Dear sir,
Here is the quotation of your required transformers to your attached documents and our technical norms which are attached to this quotation.
SFZ-35000/60, SFZ-46000/60, SFSZ-120000/220 Transformers to Algerian projects
Unit: USD
Type of Transformer |
FOB Shanghai Unit Price in USD |
Remarks |
|
SFZ-35000/60 |
611,194.03 |
With imported OLTC |
|
SFZ-46000/60 |
681,716.42 |
With imported OLTC |
|
SFSZ-120000/220 |
1,504,477.61 |
With imported OLTC |
Notes:
1. The above quotation is based on FOB Shanghai in USD, with the Currency exchange rate of USD to Chinese Yuan of 1:6.8, if changed, quotation should be adjusted accordingly.
2. Validity: 3 months from Feb, 2nd, 2009.
3. Payment: 30% by T/T, balance by irrevocable L/C, issued within 20 days after contract effectiveness.
4. Delivery: 4-6 months after contract effectiveness.
5. Transformers are made by our famous producer within our consortium.
6. Quotation Code: 670520090202
Yours,
Yang chun Lin
Project Manager
China National Electric wire&Cable Imp./Exp. Corp. (Chinacables)
Sinoway Trading & Engineering Co, Ltd.
Sinomach Group
Email:[email protected]
Tel: 0086 10 85805516
Fax: 0086 10-84568952
Mobile: 0086 13801218512
D-803, Shengshijiayuan, Road 98, Jianguo, Beijing 100022, China
Doc. No: TS-HV-TR-001
35 MVA 60/10.5 KV POWER TRANSFORMER BRIEF TECHNICAL SPECIFICATION
1.0 General Specification
1.01 The transformer shall be of 3 phase oil immersed with ONAN/ONAF cooling suitable for outdoor service as step down transformer. The ratings and other characteristics are as below:
1.02 Applicable Norm : IEC 60076
1.03 Ambient Temp: Max 55 deg C at elevation less than 1000 m.
1.04 Number of phases 3
1.05 Frequency 50 Hz(±5%)
2.0 Nominal Data
Description |
Unit |
|
Rating Voltages |
kV |
60/10.5 |
Power rating |
MVA |
35 |
Power (ONAN/ONAF) |
MVA |
28/35 |
On Load Tapping |
kV |
60 ± 8 x 1,5% / 10.5 |
Coupling |
- |
Star/Star |
Vector Group |
- |
YNyn0 |
Frequency |
Hz |
50 |
Maximum Oil Temperature |
K |
45 |
Hot Spot Winding Temperature |
K |
65 |
Temperature Class |
|
A |
|
|
HV |
MV |
Isolation Type |
|
Uniform |
Uniform |
Isolation Level |
kV |
72,5 |
12 |
Dielectric Potential at 50Hz |
kV |
140 |
28 |
Induced Voltage (6000 cycles) |
kV |
140 |
Effected |
Shock Voltage (1.2/50 μS) |
kV |
325 |
75 |
No Load Loss |
kW |
26 (with tolerance as per IEC) |
Full Load Loss |
kW |
125 (with tolerance as per IEC) |
Short Circuit Voltage at 750C |
% |
10 (with tolerance as per IEC) |
No-Load Current |
% |
0.4 |
|
|
|
|
|
|
|
|
|
|
3.0 Sound Levels-Standard IEC 551
|
Acoustic Pressure (dB) |
Acoustic Power |
Distance (m) |
ONAN |
68 |
|
0,3 |
ONAF |
70 |
|
2,0 |
Note |
At Nominal Voltage |
4.0 Circuit Bushings
|
HV |
MV |
HV-N |
MV-N |
Type |
Capacitor |
Solid |
Capacitor |
Solid |
Assigned Voltage (kV) |
72,5 |
12 |
72,5 |
12 |
Assigned Current (A) |
630 |
2000 |
630 |
2000 |
Lightening Test Voltage (kV) |
325 |
75 |
325 |
75 |
Maximum Ind.Frequency Test Voltage (kV) |
140 |
28 |
140 |
28 |
Number of Bushings |
3 |
3 |
1 |
1 |
Creepage Distance |
|
|
|
|
|
(mm/kV) |
31 |
31 |
31 |
31 |
Note: The data marked with red color differ from the requirement, and is proposed by the Manufacturer.
Doc.No: TS-HV-TR-002
46 MVA 60/10.5 KV POWER TRANSFORMER BRIEF TECHNICAL SPECIFICATION
1.0 General Specification
1.01 The transformer shall be of 3 phase oil immersed with ONAN/ONAF cooling suitable for outdoor service as step down transformer. The ratings and other characteristics are as below:
1.02 Applicable Norm : IEC 60076
1.03 Ambient Temp: Max 55 deg C at elevation less than 1000 m.
1.04 Number of phases 3
1.05 Frequency 50 Hz(±5%)
2.0 Nominal Data
Description |
Unit |
|
Rating Voltages |
kV |
60/10.5 |
Power rating |
MVA |
46 |
Power (ONAN/ONAF) |
MVA |
37/46 |
On Load Tapping |
kV |
60 ± 8 x 1,5% / 10.5 |
Coupling |
- |
Star/Star |
Vector Group |
- |
YNyn0 |
Frequency |
Hz |
50 |
Maximum Oil Temperature |
K |
45 |
Hot Spot Winding Temperature |
K |
65 |
Temperature Class |
|
A |
|
|
HV |
MV |
Isolation Type |
|
Uniform |
Uniform |
Isolation Level |
kV |
72,5 |
12 |
Dielectric Potential at 50Hz |
kV |
140 |
28 |
Induced Voltage (6000 cycles) |
kV |
140 |
Effected |
Shock Voltage (1.2/50 μS) |
kV |
325 |
75 |
No Load Loss |
kW |
28.5 (with tolerance as per IEC) |
Full Load Loss |
kW |
141 (with tolerance as per IEC) |
Short Circuit Voltage at 750C |
% |
12 (with tolerance as per IEC) |
No-Load Current |
% |
0.4 |
|
3.0 Sound Levels-Standard IEC 551
|
Acoustic Pressure (dB) |
Acoustic Power |
Distance (m) |
ONAN |
68 |
|
0,3 |
ONAF |
70 |
|
2,0 |
Note |
At Nominal Voltage |
4.0 Circuit Bushings
|
HV |
MV |
HV-N |
MV-N |
Type |
Capacitor |
Solid |
Capacitor |
Solid |
Assigned Voltage (kV) |
72,5 |
12 |
72,5 |
12 |
Assigned Current (A) |
630 |
3150 |
630 |
3150 |
Lightening Test Voltage (kV) |
325 |
75 |
325 |
75 |
Maximum Ind.Frequency Test Voltage (kV) |
140 |
28 |
140 |
28 |
Number of Bushings |
3 |
3 |
1 |
1 |
Creepage Distance |
|
|
|
|
|
(mm/kV) |
31 |
31 |
31 |
31 |
Note: The data marked with red color differ from the requirement, and is proposed by the Manufacturer.
|