1.generating sets technical specifications
Genset model |
500GFZ1-PwZ-ESM1 |
Engine type |
Z12V190ZLDK-2 |
Alternator model |
1FC6 455-6LA42 |
Rated Power (kW) |
500 |
Rated current(A) |
902 |
Rated voltage(V) |
400 |
Rated power factor COSΦ |
0.8(lag) |
Frequency(Hz) |
50 |
Fuel consumption (MJ/kWh) |
10.3 |
Lube oil consumption (g/kWh) |
less than or equal 1.0 |
Switch on method |
24VDC |
Starting Mode |
Automatic |
Voltage control method |
Automatic |
Speed regulation method |
Electronic governor |
Excitation way |
Brushless |
Wiring method |
Three-phase,four-wire system or Three-phase, three-wire system |
Vadose water cooling method |
Closed |
Connection type |
Elastic couping connection |
Dimension, L×W×H(mm) |
5678×2170×2839 |
Weight(kg) |
10750 |
Overhaul period(H) |
30000 |
1.2 Engine technical specifications
Model of engine |
Z12V190ZLDK-2 |
Configuration and type |
four stork, direct injection fuel syste |
Cylinder arrange |
V type 60°included angle |
No.of cylinder |
12 |
Total displacement, (L) |
71.45 |
Rated speed(r/min) |
1000 |
Idle speed(r/min) |
700 |
Rated power(kW) |
550 |
Fuel consumption(MJ/kWh) |
9.5 |
Lube oil consumption(g/kWh) |
less than or equal 1.0 |
Jacket water temp(oC) |
less than or equal 85 |
Lube oil temp(oC) |
less than or equal 90 |
Lube oil pressure in oil main line(kPa) |
400~800 |
Lube oil pressure in turbocharger(kPa) |
200~400 |
Stable speed drop (%) |
0~5 adjustable |
Lubricating system |
Pressure and splash lubrication |
Ignition method |
Spark plug ignition |
Starting method |
24VDC motor |
Direction of rotation |
Clock-Wise (viewed from the front) |
|
Electronic Governor |
|
|
Output way |
flywheel output |
1.3 Alternator technology specifications
Alternator model |
1FC6 455-6LA42 |
Output power(kVA) |
625 |
Rated speed(r/min) |
1000 |
Rated voltage (V) |
400 |
Rated current (A) |
902 |
Frequency (Hz) |
50 |
Power factor(lag) |
0.8 |
Insulation Clause |
F |
Exciter |
Brushless Exciter |
Altitude |
less than or equal 2500m |
Direction of rotation |
Clock-Wise (Facing flywheel) |
Protection Clause |
IP23 |
Cooling system |
|
2 Engineering equipment estimate table
Item |
Project name |
Model |
Quantity |
Generating sets |
1 |
Generating sets 500kW |
Including engines, chassis,generators, unit circuit breaker cabinet and on-site control cabinet |
1 |
2 |
Start cabinet |
|
1 |
3 |
Remote control cabinet |
|
1 |
4 |
Low voltage main cable ( unit to the circuit breaker cabinet ) |
YJV-0.6/1kv 3×185 |
50 |
5 |
Fire prevention plugging material |
|
40 |
6 |
Other power distribution, control cables |
|
1 |
7 |
Electrical complementary material |
Threading pipe, connection box, etc |
1 |
Unit air intake |
1 |
Silk screen filters |
|
1 |
2 |
Pipe special-purpose flame arrester |
|
1 |
3 |
General rubber bellows expansion joint |
|
1 |
4 |
Insert V cone flowmeter |
|
1 |
5 |
Gas treatment module |
|
1 |
6 |
Stainless steel membrane box pressure gauge |
|
2 |
7 |
bimetal thermometer |
|
1 |
8 |
Various pipe, elbow, flange |
|
1 |
Exhaust |
1 |
Muffler, exhaust pipe |
|
1 |
Cooling part |
1 |
Much fan water tank |
|
1 |
2 |
Water softener feed water pump |
|
1 |
3 |
Water softening equipment |
|
1 |
4 |
Assembly type steel plate to the water tank and a bracket |
|
1 |
5 |
Level sensor |
|
1 |
6 |
Stents pipe valve six and other accessories |
|
1 |
|
1 |
transport fee |
|
1 |
Other expenses |
1 |
design fee |
|
free |
2 |
During construction period technology service charge |
|
3 |
Joint commissioning fee |
|
Total(USD) |
315,504.00 |
Explain |
1, This budgeting does not include civil construction and installation charge; |
2, This quotation for FOB: Qingdao port; |
3,Quotation code:ning 62552012516 |
China the most famous gas engine generator sets For China gas engine generator sets or power plants, please click.
|