MPa |
Cylinder bore |
1st stage: 102mm, 2nd stage: 90mm |
Piston stroke |
65mm |
Exhaust temperature |
Max. 85°C |
Rotary speed |
1000r/min |
Shaft power |
<5kW |
Motor |
Y132S-6/5.5kW |
Overall dimensions |
970x440x700mm |
Weight |
155kg |
Manufacturer |
Nb Power ry Group Co., Ltd |
5.7 Air receiver
Model |
B500/3.24 |
Quantity |
1 set |
Air inlet & outlet |
�?/SPAN>33 |
Design pressure |
3.24MPa |
Working pressure |
2.94Mpa |
Max working temperature |
<80°C |
Volume |
500L |
Manufacturer |
Nb Power ry Group Co., Ltd |
5.8 Cooling tower
Model |
GBL-100 |
Quantity |
1 set |
Cooling capacity |
100M3/H |
Inlet water pressure |
34 kpa |
Temperature reduce |
5 - 10°C |
Fan power |
5Kw |
Net weight |
1800kg |
Manufacturer |
Zhejiang Lianf |
|