6.Technical specification
Series 6000 Gas Engine Technical Data |
Engine Model |
H16V190ZLT1-2 |
|
Origin / manufacturer |
C.HINAwC-J1D.E |
Type |
Four-stroke, spark plug ignition, turbocharged and intercooled, supercharged before mixing, electrical control, the external mixing type. |
Cylinder arrangement |
16-cylinder V-type, 60 ° angle |
Bore × stroke |
190×215mm |
Total displacement |
97. 53L |
Rated speed |
1000r/min |
Rated power |
1200kW |
Heat Rate |
�?500kJ/kW·h |
Gas inlet pressure |
100-400 kPa |
Gas pressure regulator |
equip |
Gas filter |
equip |
Air filter |
equip |
Rate of oil consumption |
�?.0g/kW.h |
Oil grade |
Not less than the Kunlun KCN7810 level or equivalent model of Mobil |
Oil volume |
460L |
Lubrication methods |
Pressure and splash lubrication |
Oil filter |
equip (Centrifugal filtration and paper fine filter, dual filter system) |
Exhaust gas temperature |
�?80�? |
Speed mode |
Electronic governor |
Stable rate |
0�?%Adjustable |
Air-fuel ratio control method |
EGSFull automatic controlA/F |
Ignition control system |
IC500 Digital |
Cooling method |
Forced water cooling |
Frost protection |
Winter, upon request, replace the antifreeze |
Noise |
<118db |
Muffler type |
Extinguishing the exhaust muffler |
Explosion protection |
equip(Intake manifold, crankcase�?/DIV> |
Cooling water temperature protection |
equip�?0�?Alarm�?/DIV> |
Cooling water low level alarm |
equip |
Lubricant temperature and high protection |
equip�?5�?Alarm�?/DIV> |
Lubricating oil pressure protection |
equip �?45kPa Alarm and shutdown |
Overspeed protection |
equip �?12%Alarm and shutdown |
Engine data acquisition |
equip,RS485 communication interface |
Crank steering |
Counterclockwise |
Alternator data |
Alternator model |
JFG 5605-6(Siemens technology�?/DIV> |
Origin / manufacturer |
JIALI |
Type |
Double support motor |
Rated capacity |
1250kVA |
Rated voltage |
3.3KV |
Rated current |
262.4A |
Rated speed |
1000r/min |
Rated frequency |
50Hz |
Power factor |
0.8(Lag�?nbsp; |
Insulation class |
F |
Degree of protection |
IP23 |
Wiring |
Three-phase three-wire (Y-shaped terminal) |
Excitation mode |
Brushless synchronous phase compound |
Adjust the voltage mode |
AVR Auto |
Cooling method |
Air natural cooling |
1200kW Gas Gensets Data |
Generator model |
1200GF9-T |
Engine model |
H16V190ZLT1-2 |
Alternator model |
JFG 5605-6/10500(Siemens technology�?/DIV> |
Control system |
GPL1200(Working voltage DC24V�?/DIV> |
Rated power |
1000kW/1250kVA |
Rated voltage |
10500V |
Frequency |
50Hz |
Rated speed |
1000r/min |
Mode of operation |
Long-distance power control / manual |
Plant control |
Local / remote communication interface |
Synchronization control |
IG-NT module automatic control |
Starting method |
24V DC dual-motor electric starter |
Cooling system |
Sub-body radiator |
Overhaul period |
35000 Hours |
Dimensions |
5998×2516×2540mm |
Quality |
21000kg |
Generating set of safety protection system
Output voltage is too low / too high alarm and sub-gate |
Single-phase ground fault alarm and sub-gate |
Frequency is too high / low alarm and sub-gate |
Cooling water temperature high alarm |
Reverse power alarm and sub-gate |
Lubricating oil temperature high alarm |
Output overload (overcurrent) Alarm and Tripping |
Lubricating oil pressure too low alarm and shutdown |
Overspeed alarm and shutdown |
Battery voltage is too low alarm |
Intake explosion protection and crankcase explosion protection |
Gas leak protection (alarm signal) |
Engine Accessories Technical Specifications
Item |
Model |
Specifications |
1. Turbocharger |
TPS48-F31 |
Run-of exhaust gas turbine |
2. Electronic controller |
EGS-02 |
Stable rate:0-5%(Adjust�?/DIV> |
3. Oil Pump |
Gear |
Speed:1206.3r / min |
Displacement:1050L / min |
Oil pressure:900 kpa |
4. Oil Filter |
Spin, the paper filter |
The bypass valve opening pressure:200kpa |
5. Centrifugal filter |
|
Rotor speed : �?5000(r / min) |
Capacity:�?.5m³/h(oil temperature 75 ° C, pressure 550kpa) |
Pressure limiting valve opening pressure :250(kpa) |
6. Oil cooler |
Plate-fin, water-cooled |
|
7. water-pump |
Closed impeller |
Speed:2000 r / min |
Head: 20.4 m |
Flow rate : 62.4 m³ / h |
8. Intercooler |
Segment |
|
9. Electric starter |
S01-39208 |
Clockwise (facing the drive end);12KW |
10. Air starter motors |
ST699BP03R |
Maximum power, speed :2400r / min |
Maximum power when the gas consumption:802 L / S |
Working pressure : 0.62 mpa |
Gas system
The function of the gas supply system: separation, filtration, gas regulator through the regulator, after dive through the solenoid valve into the gas control valve; the gas control valve to accurately control the gas flow into the left right mixer to form a combustible mixture with air according to the needs of the proportion of mixed and re-entering the turbocharger; gas pressurized by the turbocharger the left and right out of the trachea, in the cold air intake chamber into the intercooler, cooling intercooler outlet chamber into the gas cavity of the body.
Air starting system
The air starting system with pre-supply pump type starting system. The startup mode to manually switch the control and two-way solenoid valve control.
Cooling system
(1) "Heat cycle" cooling system
the system mainly consists of high temperature water pump, front radiator.
High-temperature pump the front radiator cooling water pressure delivered to the body right side of the waterway, and then passes the flywheel end of the middle string of pipes, into the body the left side of waterways. Into the body's cooling water flows through the cylinder cooling water into the cylinder head water chamber, then by the cylinder head and the face outlet into the cylinder head back to the mains water pipe hole system of the body the upper string. The convergence of two rows back to the mains water summary pipe flow back into the front radiator. The circulating water temperature control in the range of 75-85 �?
(2) "Low-temperature cycle" cooling system
The system mainly consists of the cryogenic pump, intercooler, oil cooler and rear radiator. Low temperature pump inside the rear radiator cooling water sent to the intercooler, and then flows through the oil cooler, and finally flows back to the rear radiator.
The circulating water temperature control in less than 45 �?
The scope of supply
Part of the unit:
The H16V gas engine, high-voltage generator, connectors, public chassis,
container
Control parts:
Multi-function control panel, the EGS gas control box, the synchronous controller, local
signal acquisition systems, remote communication interface
Auxiliary equipment:
Six batteries and charger, fire fighting silencer, bellows and the exhaust pipe, the
random spare parts, random tools, the use of maintenance manuals
Cooling system:
The temperature regulating valve (to control the high-temperature cooling water the size
of cycle),the horizontal radiator, radiator unit of the split between the connection pipe