Doc No:TS-HV-TR-003
120 MVA 220/63/10.5 KV POWER TRANSFORMER BRIEF TECHNICAL SPECIFICATION
1.0 General Specification
1.01 The transformer shall be of 3 phase oil immersed with ONAN/ONAF cooling suitable for outdoor service as step down transformer. The ratings and other characteristics are as below:
1.02 Applicable Norm : IEC 60076
1.03 Ambient Temp: Max 55 deg C at elevation less than 1000 m.
1.04 Number of phases 3
1.05 Frequency 50 Hz(±5%)
2.0 Nominal Data
Ratings |
HV |
MV |
IMV |
HVN |
MVN |
Power (MVA) |
120 |
120 |
40 |
|
|
Voltage (kV) |
220 |
63 |
10,5 |
|
|
Couplage |
YNyn0d11 |
Lightening Shock Potential Bearing |
Peak |
1050 |
325 |
75 |
400 |
325 |
Eff. |
|
|
|
|
|
Maximum Operating Voltage (kV) |
460 |
140 |
28 |
200 |
140 |
Applied Test Voltage (kV) |
460 |
140 |
28 |
200 |
140 |
Apparent Short Circuit Power (MVA) |
As per IEC |
As per IEC |
As per IEC |
|
|
Short Circuit Current Duration (s) |
2 |
Voltage Variation Category |
CFVV (Constant Flux Variation Voltage) (*) |
Load Regulation |
YES |
|
|
|
|
No-Load Regulation |
NO |
|
|
|
|
On Load Tapping
Nr. of Steps x (%) |
+ |
13x1,38% |
|
|
|
|
- |
13x1,38% |
|
|
|
|
|
|
|
|
|
|
|
Note (*) |
Typical. It is not a must. |
3.0 Losses
Description |
kW |
Tolerance (%) |
No Load Loss, P0 |
|
60 |
15 |
Full Load Loss, Pk |
HV/MV |
290 |
15 |
Auxiliary Losses, Paux |
|
12 |
|
Total Loss (P0+Pk) |
|
350 |
10 |
|
|
|
|
Note: |
These are typical values. Please provide your own values if different |
4.0 Short Circuit Voltage
Between the Coils |
Uk (%) |
Tolerance (%) |
Power (MVA) |
Regulaiton Position |
HV/MV |
|
|
|
+ |
12 |
±10 |
120 |
0 |
|
|
|
- |
HV/IMV |
7.33 |
±10 |
40 |
0 |
MV/IMV |
2.67 |
±10 |
40 |
0 |
5.0 Temperatures and Cooling
Maximum Oil Temperature 45K
Maximum Winding Temperature 55K
Hot Spot Temperature Value 65K
Cooling Method |
ONAN |
ONAF |
OFAF |
OFWF |
ODAF |
(%) |
75 |
100 |
|
|
|
6.0 Sound Levels-Standard IEC 551
|
Acoustic Pressure (dB) |
Acoustic Power |
Distance (m) |
ONAN |
75 |
|
0,3 |
ONAF |
80 |
|
2,0 |
Note |
At Nominal Voltage |
7.0 Circuit Bushings
|
HV |
MV |
IMV |
HV-N |
MV-N |
Type |
Capacitor |
Capacitor |
Solid |
Capacitor |
Capacitor |
Assigned Voltage (kV) |
245 |
72,5 |
12 |
126 |
72,5 |
Assigned Current (A) |
630 |
1250 |
3150 |
630 |
1250 |
Lightening Test Voltage (kV) |
1050 |
325 |
75 |
400 |
325 |
Maximum Ind.Frequency Test Voltage (kV) |
460 |
140 |
28 |
200 |
140 |
Number of Bushings |
3 |
3 |
3 |
1 |
1 |
Creepage Distance |
|
|
|
|
|
|
(mm/kV) |
31 |
31 |
31 |
31 |
31 |
Note: The data marked with red color differ from the requirement, and is proposed by the Manufacturer. |