Technical parameter for Generator Sets |
|
Type |
18V32/40 |
|
Brand |
MAN |
|
Dimension (L×W×H) mm |
12580×3730×5245 |
|
Weight t |
138 |
|
MCR kW |
8730 |
|
Voltage Rating kV |
11 |
|
PF |
0.8 |
|
Rated Speed rpm |
750 |
|
Output Frequency Hz |
50 |
|
Voltage Regulation Voltage regulation % |
±1 |
|
Voltage fluctuation rate % |
�?.5 |
|
Frequency fluctuation rate % |
�?.5 |
|
Load mutation frequency settling time (S) |
�? |
|
Mutation load voltage stabilization time (S) |
�? |
|
Terminal connection |
3phase3wire |
|
Fuel type |
diesel fuel or HFO |
|
Engine |
|
Type |
18V32/40 |
|
Brand |
MAN |
|
MCR kW |
9000 |
|
Cylinders |
18 V |
|
Spec. fuel oil consumption g/kWh |
181 |
|
Spec. lub oil consumption g/kWh |
0.8 |
|
Starting system |
Compressed Air |
|
Cooling system |
Water cooling |
|
Rated Speed rmp |
750 |
|
Idle speed rmp |
250 |
|
Mean eff. pressure (MEP) bar |
24.9 |
|
Piston speed m/s |
10 |
|
Cylinder distance mm |
630 |
|
Displacement /cylinder L |
32.17 |
|
Governor style |
Electronic governor Heinzmann |
|
Exhaust gas temperature (after TC) °C |
354 |
|
Exhaust back pressure(Max) mbar |
30 |
|
Compression ratio |
14.5 |
|
Stroke mm |
400 |
|
Bore mm |
320 |
|
Alternator |
|
Brand |
Leroy Somer/ ABB/ Siemens/AVK /HYUNDAI |
|
MCR kW |
9000 |
|
Voltage Rating kV |
11 |
|
Rated Frequency Hz |
50 |
|
PF |
0.8(Lag�?/DIV> |
|
Field System |
Brushless, PMG-excited |
|
Insulation Grade |
H |
|
Grade of Protection |
IP23 |
|
rated speed rpm |
750 |
|
|
F/F |
|
(This picture is for reference only) |