BBS  Email&MSN: ycl1227@163.com
  
Homepage   |   Power Generation   |   Project Financing    |   Equipments   |   Transmission   |   News   |   Contact    |   services   |   download   |   sitemaps   |   Business Opportunity   |   BBS-Blog   |   Purchasing-agent   |   Exchange Link  

Mail List

E-mail:

Equipments
    Gas turbine & spare parts   
      GE 9FA 255mw Gas Turbine Generator   
      GE Licensed MS9001E Series Gas Turbine plant   
      42MW GE Gas Turbine Generator   
      PG6581B Gas Turbine Series Generator Plants   
      PG6581B Gas Turbine Set Supply Scope   
      Gas Turbine Spare Parts   
      Gas Turbine Generator Site Inspection   
      2MW Gas Turbine Generator   
      7mw-Siemens-SGT200-Gas-Turbine-Cogeneration-unit   
      10MW Gas Turbine Generator   
      Used Gas Turbine Generator Plant   
      Technical-Specification-PG6581B-Gas-Turbine   
      Supply-Scope-of-PG6581B-Gas-Turbine   
      Budgetary Cost for 108MW Gas Turbine Plant   
      Siemens Gas Turbine Generator   
    Steam Turbine   
      Extraction Condensing Turbine   
      Condensing Steam Turbine   
      Recovery Turbine   
      Extraction Turbine   
      Required Data for Quotation   
      Alstom-Licensed-330MW-Steam-Turbine   
      Quotation-50MW-condensing-steam-turbine   
      Quotation-30MW-Condesing-Steam-Turbine   
    Boiler   
    Power Plant Generator   
      Air Cooled Power Generator   
    Diesel generator   
      8x8735kw MAN 18V32/40 HFO Diesel power Proposal   
      8x 4.1mw MAN 9L32/40 hfo power plant proposal   
      6 units 5.5mw MAN 12V32/40 hfo diesel plant   
      3x3.5mw MAN 8L 32/40 hfo diesel generator plant   
      1MW diesel generator    
      1.5MW Diesel Generator Set   
      2M Diesel Generator Plant   
      Sample Diesel Power Plant Proposal 9x2mw   
      Diesel power Plant List   
      Used Diesel Generator   
      Diesel Generator Pictures   
      Bio diesel generator power plant MW   
      Sample Pack List for 10x2MW HFO diesel power Plant   
      10kw-4000kw-Cummins-MTU-diesel-generator-set   
    Hydro Turbine   
    Engineering Machinery   
      Truck Mounted Crane Crawler   
      Trailer Concrete Pump   
      China Bulldozer   
      China Crane   
      Benz Truck and Lorry from China   
    Cable&Wire   
    Electric Motor   
    Transformer in MVA   
      Germany Certificates   
      Required Data for Quotation   
      Transformer Reference   
      Sample Inquiry   
    Wind Turbine Generator   

Diesel Generator Proposal

Power Plant Proposal

 

Home > Equipments > Diesel generator > 8x8735kw MAN 18V32/40 HFO Diesel power Proposal


 



The Technical Program of 8x8735kw MAN HFO 18V32/40 Power 52MW HFO Power Station

Contents

1. Company introduction............................................................................................. 1

2. Codes and standards................................................................................................ 1

3. Environmental conditions ....................................................................................... 2

4. Customer Requirements .......................................................................................... 2

5. Summary of 52MW power station........................................................................... 3

5.1 Overall description of heavy fuel oil power station.................................................. 3

5.2 Characteristics of HFO power station...................................................................... 4

5.3 The economy of program about 52MW HFO power station .................................... 5

6. Scope of supply....................................................................................................... 6

7. Configure of power station system .......................................................................... 7

7.1 Diesel generating sets.............................................................................................. 8

7.2 Lubricant system................................................................................................... 10

7.3 Lube supply system............................................................................................... 13

7.4 Coolant system ..................................................................................................... 14

7.5 Nozzle cooling circulation system......................................................................... 15

7.6 Cooling water preheating module.......................................................................... 15

7.7 Cooling water supply system................................................................................. 16

7.8 Fuel system........................................................................................................... 16

7.9 Inlet system........................................................................................................... 18

7.10 Exhaust system ................................................................................................... 18

7.11 Leaked oil & decontamination module ................................................................ 19

7.12 Compressed air system........................................................................................ 19

7.13 Electrical equipment of generating sets ............................................................... 20

7.14 Architectural equipment ...................................................................................... 23

8. The practicable contents for the contractor ............................................................ 23

9. Technical data and drawings of products ............................................................... 24

9.1 General requirements ............................................................................................ 24

9.2 Basic Requirements of information presentation ................................................... 24

10. Progress of production and delivery ...................................................................... 27

11. Delivery................................................................................................................ 28

12. The scope of service protection............................................................................. 28

13. Contacts................................................................................................................ 29

1. Company introduction

Our producer of diesel generator is an export oriented enterprise specialized in the research and development, manufacturer, sales and service of diesel generators. Because of the products, technique and service of OEM cooperation with German MTU, UK Perkins, South Korea DOOSAN,USA Marathon, France Leroysomer and other world-known enterprises, the emergency electrical stations provided electricity guarantee for Xiangguang Copper(4800KW), Jiangxi Copper Group(3200KW)锛?/SPAN>China Financial Center Database(11000KW)锛?/SPAN>Jiangxi LDK Solar (5600KW),etc. The factory of Hangzhou, established in April, 2005, is situated in Hangzhou Economic and Technological Development Zone, with a floor area of 50,402 square meters and the total investment of US$59.6 million. On October 11th, 2006, it signed a license agreement of technology acquisition and collaborative production with MAN Diesel Group to become a licensed member, specialized in producing MAN Diesel high-power, medium speed, four-stroke engines, auxiliaries and propulsion system with the power ranging from 1000kw to 10,000kw. Supervised by the experts designated by MAN Engine Company, the products all passed MAN product quality inspection, Ship Classification Society OF CCS and BV. On June 20th, 2009, the first 32/40 4500KW engine held a ceremony, released to the users and realized the production. The company plans to produce 20 engines in 2009 and 100 engines in 2010. The company dedicated to research and exploration of heavy fuel oil power station, supported by the technology and products of MAN and the over ten-year experience of emergency power station. In May,2009, signing an agreement of the heavy fuel oil power station South American market development, the two sides plan to design, construct and operate Brazil 174Mw and 200MW heavy fuel oil power station, which got technology and supporting services from MAN.

2. Codes and standards

Equipment, parts and auxiliary equipment, provided by the sealer, correspond with the latest version of the standard, but they are not limited to the following standard:

2.1 State Standards GB2820锛?/SPAN>1997 Alternated current drive reciprocating internal combustion engine generating sets, JB/T10303-2001 銆?/SPAN>Technical conditions of power frequency diesel generating sets

GB755锛?/SPAN>2000 The basic technical requirements of electric rotating motor
GB1105
锛?/SPAN>1987 Performance testing method of internal combustion engine housing
GB1859
锛?/SPAN>2000 Internal combustion engine noise determination method
GB3907
锛?/SPAN>1983 The basic measuring method of industrial radio interference
JB/T8194-2001 Vocabulary terms of internal combustion engine electrical station
GB12699-1990 Rated power, rated voltage and speed of power frequency diesel
generating sets
CB/T3253-1994 Technical conditions of marine diesel engine
CB/T3254-1994 Experiment of marine diesel engine housin
GB8840-1988 Exhaust limits of marine diesel engine

2.2 Technical standards of MAN
3. Environmental conditions
Refer to ISO : 30461/1-2002
The standard environmental condition
Environmental temperature: 25Celsius Degree
Barometric pressure: 1bar
RH (relative humidity): 30锛?BR>Fuel oil condition
Fuel lower heating value: 42700 kJ/kg

4. Customer Requirements
Place of power station: Ecuador
Total capacity of power station: 52.380MW with changing scope of 3锛?BR>Voltage: 10.5kV
Frequency: 50Hz
PF (Power Factor): 0.8pf

5. Summary of 52MW power station
5.1 Overall description of heavy fuel oil power station There are 6 MAN 18V32/40 diesel generating sets in 52MW heavy fuel oil power station, each set power: 8730KW Total power: 52380kW Voltage: 10.5kV Frequency: 50Hz PF: 0.8pf
Speed: 750rpm.
The design picture of standard electrical station锛?BR>
          鈶?Power station
          鈶?Exhaust system and exhaust boiler
          鈶?Sweetener
          鈶?Radiated coolant system
          鈶?Fuel depot
          鈶?Pump station
          鈶?Maintenance workshop and warehouse
 
52MW power station contains power station, exhaust system and exhaust boiler, radiated coolant system锛宖uel depot, pump station, maintenance workshop & warehouse and working building. Generating sets, auxiliary machines, supply unit, lube filtration separator and control system are all installed in power station. If you don't consider terrain factors influence, the ideal power station can take up an area of 200m脳165m. While the actual station design could be adjusted by weather, environment and terrain, but principle of proximity should be considered to prevent too much a long pipe arrangement. At the same time, the heat of heavy fuel oil tank is realized through the vapor of exhaust boiler, so the short line is in favor of heat insulation.
There is the general layout of 52MW power station in the annex
The heavy fuel oil could be the main fuel and light diesel oil the auxiliary fuel. With the main
generating sets parallel operation, each unit can input or exit operation. The control system could adjust power balance, power of different sets, which has protective measures of inverse power, over current, etc.
(Suggestions) The power station need to collocate a 1000kVA auxiliary engine, which can supply the black start power, light fuel oil, 24V storage battery start, power -0.40kV, frequency-50Hz, PF-0.8pf, and rotated speed-1500rpm. When the power station comes into good running, the auxiliary engine turns to the emergency standby sets.
Transformer, collocate by power station, provide the main auxiliary equipment with working power supply, the electricity of station lighting and domestic consumption.
5.2 Characteristics of HFO power station
(1) Highly-structured corollary equipment, flexible installation site and short construction period
The corollary equipment of heavy fuel oil generating sets is rather simple for little corollary equipment, small volume and light in weight. Compared with water turbine-generator set needed to dam, vapor generating set needed to boiler, fuel storage, and water treatment system, the diesel generating set has advantages of small occupation, high construction speed and low invest cost.
Modularity unit system used for heavy fuel oil generating sets, flexible arrangement according to the terrain, which is fit for construction of mountain area and mine area, subjected to small regional terrain restrictions.
(2) High thermal efficiency, low fuel oil consumption and low operation cost
The heavy fuel oil machine extended from diesel is the highest thermal motors of thermal efficiency, of which the effective thermal efficiency is 40%-50%, the high-pressure steam turbine is about 20%- 40%, and combustion gas turbine is about 20%-30%. So fuel consumption is rather low about 178g/kWh. The power station form applied with heat and power cogeneration, has the higher whole energy conversion efficiency, and the thermal power gets more fully used.
(3) The rapid starting and can quickly reach full power
The heavy fuel oil generating sets may use heavy fuel oil and light fuel, which could reach full loaded operation in 3 min of emergent condition (light fuel oil used on emergency ), and in 10 min of normal operation condition (starting uses light fuel oil, and heat engine uses heavy fuel oil ),while the thermal & electricity steam power equipment generally needs 3-4h from starting to full load. What鈥檚 more, the shutdown process of diesel is rather short, started and shutdown frequently.

          (4) Simple maintenance, small conventional maintenance work, little operation staff, overhaul period of 36000h (related to the fuel oil quality), and low operation expense.
          (5) Convenient unit combination and upgrade, capacity easy to extended
 
Each capacity of MAN heavy fuel oil power station generating sets, ranging from 3000kw to 21000kw, which has the advantage of fitting for more power supply load with more selected capacity. When adopting heavy fuel oil power station generating sets as power, the installed capacity may dispose neatly according to actual need, which can increase power set capacity in the after enlargement & production. The expansion of access is simple and smart, so the expense of primary construction investment is much lower.
5.3 The economy of program about 52MW HFO power station
锛?锛塃conomy of power station operation a. Fuel cost MAN 18V32/40 generating sets adopted by this program, the fuel consumption rate is:

Rate of loading
100锛?
85锛?
Fuel consumption rate
181g/kWh
179g/kWh
Fuel consumption 1kWh
186.6 g
184.5 g

 
Estimated with 180# heavy fuel oil, 1600 Yuan\ton Generator efficiency 97%; The fuel cost of 1kWh

Rate of loading
100%
85%
1kWh
0.299RMB
0.295RMB

 
b. Oil cost: When lube oil consumption rate is 0.8 g/kWh, generator efficiency is 97%, provided by MAN database, the lube consumption is 0.82 g/kWh.
c. Maintenance cost: The heavy fuel oil power station has a long overhaul period that can reach 36000 hours in general condition. Counted by 20 hours per day it can operate over 5 years continuously.
With a mature model18V32/40 and low malfunction rate, it is widely used by the ship and power station domain. Also with plenty of spare parts storage and supply, the maintenance cost is rather lower.
1        Scope of supply
2        Configure of power station system
 

 
 
 
 
 
Installed
 
No.
Designation
Contents
Unit
Qty.
location of
Remarks
 
 
 
 
 
machines
 
1
ZGPT-MAN 18V32/40 generating sets
Engine, shaft coupling, generator, public chassis, control panel
set
6
 
 
 
 
Comprised by lubricating pump, lube
 
 
 
 
 
 
oil cooler, lubricant temperature
 
 
 
 
 
 
control valve, lube self-cleaned filter,
 
 
 
 
2
Auxiliary module
high temperature pump, high water temperature control valve, low
set
6
 
With standby
 
 
temperature pump, low water
 
 
 
 
 
 
temperature control valve, control
 
 
 
 
 
 
switch cabinet, etc.
 
 
 
 
 
 
Including lube delivery pump, lube
 
 
 
 
3
Lube separating module
preheating device, lubricant separator, sump pump, sump tank, control switch
set
6
 
With standby
 
 
cabinet, etc.
 
 
 
 
4
Fuel supply module
Conversion valve of heavy fuel oil and light oil, fuel meter, viscosity control, fuel mixed tank, fuel pressure pump, HFO end heater, fuel cooler, fuel double filter, control switch cabinet
set
6
Power plant
With standby
5
Leakage oil & decontamination module
Sludge pump discharge, fuel leaked oil tank, lube sludge tank
set
2
 
 
6
Engine preheating module
Preheating high temperature water, lubricating oil
set
6
 
 
7
Inlet filtration muffler module
Shutter, inlet filter, inlet muffler
set
6
 
 
 
 
Radiator, centrifugal water pump,
 
 
 
 
8
Nozzle cooling module
cooler, expansion tank, temperature control valve, filling equipment, control
set
6
 
 
 
 
switch cabinet
 
 
 
 

 

 
Water
 
 
 
 
 
9
maintenance
Radiator, centrifugal water pump
set
1
 
 
 
module
 
 
 
 
 
10
Heavy oil separation module
HFO delivery pump, HFO preheating device, Separator, sump pump
set
2
Pump plant
 
11
Air container
Starting air container, working air container, pressure reducing valve
set
2
 
With standby
12
Air compressor
H.P. air compressor, L.P. air compressor
set
2
 
 
13
Radiator
High temperature water and low temperature water radiating
set
6
Radiator
 
14
Exhaust Muffler
Exhaust Muffler
set
6
Outlet and exhaust boiler
 
15
Exhaust boiler
Boiler body, air manifold, water pump, control switch cabinet
2
 
16
Switch cabinet
Switch cabinet of parallel generating sets
set
6
 
 
17
Feeder cabinet
Switch cabinet of total outgoing line
set
1
 
 
18
Neutral point arrester cabinet
Neutral point grounding of generator
set
6
Power
 
19
PT cabinet
PT bus couple
set
1
Distribution room
 
20
DC panel
 
set
1
 
 
 
Power
 
 
 
 
 
 
 
Power consumers and distributors of
 
 
 
 
21
distribution
 
set
3
 
 
 
cabinet
each module system
 
 
 
 

 
Configure of power station system contains as follows: Diesel generating sets Lube system Lube supply system Coolant system Nozzle cooling circulation system Cooled water preheating module

Cooled water supply system
 

Inlet system
Exhaust system
Leaked oil & decontamination module
Compressed air system
Electrical equipment of generating set
Architectural Equipment
锛?/SPAN>the buyer in charge锛?/SPAN>

7.1 Diesel generating sets

The generating sets mainly include diesel, duplex bearing generator, high elasticity shaft coupling and public housing. Diesel and duplex bearing generator are connected by high elasticity shaft coupling, which are also supported and fixed by public housing.

Function of diesel generating sets:
Rated power 路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路8730kW
Rated speed路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路750rpm
Rated voltage 路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路10.5kV
Rated frequency 路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路50Hz
PF(Power factor)路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路0.8
Steady-state voltage adjusting rate路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路鈮ぢ?.5%
Transient voltage adjusting rate 路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路20%--15%
Sudden load changing voltage steady time 路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路鈮?S
Voltage fluctuation rate 路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路鈮?.5%
Steady-state frequency adjusting rate 路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路鈮ぢ?.5%
Transient frequency adjusting rate路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路+10%--7%
Sudden load changing frequency steady time路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路鈮?S
Frequency fluctuation rate 路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路鈮?.5%
Waveform distortion 路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路鈮?%

The generating sets permit sudden increase 60锛?/SPAN> and reduction 100锛?/SPAN> once a time, and the function index can meets the requirement.

The generating sets as the main electrical power, no limitations for operation time, it can operate and supply electricity continuously except the normal maintenance. In the operation process, the period can permit the overload operation of one hour per 12 hours, and if it overloads 10%, the function of the sets doesn鈥檛 fall.

7.1.1 Diesel Brand and model of diesel 路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路MAN 18V32/40 Pattern 路路路路路路路路路路路路路路路路路路路路路路路路路, 路路路路路路路路路路路路路路路路路路路V, four stroke, direct injection, turbocharger, air cooled,

compressed air starting Cylinder bore 路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路320mm Stroke 路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路400mm Bore spacing 路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路630mm Compressed ratio 路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路14.5

MCR (Most Continuous Power)\speed 路路路路路路路路路路路路路路路路路路9000kW/750 r/min Direction of rotation路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路Crankshaft clock-wise rotation (as viewed from output end) Lowest steady speed 路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路250r/min

Fuel consumption rate (When MCR happens)鈥?.... 181g/kW.h锛?/SPAN>tolerance+5%

MEP (Mean effective pressure) 路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路24.9Mpa

Pistons mean speed 路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路10 m/s

Air intake flow 路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路6.8kg/kW.h

Exhaust gas flow路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路7.0kg/kW.h

Exhaust gas temperature after supercharger 路路路路路路路路路路路路路路路路路路路路路路鈮?54Celsius Degree

Supercharger air pressure路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路0.404MPa (Absolute pressure) Supercharger air temperature before cylinder路路路路路路路路路路路路路路路路路路路路路路43Celsius Degree

Exhaust main pipe temperature before supercharger鈥︹鈥?鈮?65Celsius Degree

Exhaust temperature of every cylinder 路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路鈮?10Celsius Degree

Most combustion pressure 路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路19.0Mpa
Diesel inlet lube pressure 路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路0.4-0.5MPa
Diesel inlet lube temperature 路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路65Celsius Degree

H.T. water into-machine
pressure ••••••••••••••••••••••••••••••••••••••••••0.3-0.4MPa
         H.T. water out-machine
pressure ••••••••••••••••••••••••••••••••••••••••••••••••••90Celsius Degree
Injector coolant water into-machine pressure鈥︹鈥︹.0.2-0.5 MPa
Injector coolant water into-machine temperature 鈥︹鈥︹鈥︹..60 Celsius Degree
Fuel into-machine
pressure ••••••••••••••••••••••••••••••••••••••••••••••••••••••••0.4-0.8MPa


 

7.1.2 Generator Brand of generator 路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路LEROYSOMER Generator output power\speed 路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路9000kW/750 r/min

Direction of rotation路路路路路路路路路路路路路路路路路路路路路路路路路路路路路Counter clock-wise (as viewed from input end) PF路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路0.8 Voltage,

frequency 路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路10.5kV 50Hz Efficiency路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路97%
Grade of Protection路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路IP23
Winding temperature sensory 路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路2脳3Pt100(sensory) (1 set standby) Anti-freezing heater 路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路AC220V
Coolant method路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路Self-fan coolant
AVR (Automatic Voltage Regulator) 路路路路路路路路路路路路路路路路路路路路路Installed on generator
7.1.3 High elasticity shaft coupling Connect the diesel and generator elastically in order to make sure the output power from diesel deliver to
generator. Model 路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路CRS3420
7.1.4 Public housing
Fix and support diesel and generator, internally install lube working oil tank and contain lube for diesel.

7.2 Lubricant system
Lubricant system provides sets with lube of regular flow, temperature and quality, in order to lubricate and cool bearing, operation parts and piston. With separation, filtration and fresh supplement of lube, it can guarantee the function of set lube. Lubricant system is a closed circulation system that connects atmosphere with crankcase breather, as shown in Figure1. Out of power house
 
Figure 1: The principle diagram of lubricant system
Lubricant system contains lube working tank, lube oil pump, lube cooler, lube temperature control valve, lube oil filter, lube pressure regulating valve, lube preheating module and lube cleaned separating module, etc. 7.2.1Lube working tank
Installed public housing of generating sets internally. When the generating sets operate, the oil level must be between upper limit and bottom limit of working tank.
Capacity of lube 路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路9 cubic meters
7.2.2 Lube oil pump
Lube oil pump has gear type and screw pump, which can make circulation by the lube. Installed safe relief valve internally to prevent the high system pressure. And lube oil pump drives by motor, one standby one uses.
Flow 路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路180 m3/h, 8 bar
7.2.3 Lube cooler Lube cooler is panel cooler to take accumulated heat of system. Heat exchange路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路680 kW
7.2.4 Lube temperature control valve Lube temperature control valve uses for maintain the constant temperature of system or the change within the small range of system temperature. Control temperature 路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路65Celsius Degree
7.2.5 Lube oil filter Lube oil filter can protect the diesel, which can keep off the impurity and lies in the entrance of diesel lube oil. Also the lube oil filter is continuous cross flow current kick-type self-cleaned filter.
Nominal filter fineness路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路34渭m
7.2.6 Lube pressure regulating valve Lube pressure regulating valve is to regulate the system power of the operation process, which can make
the inlet lube within the certain range of pressure of diesel. Regulating pressure路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路4-5bar
7.2.7 Lube preheating module
Parallel connection with the main lube system, it may preheat the lube of working tank to guarantee the rap is starting or sudden load. Generally, high temperature coolant water system and lube oil system are preheated with the same module. Preheating temperature 路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路40 Celsius Degree
7.2.8 Lube cleaned separating module It is connected with the main lube system, very important, which includes lube delivery pump, lube preheating unit, lube separator, sump pump, sump tank, and control switch cabinet. Generally, it separates the moisture and harmful of lube oil dust with centrifugal oil separator.
Effective handling capacity路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路2.25 m3
7.3 Lube supply system Lube supply system provide system with accepted, storaged and full lube to make the continuous
operation of power station. The new lube is supplied by oil can or tanker truck. Then the workers can fill the tank of every lube working tank.
 
Figure 2: The principle diagram of lube supply system
Figure 2 is lube supply system including baggage hold oil of lubricant unit, lube storage oil can, lube delivery pump, lube capacity gauge, etc. 7.3.1The unloading oil unit of lubricant system
This unit mainly contains unloading oil pump, valve and granular filter. The unloading oil pump is gear type or screw pump that provides lube into storage tank from oil can or tanker truck, and drives by motor, one standby one uses.
The unloading oil flow路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路25 m3/h锛?bar (one standby one uses)
7.3.2Lube storage tank
Arranged in the oil house, heated by the steam and the normal operation of power station, the oil level must be between upper limit and bottom limit of working tank.
Capacity of lube storage tank路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路15 m3
7.3.3 Lube delivery pump This unit is gear-type pump with the main function of delivering the lube oil of oil tank to the working
oil tank, which drives by motor, one standby one uses. Delivery pump路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路15 m3/h锛?bar (one standby one uses)
7.4 Coolant system
Coolant system, divided into two-closed circulation system, the low temperature water circulation system and high temperature water circulation system connect the atmosphere with the expansion radiator. Excepted from cooling the main machine, it needs to guarantee the proper temperature of the engine to meet combustion demand different load. The low temperature water is responsible for cooling supercharge Air II and lube oil, while the high temperature water for cooling cylinder jacket, supercharge Air I and cylinder head. And the external cooling uses the radiator not adding water.
The low temperature water circulation system and high temperature water circulation system include expansion radiator, water pump, radiator and temperature control valve.
7.4.1 Expansion radiator Expansion radiator compensates the heat expansion of high temperature water system and high temperature water circulation system which has the effect for compensating water and releasing air.
High temperature expansion radiator 路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路250 L
Low temperature expansion radiator路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路250 L

7.4.2Water pump Both high temperature water pump and low temperature water pump are all centrifugal water pump, driving by the motor, one standby one uses. High & low temperature water pump deliver high temperature
 
water and low temperature water separately through pump, making the circulation in the return line of their
own. High temperature water pump flow 路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路108m3/h, 5 bar Low temperature water pump flow 路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路180m3/h, 4.5 bar
7.4.3 Radiator
The low temperature radiator is responsible for cooling supercharge Air II &lube oil and drop off the heat of nozzle, while the high temperature radiator for cooling cylinder jacket, supercharge Air I and cylinder head.
High temperature heat release路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路 3020 kW Low temperature heat release路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路 2495kW 7.4.4Temperature control valve
The main function of high temperature water temperature control valve is to keep the constant temperature of out-let high temperature water, while the low temperature water temperature control valve is to keep the constant temperature of in-let low temperature water.
High temperature water temperature control valve 鈥︹鈥?.90Celsius Degree
Low temperature water temperature control valve鈥︹鈥︹..decided by the local conditions

7.5 Nozzle cooling circulation system
Cool the nozzle as burning the heavy fuel oil. Nozzle cooling circulation system is a closed forced circulation system for cooling nozzle and taking heat by low temperature water system .Nozzle cooling circulation system mainly contains radiator, centrifugal water pump,
cooler, expansion radiator, temperature control valve and compensating water unit, forming the nozzle coolant module with all the equipment.
Heat exchange 路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路35kW
Water flow路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路3.2 m3/h锛?.0bar
7.6 Cooling water preheating module
Parallel connection with the main high temperature coolant water system, this unit preheats the cooled water in sets and pipe to guarantee the rapid starting and sudden load of engine. Generally, high temperature coolant water system and lube oil system are preheated with the same module
 
Preheating temperature 路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路40 Celsius Degree
7.7 Cooling water supply system
The main function of cooling water supply system is to supply and storage cooling water to meet the water consumption of boiler system, guarantee the normal operation, has the function of softening and dealing with raw water. The cooling water supply system includes softening equipment, radiator and centrifugal water pump.
Systematic radiator鈥︹鈥︹鈥︹鈥︹鈥︹.20 m3
Water supply pump 路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路6m3/h, 3 bar (one standby one uses)
Water softening equipment
7.8 Fuel system
Fuel system includes the parts of unloading oil, storage, delivery, handling, supply and gather of return oil, whose functions are to supply fuel continually to diesel and to preserve the constant flow, pressure, cleanness and viscosity. The heavy fuel oil system has the light oil as standby use, when starting and shutdown changing to light oil supply.
Fuel system includes heavy unloading fuel oil unit, heavy fuel oil storage oil-can, heavy fuel oil delivery unit, heavy fuel oil buffer oil cabinet, heavy fuel oil separating module, daily-used heavy fuel oil cabinet, fuel supply module, oil sludge tank, diesel unloading oil unit and daily-used diesel cabinet. 7.8.1Heavy unloading fuel oil unit
This unit mainly contains unloading oil pump, valve and granular filter. The unloading oil pump is gear type or screw pump that provides heavy fuel oil into storage tank from tanker truck through pump, and drives by motor, one standby one uses.
Unloading oil flow 路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路70 m3/h锛?bar
 
7.8.2Heavy fuel oil storage oil-can
Arranged in the oil house, heated by the steam and with the normal operation of power station, the oil level must be between upper limit and bottom limit of working tank. Capacity of heavy fuel oil storage oil-can路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路10000 m3 heated by the steam
One oil-cans can make 6 machines use 20 days 7.8.3Heavy fuel oil delivery unit Heavy fuel oil delivery unit has gear type and screw pump, with the main function of delivering heavy fuel oil from storage oil-can to buffer oil cabinet by pump, which drives by motor, one standby one uses. Delivery pump flow 路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路35m3/h锛? bar (one standby one uses) 7.8.4Heavy fuel oil buffer oil cabinet Arranged in the oil house, heated by the steam and with the normal operation of power station, the oil level must be between upper limit and bottom limit of working tank. Capacity 路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路110 m3 heated by the steam
7.8.5 Heavy fuel oil separating module
This unit, very significant, filtrates the heavy fuel oil with separator, which includes heavy fuel oil delivery pump, heavy fuel oil preheating unit, separator, oil sump and switch control cabinet. The separating impurity is delivered to oil sludge tank by pump.
Effective handling capacity路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路20 m3/h 7.8.6Daily-used heavy fuel oil cabinet
Arranged in the oil house, heated by the steam and with the normal operation of power station, the oil level must be between upper limit and bottom limit of working tank. Capacity 路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路220 m3
7.8.7Fuel supply module The main function of this unit is to heat and pressure fuel filtration, to supply the diesel fuel under the circumstance of standard temperature, pressure, viscosity and flow, and to realize the transfer between heavy fuel and light oil. This can change into the light oil between the starting and shutdown. Fuel supply module includes conversion valve of heavy fuel oil and light oil, fuel meter, viscosity control, fuel mixed tank, fuel pressure pump, HFO end heater, fuel cooler, fuel twin filters, and control switch cabinet.
Fuel pressure pump 路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路2.7 m3/h, 8 bar(one standby one uses锛?BR>Fuel twin filters路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路34渭m
Fuel mixed tank 路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路70 L

7.8.8 Oil sludge tank Oil sludge tank, heated by vapor of sludge tank, is used for storage impurity, oil sludge and oil residue
after the heavy fuel oil separated. Capacity of oil sludge tank路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路5 m3
7.8.9 Diesel unloading oil unit
This unit mainly contains unloading oil pump, valve and granular filter. The unloading oil pump is gear type or screw pump that provides heavy fuel oil into storage tank from tanker truck through pump, and drives by motor, one standby one uses.
Unloading oil flow 路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路11.52 m3/h锛?bar
7.8.10 Daily-used diesel cabinet
Arranged in the oil house, playing the role of daily-used working oil tank and game storage, and with the normal operation of power station , the oil level must be between upper limit and bottom limit of working tank. It needs to be heated by the steam in winter
Capacity of daily-used diesel cabinet路路路路路路路路路路路路路路路路路路路路路100 m3
7.9 Inlet system
Air inlet comes into the cylinder of main machine after turbocharged, to prevent the machine weary and clean air. Muffler is generally installed between turbocharger and air filter, which can reduce the high-frequent noise produced by the turbocharger. The inlet system contains shutter, inlet filter and inlet muffler, which forms the inlet filtration muffler module with each equipment combined. Figure 6: Diagram of inlet system
Air flow路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路30.5 t/h
Inlet muffler 路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路30dB (A)

7.10 Exhaust system The burned exhaust gas is pushed out by turbocharger, the temperature from 300Celsius Degree to 335Celsius Degree depending on the load of engine and used fuel. Before push put exhaust gas, it is recovering waste heat first by the
muffler, then by the exhaust boiler. If needed, the second exhaust cleaned system, such as desulphurization equipment, is also installed. The exhaust system includes exhaust muffler, exhaust boiler and
 
desulphurization equipment.
 
Figure 7: Diagram of exhaust system
7.10.1 Exhaust muffler
Function: Reduce the exhaust noise of engine.
Exhaust flow 路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路66.6 t/h
Exhaust muffler 路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路25 dB (A)
7.10.2 Exhaust boiler Function: Exhaust energy circulation use for heat of heavy fuel oil, water and lubricating oil, heat tracing, containing exhaust muffler, boiler body, air manifold, water pump and control switch cabinet.
Evaporation capacity路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路2.5 t/h Pressure 路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路9 bar Temperature路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路175Celsius Degree
7.11 Leaked oil & decontamination module
This unit includes fuel leaked oil tank, lube sludge tank, sludge pump and exhaust oil pump, with function for collecting leaked fuel then supplying heavy fuel oil separating module. The lube oil sludge separated by the unit delivers to the oil sludge tank. Also, the oil sludge separated by heavy fuel oil separating module delivers to the oil sludge tank through the leaked oil pump.
Sludge and exhaust oil pump 路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路1.8 m3/h锛?bar (one standby one use)

Fuel leaked oil tank 路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路750 L
heated by the steam
Lube sludge tank 路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路750 L
heated by the steam
7.12 Compressed air system
 

 
Compressed air system mainly contains starting air container, working air container, pressure reducing valve and air compressor.
7.12.11 Starting air container路路路路路路路路路路路路路路路路路路路路路路路路路路路路路Quantity: 2
Capacity 路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路1000 L, 30bar
7.12.2 Working air container 路路路路路路路路路路路路路路路路路路路路路路路路路路路路路Quantity: 1 Capacity 路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路500 L, 10bar
7.12.3 Pressure reducing valve 路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路Quantity: 2 Capability路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路30-7bar
7.12.4 Air compressor路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路Quantity: 2 Capability 路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路30bar, 52 m3/h
7.13 Electrical equipment of generating sets
Medium voltage switchgear mainly includes switch cabinet of generating sets, feeder switch cabinet and BAB Foundation cabinets.
7.13.1 Switch cabinet of generating sets Cabinet 路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路KYN28-12 Dimensions路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路800(W)脳1500(D)脳2200锛圚锛塵m Breaker 路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路VS1circuit breaker 12kV 锛?30A锛?-pole 25kA
Draw out type circuit breaker
Protection 路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路PWZB
Quantity路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路6 side

7.13.2 Feeder switch cabinet Cabinet 路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路KYN28-12 Dimensions路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路800(W)脳1500(D)脳2200锛圚锛塵m Breaker 路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路VS1 circuit breaker 12kV锛?000A锛?-pole 40kA
Draw out type circuit breaker
Protection 路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路PWZB
Quantity路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路1 side

7.13.3 PT cabinet
Cabinet 路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路KYN28-12
Dimensions路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路800(W)脳1500(D)脳2200锛圚锛塵m
Quantity路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路1 side

7.13.4 BAB Foundation cabinets
Dimensions路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路800(W)脳1500(D)脳2200锛圚锛塵m
Dimensions
Color 路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路Camel gray
Quantity路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路6 side
7.13.5 Control panel of generating sets Dimensions路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路800(W) 脳800(D) 脳2200(H) mm Color 路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路Camel gray
Quantity路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路6 side Containing control switch, controller, control relay, sensory and alarm display window, etc. Control function
Engine speed regulator
Digital synchronization & load control
Automatic voltage regulation
Voltage monitoring
Frequency monitoring
Breaker chain
Breaker closing
Breaker tripping
Engine auxiliary module control
Engine starting and shutdown
Alarm display window Generator control panel displayed the parameter of shutdown and alarm related to electricity and machinery. The parameter of shutdown comes from hard-wired contact end voltage of engine protection system, while the alarm settings is produced by the analog signal from installed sensory according to the main control module. The company can provide different kinds of sensory, such as 4-20mA and PT100.

The displayed alarm & shutdown parameter as follows:
Indicator light of control power supply
Indicator light of engine starting malfunction
Indicator light of emergent shutdown
Engine over-speed indicator light
High engine temperature
High engine oil temperature
Engine coolant level
Low oil pressure
Differential malfunction
Generator over-current
Grounding malfunction

Loss of voltage \ over-voltage
Reverse power
Loss of magnet
High winding temperature
High bearing temperature
High temperature of exhaust pipe
High temperature of exhaust
Low fuel oil level
Low temperature of coolant
Regulator malfunction
Monitor of metal particles in oil pan
Malfunction of lube treatment facility

7.13.6 Direct current cabinet Dimensions路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路800(W)脳600(D)脳2200(H) mm Quantity路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路1 side
AC input voltage 路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路AC 480V卤15%锛?0Hz锛宼hree phase four wire system锛?two input electrical power DC Output Voltage 路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路DC220V 锛?(Working voltage of auxiliary switch cabinet锛?
Battery capacity路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路Plumbonic acid battery non-maintenance 65Ah Precision of voltage regulation路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路鈮ぢ?.5% Precision of steady current 路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路鈮ぢ?.5% Ripple factor路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路鈮ぢ?.5% System efficiency 路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路鈮?0% Power factor (PF) 路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路鈮?.92 Operation noise 路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路鈮?0dB Dielectric strength 路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路2000V/min no flashover, no disruption Grounding resistor路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路锛?.1惟 Output return circuit路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路Standard configuration: KM 5, HM 5. Cabinet structure 路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路Product screen body of our company adopt PK
structure, the front with glass doors
Grade of Protection 路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路路IP30

7.14 Architectural equipment
Architectural equipment includes infrastructure, power plant, pump plant, maintenance workshop, basic equipment, frozen soils construction referred to local environment and detailed construction schedule, subsequently communicated among the buyer, designing institute and the sealer.
1        The practicable contents for the contractor
2        Technical data and drawings of products
 

No.
Contents
Remarks
1
The whole design of power station
Project design satisfied for local environment
2
Construction project, equipment foundation construction
 
3
Units in place
 
4
Installation of power station equipment
 
5
Pipes (oil pipe, water pipe, air pipe, smoke pipe, tracing pipe, etc.)
 
6
Oil tank& construction, heavy fuel oil separating unit
 

 

7
heavy fuel oil, diesel oil, lube unloading oil equipment
 
8
Unit station service transformer, generator transformer, electricity transmission
 
9
Cable, wire, bridge
 
10
1000kVA auxiliary machine
 

 
9.1 General requirements
9.1.1 The data provided by the sealer should be the national legal system of units, ie International System of Units, language be Chinese, the foreign drawings and files of import parts be provided foreign original documents. The sealer will provide the whole information and drawing according to units technical specifications, technical requirements, scope of supply and guaranteed conditions.
9.1.2 The drawings offered by the sealer should be clear and micro-copied drawings are forbidden to be offered. The organization structure of data is to be clear and strict in logic. The content of data must be correct, accurate, clear and comprehensive, meeting the project.
9.1.3 The sealer should provide the data related with the equipment design in time.
9.1.4 If to be found, the sealer will provide the files and data free of charge to other data not lined in the contract but project to be needed. When the equipment make an improvement, the sealer will provide the new technical data free of charge in time.
9.2 Basic Requirements of information presentation
9.2.1 Technical files of coordination with project design data and drawings
The sealer will provide the data and drawings satisfied for the project design, project installation and operation maintenance.
As following

No
Designation
Qty.
time
Remarks
1
Unit profile, unit installation system drawing, drawings of external
1
In one half a month after contract signing
AUTOCAD E-document
2
The basic reference diagram of generating sets
1
In one half a month after contract signing
AUTOCAD E-document
3
Reference diagram of power plant
1
In one half a month after contract signing
AUTOCAD E-document
4
Principle diagram of system electricity, switch cabinet (one or two return circuit, chain, signal return circuit and external contacts )
1
In one half a month after contract signing
AUTOCAD E-document
5
Switch cabinet, outlet cabinet installation and connecting diagram
1
In one half a month after contract signing
AUTOCAD E-document

 
9.2.2 The technical files as data and diagram delivered with equipment
The sealer shall provide the needed data and diagram satisfied for the project installation, pre-commissioning, performance acceptance and operation maintenance in time (rather than the following files).

_

_

No.
Designation
Qty.
Time
Remarks
1
Drawings of unit profile, external auxiliary equipment and connection dimension, installation drawing
One set
Delivered with the equipment
 
2 _Principle diagram of system electricity, switch cabinet (one or two return circuit, chain, signal return circuit and external contacts )
 
 
3 _Diagram of units control system
 
 
 

_

_

_

_

_

_

_

_

4
Diagram of external auxiliary equipment control system
 
 
 
5 _Switch cabinet, outlet cabinet installation and connecting diagram
 
 
6 _Installation operating instructions
 
 
7 _Operating instructions
 
 
8 _Maintenance instructions
 
 
9 _Atlas of spare parts
 
 
10 _List of spare parts about operation maintenance and loss
 
 
11 _List of equipment packing
 
 
12 _certification by manufacturer
 
 
 

The Technical Program of HFO Power Station
10. Progress of production and delivery (19-20 months)

 
 
 
 
 
 
Scheduled plan of HFO power station project
 
 
 
No.锛?/B>
Edition\ modification锛?/B>2009/ 0
 
 
 
 
 
 
 
 
 
 
Effective date锛?/B>
 
Period of
 
 
 
 
20XX
 
 
锛?0XX+1锛?
No.
time Project name
Janu ary
Febr uary
Mar ch
Apri l
May
June
July
Aug ust
Sept emb er
Oct ober
Nov emb er
Dec emb er
Janu ary
Febr uary
Mar ch
Apri l
May
June
July
1
Contract signing
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
2
Engine scheduling
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
3
Purchase of generator and auxiliary equipment
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Unit production and test
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
4
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
delivery
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Delivery of unit and
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
5
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
auxiliary equipment
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
6
Equipment installation
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
7
System debug
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
8
Operation training
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 
27
11. Delivery
11.1 Delivery requirements
The buyer is responsible for delivering the equipment and insurance for transportation expenses.

11.2 Package requirements
The sealer is in charge of equipment package, the package costs included in the total amount. The package and delivery be in accordance with the specifications of GB191-73 pictorial markings for handling of packages.
11.3 Place of delivery
Place of delivery in the sealer鈥檚 factory, the buyer should recognize the dispatch goods with the sealer helping to provide truck loading.
11.4 If the damage and loss happen to the equipment in transportation, the sealer will negotiate with the carrier and claim for compensation.
12. The scope of service protection
12.1 Warranty period
Warranty period under scope of supply is one year. In the warranty period, the second party is in charge of free, for the problem of building in quality produced by the defects in equipment manufacture. After the warranty period, the sealer provides the technical consultation free of charge and the spare parts at the best price, also responsible for the life-long maintenance.
12.2 Guarantee of field service
In the warranty period, the sealer could provide more timely and comprehensive service guarantee. The spot service engineers sent by ZGPT are for the after-sales guaranteed work and train the spot operation workers, with food and accommodation provided by the buyer.
12.3 Technical training----to provide the training service free of charge
The sealer can provide the training of five days for ten persons, with food and accommodation provided by the buyer.
12.4 Installation of on-site guidance and commissioning The sealer is responsible for the installation of equipment and commissioning; while the buyer is
28
for solve the just requirements of the spot service engineers in order to ensure all tasks are carried.
12.5 Commitment
12.5.1 The aptitudes for spot service engineers of the sealer as follows: a. Compliance with law, each rules and regulations on site. b. In place on time with strong enterprise and responsibility. c. Knowing about the equipment design in contract, familiar with the structure, having the spot working experience of the same or similar unit, able to do the spot guidance work correctly. d. Healthy for the condition of field work.
12.5.2 The responsibilities of the spot service workers a. The tasks mainly include the processing about problems of equipment quality, guidance for installation and commissioning, participation in trial running and acceptance functional test. b. Before installation and commissioning, the technical workers should speak clearly to the buyer, explained and demonstrate the procedures and methods to be going.
c. The service workers have the right to dealing with all the problems of technology and business, ie, the service workers have to resolve the problems within the time allowed by the buyer, if the quality problems happen. If the sealer entrusts the buyer resolve the problem, the spot service workers of sealer must have the power of attorney and afford the related economic responsibility.
d. Pre-negotiation to the buyer about the normal come& go and change of the spot service workers.
12.5.3 The obligations about the buyer Coordination with the works of the spot service workers and provision with the convenience for life, transport and telecommunications.
The buyer evaluates and recognizes the writing reasonable suggestions, and if the bad result happens for no execution of the buyer, it鈥檚 for buyer's account.
13. Contacts
Both parties will agree in the contract execution stage about the plan, time, place, and contents of contacts.

Copyright©2006-2010 Leda Greenpoweer Beijing
   Fax:0086-10-84568952  E-mail:
ycl1227@163.com