Fuel Gas standards and Fuel consumption
1. Composition (Natural gas)
Composition |
CH4 |
C2H6 |
C3H8 |
C4H10 |
H2S |
N2 |
CO2 |
Content (%) |
greater than or equal 76 |
<10 |
<8 |
<6 |
<0.1 |
<2 |
<1 |
2 . Calorific value: greater than or equal 41860KJ/Nm3
3. Purification requirements:
Ensure there is no liquid ingredient in natural gas.
Other ingredients |
Dust |
Sulfide |
Content(mg/m3) |
>10 |
<20 |
4. Fuel consumption:
Gas Engine Model:H16V190ZLT1-2
Under standard environmental conditions (standard atmospheric pressure at 25 oC, relative humidity 30%), with 1200kW power output capability, the unit has the ability to run continuously 1000kW conditions, fuel gas consumption is 330Nm³/ h.
3MW CHP Power Plant:
Fuel Gas Consumption: 990Nm³/ h.