DESCRIPTION |
UNIT |
SUPPLIER’S REQUIRE-
MENTS |
1 |
Standard to which the cable conform |
- |
IEC STANDARDS |
2 |
Conductor Material |
- |
Copper Alumimium |
3 |
Number and diameter of Conductor Strands |
No/mm |
87/2.75 87/3.14 |
4 |
Conductor Shape |
- |
compact stranded circular |
5 |
Conductor Diameter |
mm |
26.6 30.0 |
6 |
Conductor Cross-sectional Area |
mm2 |
1*500 1*630 |
7 |
Min. Thickness of semi-conductive conductor shield
Nominal |
mm |
0.2 0.2
0.8 0.8 |
8 |
Insulation Material |
- |
XLPE XLPE |
9 |
Min. thickness of insulation
Nominal |
mm |
7.1 7.1
8.0 8.0 |
10 |
Nominal thickness of semi-conductive insulation shield |
mm |
1.0 1.0 |
11 |
Diameter over insulation |
mm |
44.2 47.6 |
12 |
Min. thickness of semi-conductive insulation shield |
mm |
0.3 0.3 |
13 |
Thickness of copper shield tape |
mm |
0.12 0.12 |
14 |
Number of copper shield tapes |
No. |
2 2 |
15 |
Diameter over shield tape |
mm |
46.6 50.0 |
16 |
Minimum thickness of bedding |
mm |
1.16 1.16 |
17 |
Nominal thickness of bedding
|
mm |
1.7 1.7 |
18 |
Number and diameter of non-metallic armour wire |
No./mm |
3.2/50 3.2/63 |
19 |
Oversheath Material |
- |
MDPE MDPE |
20 |
Minimum oversheath thickness |
mm |
2.04 2.04 |
21 |
Nominal oversheath thickness |
mm |
2.8 2.8 |
22 |
Outer diameter of cable |
mm |
62.2 65.6 |
23 |
Conductor DC resistance per km at 20oC and 50Hz |
ohm/km |
0.037 0.0458 |
24 |
Short circuit capacity of copper shield for one second with a prior phase conductor temperature of 90oC |
kA |
71.4 59.6 |
25 |
Max. Delivery length per drum |
m |
500 500 |
26 |
Weight of conductor per km |
kg/km |
4481 1701 |
27 |
Weight of cable per km |
kg/km |
8800 6700 |
28 |
Gross weight of full cable drum |
kg |
6000 5000 |
29 |
Size of cable drum |
mm |
2500*1250*1120 |
30 |
Manufacturer’s name |
- |
HQ |
31 |
Country of origin |
- |
P.R.China |