BBS  Email&MSN: [email protected]
  
Homepage   |   Power Generation   |   Top Spare parts   |   spare parts   |   China OEM Equipment and Spare Parts   |   Project Financing    |   Equipments   |   China Small EPC Contractor   |   Transmission   |   Financing-Ebook   |   Contact Us   |   Used Equipment   |   download   |   sitemaps   |   Project-Equipment-Parts-Enquiry   |   供货商Supplier   |   Exchange Link   |   Breaking News  

Mail List

E-mail:

Power Generation
     Big Power Plant Projects  
     GE Gas Turbine Power Plant Project  
       3x42mw gas turbine plant proposal  
     15MW Heat recovery plant GE 6B Gas Turbine Plant  
     200mw Coal Fired Plant  
     600mw ultra super critical power plant  
     1500mw GE gas turbine plant  
     3x750mw Gas Turbine Combined Cycle Power Plant  
     360000 M3/D Sea Water Desalination  
     geothermal power plant  
       Work Scope  
       Design Data  
       Steam Turbine  
       Cooling System  
       Water System  
       Ventilation  
       Instrumentation Auto.  
       Electrification  
     Diesel power Plant  
     waste heat recovery power plant  
       4.5MW Waste heat recovery 2500t/d Cement Line  
       7.5MW Waste heat recovery 2x2500t/d Cement Line  
       9MW Waste heat recovery 5000t/d Cement Line  
       18MW Waste heat recovery 2x5000t/d Cement Line  
       Technical Proposal of 9MW Recovery Plant  
       Power Plant Connection and Main Equipments  
       Main Equipment Recovery Plant  
       Power Plant Construction Schedule  
       China Reference List waste heat Plants  
       Preliminary Proposal for Cement Plant  
     Thermal Power proposal  
     Questionnaire for Gas/HFO/Liquid Fuel Power Plant  
     Check-List-for-quotation-on-power-plant  
     Power project reference  
       Thermal plant List  
       Foreign Small plant  
       Reference of Sinomach  
       Diesel generator plant list   
       waste heat recovery power plant list  
       Gas Turbine Power plant Reference  
     Indicative quotation of 2x50MW coal fired plant  
     Estimated Quotation for Plant  
     China large scaled industry power project  
     Biomass-Gasification-Power-Generation-System  
     Gas Engine Generator power plant  
       Proposal quotation of 2x2.6mw gas engine generator  
       500kw-5200kw gas engine generator series  
       500kw-5500kw Gas-Duel fuel diesel Generator  
       well-known-diesel-generator-set-and-Gas-genset  
     Solar-Panel-Power-Plant-Quotation  
     China top conveyor belt for power, mining, port  
     Environment-friendly-solar-power-plant  
     China-the-most-famous-gas-engine-generator-sets  
       Natural-Gas-Genset  
       Biogas-Genset-Landfill-gas-Generator-set  
       Coal-Mine-Gas-Genset  
       Biomass-Genset  
       Coal-Gas-Producer-Gas-Genset  
       Low-BTU-Gas-Genset  
       Gas-Engine  
     3mw-and-4mw-gas-genset-by-CNPC-produce  

Diesel Generator Proposal

Power Plant Proposal
Required Information for Power Plant Project design and quotation

Home > Power Generation > 3x750mw Gas Turbine Combined Cycle Power Plant


Google

1.0    Project Concept
1.1 Power Plant Planning and Capacity of Units
The Power Plant planning capacity of XXXXX CPDO is 3x750 MW class, which comprising three phases: one set of nominal 750 MW class output natural gas/light diesel oil fired Combined Cycle units will be built in phase 1, and another two sets of nominal 750 MW class output natural gas fired Combined Cycle units will be built in phase 2 and phase 3. And the additional expansion is possible.
1.2    General Layout
1.2 Power plant general layout
The whole site is separated into four parts, they are main power block building area, switch gear equipment area, auxiliary production area and plant front area.
Main power block building area is arranged in the central area, it consists of steam turbine house, gas turbine generation unit, heat recovery steam generator and electrical building. The north area of the plant is reserved for the extension purposes. Switch gear equipment area consists of transformer yard and 220kV GIS. The switch gear equipment area, rain water drainage pump house and starting boiler house are arranged east to the main building area. Plant front area is arranged south of main building area, this area consists of the following items: production overall building, mess hall, bathroom, rest room for night shift, warehouse and maintenance building. And gas regulator station is arranged east of the plant front area. Auxiliary production area is arranged in the west, this area consists of the following items: combined water treatment station, chemical water treatment station, sewage water treatment house, industrial waste water treatment station and hydrogen generation plant.
To the first phase, the plant is about 280m across from north to south and about 360m from east to west, the area of power plant is 8.30 hm2.
1.3 Main Equipment Selection
Due to the capacity of the phase 1 and phase 2 and phase 3 are the same, the same main equipment are selected for the phase 1 and phase 2 and phase 3 for the convenience of the design, installation, operation, maintenance, BOP and spare parts.
1.3.1 Plant Performance
One set of S209FA gas-fired combined cycle unit is installed in each phase, the estimated plant performance for XXXXX CPDP Project is seen in the table 5- 4.
The following assumptions, guidelines, and criteria govern this analysis.
- Performance will be based on a 2x1 General Electric PG9351(FA) combined cycle operating on natural gas from the “City Gas�?
- Performance is based on new and clean equipment operating at ISO conditions; 15�?(59°F), 60 percent relative humidity, mean sea level.
- GT performance is based on estimated performance of the 9FA operating on natural gas with a dry low nitrogen oxides combustion system.
- The design characteristics of the Natural gas are given in table 1.3-2.
- The gas line pressure is 7 bar which is not sufficient for the GE 9FA. The 9FA requires a minimum gas pressure of 3.25 MPa, so, gas Compressors are necessary to rise the gas line pressure.
- The cooling water temperature is provisional 15°C.

Table 1.3-1
Performance Summary Table
Plant Performance at ISO Conditions Burning Natural Gas of the “City Gas�?/DIV>
New and Clean Plant Performance �?GE 9FA Combustion Turbine
Ambient Temperature, �?
15
Relative Humidity, %
60
Fuel
City Gas
 
CTG Output (each), kW
254, 912
Number of CTGs Operating
2
Total CTG Output, kW
509, 824
Steam Turbine Output, kW
274, 583
Gross Plant Output, kW
784, 407
Auxiliary Power, kW
14, 976
Net Plant Output, kW
769, 431
Gross CTG Heat Rate (LHV), kJ/kW.h
6, 393
Gross CTG Heat Rate (HHV), kJ/kW.h
7, 076
Net Plant Heat Rate (LHV), kJ/kW.h
6, 517
Net Plant Heat Rate (HHV), kJ/kW.h
7, 214
Net Plant Efficiency (LHV),  %
55.24
Net Plant Efficiency (HHV),  %
49.904
Notes:
1)    Performances are based on a three-pressure, reheat, and combined cycle using a deaerating condenser.
2)    The gas turbines are using DLN combustors to control NOx.
        
1.3.2 Fuel
Natural gas will be used for the project. The composition analysis of natural gas is listed in Table 1.3-2.
Characteristics of the Fuel Gas to be Used by the Power Plant :                                                 
                     Table 1.3-2. natural gas Composition
Percent by Weight
Percent by Volume
Composition
0.62
0.385
Nitrogen
1.72
0.688
Carbon Dioxide
84.49
92.766
Methane
7.03
4.117
Ethane
3.03
1.211
Propane
1.74
0.529
Butane
0.68
0.165
Pentanes
0.67
0.138
Hexanes
0.02
0.001
Heptanes Plus
 
Value
Parameter
17.57
Molecular weight
0.742 (0.0046)
Density gm/liter (lb/ft3) @ 60 F and 14.696 psia
 
Higher heating value:
12,809 (23,056)
    kcal/kg (Btu/lb)
9545 (1072.6)
    Kcal/kg (Btu/ft3) @ 60 F and 14.696 psia
10,060 (18,103)
    Sulfur content, ppm (max)
According to the above fuel gas, the Natural gas consumption is given in the following Table.
 
item
Unit
Value
1
One set of 2´1 CC
Kg/s
25.97
2
Two set of 2´1 CC
Kg/s
51.95
3
Three set of 2´1 CC
Kg/s
77.92
 
1.3.3 Main equipment
The proposed gas-fired combined cycle plant consists of two gas turbines, two heat recovery steam generators and one steam turbine. The combustion turbines exhaust into separate heat recovery steam generators (HRSGs), which produce steam to drive the single condensing steam turbine (ST).  Steam exhausted from the steam turbine is condensed in a deaerating condenser.  The condenser rejects its heat through a circulating once-through seawater system.
1.3.3.1 Gas Turbine
The GT used for the performance runs is the General Electric (GE) PG9351(FA) (9FA), equipped with a hydrogen cooled generator.  The 9FA is derived from the GE 9F CTG of 50 Hz, heavy-duty type GTs.  The 9FA GT consists of a 15.8-stage axial flow compressor and a 3-stage reaction type turbine.  In addition, the 9FA uses horizontally split casings and a cold end drive generator.
1.3.3.2 Heat Recovery Steam Generator
The HRSGs are designed to recover heat from the exhaust gas of the gas turbines and produce steam for use in the steam turbine. Each HRSG is an unfired, three-pressure, reheat, natural circulation type with horizontal gas flow and vertical fin tubes in all sections.
Each HRSG is arranged with a high-pressure (HP) superheater, reheater sections, HP drum, HP evaporator, high temperature and low temperature HP economizers, intermediate-pressure (IP) superheater, IP drum, IP evaporator, IP economizer, low-pressure (LP) superheater, LP drum, LP evaporator, LP economizer, and an exhaust stack. Three 50 percent capacity boiler feed pumps with interstage bleeds are included to take suction from the LP drum and pump through the HP and IP HRSG sections. Each exhaust gas stream passes through a stack to the atmosphere.
To eliminate the concern of exhaust gas condensation on the LP economizer tubes the condensate inlet temperature is controlled using an LP economizer recirculation loop. A recirculation pump is provided to pump a fraction of water from the LP economizer outlet to the LP economizer inlet for temperature control.
The ductwork and casings are designed to achieve the required outer face temperatures. Platforms, stairways, and ladders provide access to the drums, instrumentation, and valves. Access doors facilitate inspection and maintenance of the ductwork and/or heat exchanger modules.
1.3.3.3 Steam Turbine
The steam turbine is a horizontally split, multi-stage, condensing, reheat, dual flow, down exhaust steam turbine, which is directly coupled to a 3, 000 rpm generator. The steam before the main steam entrance valve of the steam turbine is designed to operate at throttle conditions of 12.4 MPa/566°C and in a sliding-pressure mode. The steam turbine also has a low-pressure admission. The steam turbine has standard accessories including a lube oil system, digital electro hydraulic control (DEHC) system, turning gear, and a gland steam condenser. The steam turbine, steam turbine generator, and condenser will be housed in a steam turbine building.
1.3.3.4 Condenser and Vacuum equipment
Heat rejection for a set of S-209FA combined cycle in this project is accomplished by circulating cooling water through the deaerating condenser. The cooling water is obtained from the Nile River. The cooling water flow rate is 12, 480 kg/s with a 10°C temperature rise. The cooling water flow rate includes auxiliary cooling water, which is approximately 5 percent of the total cooling water flow.
The condenser air removal system creates and maintains vacuum in the shell side of the main condenser by removing air and noncondensable gases. Noncondensables will be removed and condenser vacuum will be maintained using liquid ring vacuum pump.
Steam entering the condenser is deaerated as it condenses to the hot well which supplies deaerated condensate to the suction of the condensate pumps. For low load operation, sparging steam is supplied to the condenser if necessary to maintain proper oxygen levels.
1.3.4 Main Equipment Performance
The main equipment performance of S-209FA is based on 15 °C, 60 percent relative humidity, mean sea level with cooling water temperature of 15 °C, new and clean equipment, and operating on natural gas from the “City Gas�?with a dry low nitrogen oxides combustion system for NOx control.
Gas Turbine:  ( Two sets )
 
Model:
GE 9351 FA
Rated output: (each)
254.912 MW
Rated rotating speed:
3000 r/min
Rated exhaust gas flow: (each)
2383 t/h
Rated exhaust gas temperature:
607°C
 
 
Gas turbine generator: ( Two sets )
 
Rated capacity:
254.912 MVA
Rated rotating speed:
3000 r/min
Cooling mode:
Water-hydrogen-hydrogen
 
 
HRSG: ( Two sets )
 
Model:
Three-Pressure, reheat, natural circulation, horizontal
The outlet flow of HP steam: (each)
270.75 t/h
The outlet temperature of HP steam:
568 �?/DIV>
The outlet pressure of HP steam:
12.65MPa
The outlet flow of IP reheat steam: (each)
310.55 t/h ( incoming flow of reheat steam 263.8 t/h, producing IP additional steam of 46.75 t/h )
The outlet temperature of IP steam:
568�?/DIV>
The outlet pressure of IP steam:
2.898 MPa
The outlet flow of LP steam: (each)
59.15 t/h
The outlet temperature of LP steam:
290 �?/DIV>
The outlet pressure of LP steam:
0.3619 MPa
Inlet flue gas temperature:
607 �?/DIV>
Outlet flue gas temperature:
93 �?/DIV>
Inlet flue gas flow:
2383 t/h
 
 
Steam turbine: ( One set )
 
Model�?/DIV>
HP, reheat, three cylinders, down exhaust, single shaft, condensing
Rated rotating speed:
3000 r/min
Rated output:
274.583MW
Inlet pressure of HP steam turbine:
12.4MPa
Inlet temperature of HP steam turbine:
566 �?/DIV>
Inlet flow of HP steam turbine:
541.5 t/h
Inlet pressure of IP steam turbine:
2.76MPa
Inlet temperature of IP steam turbine:
566�?/DIV>
Inlet flow of IP steam turbine:
621.1 t/h
Inlet pressure of LP steam turbine:
0.3351 MPa
Inlet temperature of LP steam turbine:
288�?/DIV>
Inlet flow of LP steam turbine:
118.3 t/h
Steam turbine back pressure
6.89 kPa
 
 
Steam turbine generator: ( One set )
 
Rated capacity:
274.583 MVA
Rated rotating speed:
3000 r/min
Cooling mode:
Water-hydrogen-hydrogen
 
 
Gross plant output of Combined Cycle:
784, 407 MW
Auxiliary power:
14, 976 MW
Net plant output:
769, 431 MW
Net plant heat rate:  (LHV)
6, 517 kJ/kW.h
Net plant heat rate:  (HHV)
7, 214kJ/kW.h
Net plant efficiency: (LHV)
55.24 �?/DIV>
Net plant efficiency:  (HHV)
49.904�?/DIV>
 
1.4 Thermal System
The thermal system is based on multi-axis S-209FA combined cycle for each phase, including: two sets of gas turbines, two sets of HRSGs and one steam turbine.
Air is compressed by the compressor which is on the same shaft with the gas turbine, then it enters the combustion chamber and mixes with the natural gas, the high temperature flue gas produced from combustion of the mixture gas drives the gas turbine. The flue gas from the gas turbine goes to the HRSG for the heat exchange, then passes through the stack to atmosphere. The high temperature flue gas also can pass through a bypass stack to atmosphere to meet the rapid startup requirement.
The steam and water processes are as follows: The feed water from the HRSG LP economizer is split into the two parts. One part is pumped to the fuel heater through the recirculating pump, another part is fed to the LP steam drum and forms the natural circulation in the LP evaporator section by gravitation. Water from the LP evaporator section is supplied through an interstage bleed feed water pump into two parts. The IP part is first fed to the IP economizer, then to the IP steam drum and form the natural circulation in the IP evaporator section by gravitation. The HP part is first fed to the HP economizer, then to the HP steam drum and form the natural circulation in the HP evaporator section by gravitation. HP steam produced from the HP steam drum is heated in superheater, then supplied to the HP steam turbine. The exhaust steam from the HP steam turbine is mixed with the IP steam produced from the IP steam drum, then enters the IP reheater before it goes to IP steam turbine. The exhaust steam from the IP steam turbine is mixed with the LP steam produced from the LP steam drum and heated in LP superheater, then enters the LP steam turbine. The steam turbine exhausts steam downward to a deaerating condenser. The condensed water from the condenser is supplied to the condenser pump and mixed with the condensate from the fuel heater, then goes to the LP economizer, a steam water cycle is thus completed.
1.4.1 Main Steam System
The main steam system will convey HP steam from the two sets of HRSGs to the HP steam turbine. The main steam system will be provided with bypass of main steam flow to the cold reheat system during startup, shutdown, and sudden load changes. The pressure and temperature of the main steam will be reduced with a combination pressure reducing and desuperheating valve before the steam enters the cold reheat piping. The boiler feed system will provide desuperheating water.
1.4.2 Reheat System
The reheat system consists of hot reheat and cold reheat steam piping. The cold reheat piping transports steam from the exhaust of the HP steam turbine to the reheater sections of the HRSGs. Cold reheat also receives steam from the intermediate pressure superheater on each HRSG. The hot reheat steam piping conveys the reheated steam from the HRSGs to the intermediate pressure steam turbine.
The reheat steam system will be provided with bypass of reheat steam flow to the condenser during startup, shutdown, and sudden load changes. The pressure and temperature of the reheat steam will be reduced with a combination pressure reducing and desuperheating valve before the steam enters the condenser. The boiler feed system will provide desuperheating water.
1.4.3 Low Pressure Steam System
The LP steam system will convey LP steam from the HP steam turbine and the HRSGs to the LP steam turbine.
The LP steam system will be provided with bypass of LP steam flow to the condenser during startup, shutdown, and sudden load changes. The pressure and temperature of the LP steam will be reduced with a combination pressure reducing and desuperheating valve (if required) before the steam enters the condenser. The boiler feed system will provide desuperheating water (if required).
1.4.4 Condensate System
Condensate pumps will take suction from the condenser hot well through suction strainers. Condensate will be pumped from the hot well by the condensate pumps, through the gland steam condenser and the HRSG LP economizers before reaching the LP drum. Condensate regulator control valves will control the water level in the LP drum.
1.4.5 Boiler Feedwater System
The boiler feedwater system will take water from the LP drum of the HRSGs and supply the HP and IP economizer sections of the HRSG. The water from the feedwater pump outlet is fed to the HP economizer. The IP feedwater using an interstage bleed from the pump at the required pressure is fed to the LP economizer. The boiler feedwater system will also supply desuperheating water to all the desuperheaters within the plant.
1.4.6 Circulating Water System
The steam turbine exhausts steam downward to a condenser. The condensing system will receive steam from the steam turbine and condense it using sea water from the circulating water system as the cooling medium. The condenser air removal system creates and maintains vacuum in the shell side of the main condenser by removing air and noncondensable gases.
The circulating water is pumped from the intake structure pond through the condenser and closed cycle cooling heat exchangers and discharged to the Nile River.
1.4.7 Auxiliary Cooling Water System
The Auxiliary Cooling Water System removes heat from the Closed Cycle Cooling Water System via the closed cycle cooling water heat exchangers.
During normal operation the Circulating Water System will supply cooling water to the closed cycle cooling water heat exchangers. After passing through the heat exchangers, the auxiliary cooling water will be discharged into the Circulating Water System downstream of the condenser discharge iso­la­tion valves
1.4.8 Closed Cycle Cooling Water System
The Closed Cycle Cooling Water System provides a clean source of cooling water to the mechanical and fluid systems requiring cooling. This cooling water is provided by circulating water through the closed cooling water heat exchangers which are cooled by the Circulating Water System.
1.4.9 Demineralized Water Makeup and Storage System
The Demineralized Water Makeup and Storage System will supply demineralized water for the condenser, and the combustion turbine wash and closed cooling water system.
Makeup water can enter the condenser by either pump or gravity.
1.4.10 Compressed Air System
Air compressors will provide control and service compressed air for the power island and chemical water treatment portion of the plant.
1.4.11 Boiler Vents and Drains System
The boiler vents and drains system will take all operating and maintenance vents and drains from the HRSG and convey them to the appropriate location. High pressure HRSG operating drains will be taken to the flash expander before entering the plant drains system. Low temperature HRSG drains will be taken directly to the plant drains system.
1.4.12 Emergency Diesel Generator
The emergency diesel generator is used to bring the plant in an orderly manner in the event of a plant trip. Black start capability has not been included. Electrical power requirements for starting the plant up will be taken from the grid.
1.5 Gas System
The fuel of the project is natural gas. Natural gas will be transported to the site via a gas pipeline operated by "City Gas". At the outlet of the reducing gas station, the gas pressure is 7 bar. The gas line pressure is not sufficient for the GE 9FA which requires a minimum gas pressure of 2.79 MPa (405 psia), so, gas Compressors are needed to rise the gas line pressure.
As the fuel supply system is relatively reliable, no gas tank is provided inside the plant. A totaling flow meter will be supplied to measure gas consumption of each gas turbine.
A gas-operated (spring closing) valve will automatically isolate the fuel gas lines coming into the turbine generator building when a fire is detected on the gas turbines or in the building. A solenoid valve will then vent the gas in the line outside the generation building.
 
 


1.6 Electrical System
1.6.1 General Description
The combined cycle generating units rated 1x750 MW class will be installed in this project. One combined cycle generating unit 750 MW class will be installed consisting of 2 (two) sets of gas turbine generators and 1 (one) set of steam turbine generator. There is a possibility to extend the next phase.
1.6.2 Electrical Main Connection
Because there is lack of the grid parameters, this period the scheme of the electrical main connection is assumed as follows: The generator shall be stepped up and connect to the high voltage (230kV) switchyard bus through a main transformer, each generating units shall adopt the generator-transformer unit connection. 3 (Three) generator-transformer units will be all connected into 220kV bus, which is double busbar connection. There are two 220kV outgoing transmission lines.
Stand-by Transformer shall be equipped as stand-by power supply of unit auxiliary power system. Stand-by Transformer will be connected into 220kV bus. At the terminal of each gas turbine generator there will be one generator breaker.
1.6.2.1 Turbine Generator Bus Duct
The Turbine Generator Bus Duct System provides a path for transfer of power from each turbine generator to the step-up transformer. The system will consist of the following major com­ponents:
    Isolated phase bus duct.
    Bus duct supports and hangers.
    Tap isolated bus connections to the unit auxiliary transformers.
    Tap isolated bus connections to the generator outlet surge protection cabinet and potential transformer cabinet.
    Connections with generator breaker.
The bus duct assembly will be rated to accept the full peak output of the generator over the entire ambient temperature range.
Tap bus connections are provided to connect the high voltage winding of each unit auxiliary transformer, the generator surge protection, and the potential transformer cabinet.
1.6.2.2 Generator Breakers
The generator breaker provides the means to synchronize the generator output to the substation and disconnect the generator from the system in the event of a fault or other damaging condition.
The gas turbine generator breakers will be the indoor SF6 or vacuum insulated type. The breakers will be provided with a manually operated disconnect switch for main­tenance purposes.
Because no circuit breakers at the terminal of the steam turbine generator will be installed, synchronization and trip of the generator from power system will be realized by high voltage side breaker of the steam turbine generator.
1.6.2.3 Generator Step-Up Transformers
The Generator Step-Up Transformer System will consist of the following major components:
    Generator step-up transformer for each generator.
    Protective relay panels
The generator transformers will be two windings with grounded wye connections for the high voltage and delta connections for the low voltage windings. The transformer is cooled with forced and oil-air cooling system (ODAF). The transformer rating will be selected with sufficient capacity to carry the maximum expected generator output over the full ambient range. Surge arresters will be pro­vided at the high voltage bushing to protect the transformer from surges on the 220 kV systems resulting from lightning strikes or other sys­tem dis­turb­ances.
The transformers will be set on concrete foundation. Oil containment will be pro­vided as part of the Oil Spill Prevention System. Fire detection and prevention will be provided using an automatic spray fire-fighting system.
1.6.3 Type Selection of 220kV Switchgear
SF6 gas insulated enclosure type combined switchgear (GIS) will be adopted for the 220kV switchgear. Its advantages are: compact structure, small ground area (compared with other forms of switchgear); preventing pollution and corrosion and ensuring safe operation of the plant. Its disadvantage is: equipment investment will be higher.
1.6.3.1 220 kV Switchgear and Connections to Grid
The 220 kV Gas Insulated Substation (GIS) Switchgear System will serve as the primary power flow switching interface between the generator step-up transformers and the 220 kV power system.
The Switchgear System will consist of the following major components:
    SF6 Circuit Breakers
    Current Transformers
    Voltage Transformers
    Isolating Switches
Lightning arresters
The 220 kV Switchgear System will be an outdoor GIS design.
Connections from the generator step-up transformers to the switchyard will be of ACSR overhead conductors.
1.6.4 Auxiliary Power System
The auxiliary power source of each combined cycle gas unit will be got by two medium voltage (MV) auxiliary transformers connected separately to the LV sides of two step-up transformers of two gas turbine generator units. The whole unit will be supplied by these two MV auxiliary transformers. The voltages of auxiliary power system will be 6kV and 380V; the neutral of 6kV system will be grounded by resistance; the neutral of 380V system will be solidly grounded.
1.6.4.1 AC Auxiliary Power Supply (6kV)
The AC Auxiliary Power Supply (6kV) System provides power source to 6kV plant auxiliaries. The system will consist of the following major com­po­nents:
    Two-winding delta, wye generator kV/6.3 kV units of oil insulated auxiliary trans­formers with ±8 x 1.25 percent on-load tapping range, as required.
    Neutral grounding resistor on the secondary of each unit auxil­iary trans­former as required.
    6kV metal-clad switchgear with metal-enclosed vacuum circuit breakers, as required.
    6kV nonsegregated phase bus duct.
The sectionalized single bus connection will be adopted by AC Power Supply (6kV) System. 6kV power system will be supplied by two unit auxiliary transformers and Stand-by transformers. The secondary winding (6.3 kV) of the unit auxiliary transformers will be low resistance grounded to limit the maximum line to ground fault current to less than 200 amps. The 6kV switchgear will distribute the power through electrically oper­ated circuit breakers to the various 6kV loads.
Loads to dual auxiliaries will be distributed between the two sections of the 6kV switchgear so that loss of a single unit auxiliary transformer will not result in complete loss of function.
The two unit auxiliary transformers will be sized to provide power for the auxiliary electrical equipment and will have ratings for both natural and forced air cooling at 65°C temperature rise as per IEC-76. Each unit auxiliary transformers will be sized to carry the entire plant auxiliary load at rated capacity.
The auxiliary transformer will be equipped with on-load tap changes. During unit startup the auxiliary power supply to the plant is from the grid through the unit transformer while the generator breaker is open.
The Stand-by transformer will be set to provide the stand-by power of 6kV switchgear. The rated capacity of the Stand-by transformer is equal to the rated capacity of the auxiliary transformer.
1.6.4.2 AC Auxiliary Power Supply (380/220 V)
The AC Auxiliary Power Supply (380/220 V) System provides solidly grounded 380/220V three-phase four wire power for 380V motor loads and other 380/220V loads. The system will consist of the following major com­ponents:
    6.3/0. 4kV low voltage auxiliary trans­formers.
    380/220V three-phase, four-wire power center (PC), as required.
    380/220V three-phase, four-wire motor control centers (MCC), as required.
There are two section of buses for AC power supply (380/220V). Each bus will be sectionalized by section circuit breaks. Each bus is supplied by two low voltage auxiliary trans­formers which are standby for each other. There are four low voltage auxiliary transformers for 380V power system.
The low voltage auxiliary transformers will be with ±2 x 2.5 percent no-load tapping range. Each transformer will be of dry type or cast coil and have both natural cooled and fan cooled ratings. The secondary of the transformers will be wye con­nected and solidly grounded to ground detection equipment.
Metal-clad air circuit breakers will be con­nected to the main bus to distribute 380V three-phase power to motor control centers and intermediate size motor. Each load served from 380V breaker will be provided with individual ground fault protection device to assure high availability.
MCCs will be energized from 380V PC. MCCs will provide power to continuous 380V loads, intermediate 380/220V loads and HVAC loads.
1.6.4.3 DC Power Supply
The DC Power Supply System provides a reliable source of power for critical control and power functions during normal and emergency plant operat­ing conditions. This will include the normal source of power for the Uninterrupted Power System (UPS).
The DC system is equipped with storage batteries, battery chargers and DC distribution panels. The DC system supplies DC power for relay protection, control system, and emergency for personnel disperse.
DC power system consists of the following major components:
     220V sealed, ungrounded lead acid battery. (Low volatile, valve controlled battery utilizing immobilized electrolyte may be preferred.)
    SCRF filtered silicon controlled rectifying chargers
    DC distribution panels.
Two DC systems will be provided for the plant.
The systems will be for the general plant loads those require 220V DC power. The loads will include control power for the 220 kV and 500 kV step-up substations,  6.3kV switchgear, Low voltage auxiliary transformers, generator step-up transformers, unit auxiliary transformers, various control panels, the steam turbine DC lube oil pump, and emergency seal-oil pump. The systems will be for the Uninterrupted Power Supply.
Each battery charger will receive 380V, three-phase, AC power from the AC Power Supply (380 V) System and continuously float charge each battery unit while simultaneously supplying power to the DC loads. A ground detection scheme will be provided to detect grounds on either polarity of the DC Power Supply System for annunciation in the control room.
Each battery and the battery charger system will be connected through a DC distribution panel. DC loads will be fed from individual CBs in the DC distribution panels.
1.6.4.4 Uninterruptied Power Supply
The Uninterrupted Power Supply (UPS) provides 220V AC, single-phase, 50 hertz power to the DCS, essential instrumentation and equipment loads that require uninterrupted AC power. The system will consist of the following major com­ponents:
    220V, single-phase, 50 hertz in­verters.
    Solid-state static transfer switch.
    Manual bypass switch.
    UPS AC distribution panel (for distribution of 220V AC essential service power).
    AC source of power.
    220V DC battery with chargers.
The full-capacity inverters will be connected to the 220V AC panel boards through a static transfer switch and a manual bypass switch. Protecting, mon­i­tor­ing, regulating, and phasing devices will be included on the inverter for normal DC input from the DC power supply. During normal opera­tion, the inverters will supply the essen­tial AC loads.
Solid-state switches connected to the output of the inverters will con­tinuously moni­tor both inverter outputs and the AC source and will maintain synchronism. The static switches will auto­matically transfer essential AC loads in less than 0.25 Hz without interruption from the normal or inverter output to the AC source upon loss of inverter output.
A manual bypass switch will be provided to enable isolation of the inverter and static switch from service for testing and main­tenance without interruption to the Essential Service AC System loads.
Loads will be connected to the UPS through the UPS distribution panel boards.
1.6.5 Control Mode
There will be centralized boiler-turbine-generator central control room (CCR) for each unit and two local control rooms (LCR) for gas turbine generators. Electrical equipment controlled in CCR will be: 220kV transmission line CBs, main transformer incoming CBs, auxiliary power system CBs, etc.; CBs at the terminals of gas turbine generator units will be controlled in CCR. Distributed Control System (DCS) will be adopted for the control of the whole plant. Relevant instrumentation, relay protection and automatic devices will also be installed in CCR. Microcomputer type protection will be adopted.
1.6.6 Layout of Electrical Equipment
Main transformers, MV auxiliary transformers and 220kV switchgears (GIS) will be laid out of A row of turbine house in the plant. MV and LV switchgears will be laid in main machine hall and auxiliary workshop.
1.6.7 Earthing
The Earthing System provides an adequate path to permit the dissipation of earth fault currents, lightning, and switching surges for protection of plant personnel and electrical equipment.        
All outdoor equipment that may be contacted by operation personnel, such as metal enclosures, cabinets, boxes, steel structures, and fencing will be solidly connected to the grounding system. The switchyard area will be fenced and covered with a crushed aggregate surfacing above the ground for personnel safety.
The Earthing System will consist of the following major components:
    Earth grid and earth loop conductors with terminals for attach­ment to metallic structures and selected equipment.
    Earth rods or earth detecting wells.
    Earthing conductors to equipment.
An earth grid system consisting of bare stranded copper conductors exothermal welded to copper-clad earth rods or earth wells will be installed to provide a low resistance path to earth for fault currents, lightning strikes, and other electrical current surges. The earth grid will be buried beneath and around all major plant buildings and structures. The number, location, and depth of the earth rods or earth wells will be determined by the soil conductivity and subsurface structural properties of the plant site.
1.6.8 Lightning Protection
The Lightning Protection System will protect buildings and equipment from lightning damage.
The Lightning Protection System will consist of the following major components:
    Lightning rod
    Down Conductors.
    Copper or Brass Plate.
The Lightning Protection System will consist of lightning rods installed on the top of important buildings and equipment. The design will be in accordance with NFPA 780, UL 96A, and applicable Chinese National Standards. The structures requiring lightning protec­tion will be determined during detailed design.
1.6.9 Raceway
The Raceway System provides support and protection for electrical power and control circuits between various pieces of equipment, devices, and cabinets.
The Raceway System will consist of the following major components:
    Cable tray.
    Conduit.
    Duct bank.
    Cable race.
    Buried duct.
    Junction and pull boxes.
Components of the Raceway System shall be separated according to different classifications and standards of cables as required to avoid electromagnetic interference.
1.7    Control System
1.7.1 Control mode and control bu, ilding
The plant will take the centralization control mode. The local control cabinets located near to the CTs will also be provided for pure gas turbine cycle operation during commissioning.
The make-up water system, chlorinating with electrolysis of sea water system, waste water system, hydrogen generati, , ng system and compressed air system etc. will also take the centralization control mode. Only facilities only for start-up and commissioning will be provided in local room of the relative auxiliary systems.
1.7.2 Automatic level of the thermal processes
The plant controls will be provided by a combination of the Plant Distributed Control System(DCS�?and specific microprocessor-based control systems supplied with major equipment packages as described below:
DCS--The DCS will implement the control algorithms for the HRSGs and the balance-of-plant equipment and will coordinate the control of the Combustion Turbine and Steam Turbine control systems in response to unit load demands.
Combustion Turbine (CT) Controls--Combustion Turbines will be supplied with specific microprocessor--based control systems, which implement the control and protection logic associated with the CTs.  If the DCS and the CTs control systems are of different suppliers�?hardware, interface will be provided between the two control systems to enable information exchange to use operators DCS for alarm collection, and information display/collection. The important signal between the two control systems will be transmitted by hardwire.
Steam Turbine (ST) Controls--The Steam Turbine will be supplied with specific microprocessor--based control system similar to the Combustion Turbine.  If necessary, interface and hardwire will be provided between the DCS and the STs control systems similar to that provided for the CTs.
Water Treatment Systems--The Make-up Water System for the heat-recovering boiler will be provided with a specific microprocessor--based control system. This system is designed for start-up and shutdown by operator with DCS in control room for sequence operation and for normal automatic operation without operator intervention. Process alarms and major process parameters will be transmitted to the DCS for centralized operator monitoring. The waste water system will also be provided with a specific microprocessor--based control system similar to that provided for the Make-up Water System.
Continuous Emissions Monitoring System(CEMS�?-The CEMS will be provided with a specific microprocessor--based control and data collection system. Emissions data will be transmitted to the DCS for real--time operator display as well as long--term data storage.  
In the central control room, the color CRT/keyboard will be used as major facilities for the control and monitoring of the plant, and small quantity of conventional instruments and back-up hard manual operating devices necessary will also be provided. Except for a part of the preparations which needs local manual intervention by assistant operators. During the period of the unit start up, normal operation, shut down and emergencies will be carried out by operators under the operation guidance of CRT screen displays in the central control room. The close-loop control, sequence control, protection and interlock will be automatically performed by DCS and specific micro-process.
1.8    Water Supply System
The water source for the power plant consists of sea water source and fresh water source.
The sea water is mainly used as cooling water for condenser and auxiliary closed cooling water system which is of once through water supply system. The technical process of this cooling water system is as follows:
Sea water intake chamber→Bar screen & traveling screen  �?circulating pumps �?Pressure water supply pipes �?Condenser and auxiliary heat exchanger �?Pressure water-return pipes �?siphon well �?Gravity flow culverts �?outfall.
The fresh water which comes from seawater desalination plant is mainly used for make-up water for HRSG, CTG water injection, make-up water for closed cooling system, air conditioning water, service, domestic and fire fighting water system, etc. According to the water flow rate demand of the power plant, a make-up water pump house will be built.
1.9. Chemical water treatment
1.9.1 Work scope
Design of chemical section for this project main includes the following content:
a、Boiler makeup water treatment system;
b、Condensate polishing treatment system;
c、Wastewater treatment system;
d、Recirculating cooling water treatment system;
e、Thermal system chemical feed treatment;
f、Water and steam sampling system;
g、Hydrogen generation station;
h、Chemical laboratory.
1.9.2 Boiler makeup water treatment system
The boiler makeup water treatment system mainly removes salt residues in desalinated water through primary desalination plus ion exchanger treatment process. The generated water is very pure demineralized water, could satisfy high-parameter boiler feed water water quality requirement. Main process flow of treatment system is as follows:
Desalinated water _ RO device _ cation bed _anion bed _mixed bed _demineralized water tank _main plant building
Hardness:
�? mmol/L
Conductivity (25�?:
�?.2 mS/cm
Silicon dioxide (SiO2):
�?0 mg/L
1.9.3. Condensate polishing treatment system
Condensate polishing treatment system mainly removes suspended matter and dissolved solids in the condensate, so as to ensure water steam system quality. The system could treat 100% condensate.Main process flow of treatment system is as follows:
Condensate pump outlet _ deironing filter _ Condensate heater
1.9.4. Wastewater treatment system
The wastewater will be treated and satisfied the discharge demand. The treated wasterwater will be discharged.
1.9.5. Recirculating cooling water treatment system
In order to inhibit hydrobiont reproduction prevent corrosion and scaling, recirculating cooling water treatment system is provided with sodium hypochlorite and corrosion and scale inhibitor dosing treatment device. Each dosing device includes dissolving tank and dosing pump. Chemicals is fed into Recirculating cooling water treatment system by dosing pump, inhibit biological reproduction, prevent corrosion and scaling.
1.9.6. Thermal system chemical feed treatment
Chemical dosing system in main building could control the quality of condensate, feed water, closed cooling water and boiler water effectively, reduce thermal system scaling and corrosion to the maximum extent. Chemical dosing system includes ammonification, hydrazine treatment of feed water and condensed water, closed cooling water ammonification and boiler water phosphate dosing system.
1.9.7. Water and steam sampling system
In order to monitor water, steam quality change during the operation of turbine boiler timely and accurately, diagnoze equipment fault in the system, ensure safe operation of the units in power plant, each unit is provided with one centralized water steam sampling analysis device. Water steam sampling system includes necessary sampling points, online analyzer, manual sampling tray and control system and condenser leak detection system.
1.9.8. Hydrogen generation station
In order to satisfy hydrogen demand for turbine generator cooling, a hydrogen generation system is supplied to generate dry hydrogen of proper pressure and purity.
1.9.9. Chemical laboratory
According to the requirements of the project, a chemical lab is been designed and arranged beside the boiler makeup water treatment workshop.
 
 
1  Investment Estimation
1.1  Scope of drawing up
The investment estimation consists of the equipment, civil engineering, installation work within the wall of the power plant,  excluding Land reclamation and Land costs�?/DIV>
1.2  The principal of investment estimation
1.2.1  Item dividing and standard of expenses
    According to the ‘budget management system and regulate of power industry ‘issued by State Economic and Trade Commission of China in 2007,we divided the items and calculate various expenses.
1.2.2  Ration and index
    Both installation and civil works use�?power construction budgetary estimate�?issued by State Economic and Trade Commission in 2001,’power engineering budgetary estimate �?which was edited in 2007) and consulting ‘reference cost index of electricity generating, transmitting and transformer�?authorized by China Power Engineering Consult Group Co(price level is equal to 2008).
1.2.3  Price of labors, materials and machines
    The price of labors, materials and machines is calculated with the active price standard in China.
1.2.4  Others
(1)  Basic prepare expenses
The rate of basic reservation is 7�? and the costs is included in the unit work.
(2)  Expenses of takeovering land
The investment estimate doesn’t consist of land space and land reclamation.
(3)  Traffic engineering
The investment estimate doesn’t consist of road outside of the power plant .
(6)  Export charges
    The price of equipment material is considered as purchased in China.
(8)  The unit of currency
In the report ,the unit of currency is USD.
(9) local duties, tariffs and taxes
The price does not include project country’s duties, tariffs and taxes.
1.3  Investment
The static investment is USD 993,627,900.
The General Budget Estimate Table of Electricity Generation Project
Table 1A :
Designed Capacity: 750MW
Date: December.2009
 /DIV>
Description and Specification
engineering expenses of construction
purchase expense of equipments
installation engineering expense
other expenses
Total in 10000 USD
A
Thermal system /DIV>
2,583.37
55,759.54
1,896.45
 /DIV>
60,239.36
B
Fuel supply system /DIV>
227.81
3,211.68
73.96
 /DIV>
3,513.45
C
Chemical water treatment system
220.83
452.48
261.65
 /DIV>
934.97
D
Water supply system /DIV>
266.19
813.21
431.55
 /DIV>
1,510.95
E
Electric system /DIV>
208.97
4,991.60
2,142.05
 /DIV>
7,342.62
F
I&C system /DIV>
 /DIV>
1,660.96
582.61
 /DIV>
2,243.57
G
Accessory production engineering
1,273.37
581.21
102.92
 /DIV>
1,957.50
 /DIV>
Sub total /DIV>
4,780.54
67,470.69
5,491.18
 /DIV>
77,742.40
H
Other expenses /DIV>
 /DIV>
 /DIV>
 /DIV>
21,620.39
21,620.39
 /DIV>
Total /DIV>
4,780.54
67,470.69
5,491.18
21,620.39
99,362.79


Statement: Any reference to the OEM, part number or other OEM information is for the purpose of identification only and does not imply that the part was manufactured by the Original Equipment Manufacturer.

All the brands and trademarks in the whole domain of the website belong to their own owners and does not mean that we are their authorized partner or dealer. All the information in this website is only for reference, we do not assure its accuracy.

This statement supersedes all other claims and statements on all pages, files, pics and information within this whole web domain.
Copyright©2006-2019 Leda Greenpower Beijing ICP Reg. No: 10010978.   Fax:0086-10-84161062  E-mail:
[email protected] [email protected]