4. Guaranteed Technical Particulars
(220 KV XLPE CABLE)
- General
1.1 Manufacturer: Chongqing Electric Wire & Cable Co., Ltd.
1.2. Place of manufacture: 239 Jinguo Ave., Yubei National Agricultural Technology Park, Chongqing P.R.China
1.3 Type/designation: YJLW02-127/220kv-1*800 (Cu/XLPE/Corrugated Al. sheathed/PVC)
1.4 Applicable standards (Please list all applicable standards)
a) IEC 62067(2001) Power cable with extruded insulation and their accessories for related as amended/revised till date, as applicable.
b) IEC 60228(1978) Conductor for insulated cables.
c) IEC 60229(1982) Tests on cable over sheaths.
d) IEC 60230(1966) Impulse tests on cables and their accessories.
- Main data (applicable to cable and accessories)
2.1 Rated system voltage kV: 127/220
2.2 Highest voltage for equipment Um kV : 245
2.3 Rated frequency
o Normal condition Hz: 50
o Exceptional condition Hz: 49~61
2.4 Rated power frequency withstand voltage kVrms: 460KV/1min
2.5 Rated lightening impulse KV peak:
o Rated switching impulse withstand voltage kV peak: 1050KV
2.6 15 minute dry power frequency withstand test voltage KVrms 254KV/15min
2.7 Maximum partial discharge PC attest voltage kVrms: No discharge tested
2.8 Test voltage after laying, applied on complete installation (cable and cable end seals) kV: 216 KV (1.7 U0) AC voltage , 1 hour ; or 127 KV (U0) AC voltage , 24 hours
2.9 Maximum permissible operating temperatures at:-
o Continuous rated operation Celsius Degree: 90
o Short time emergency (overload) operation Celsius Degree 105
o Short-circuit condition Celsius Degree 250
3.0 Cable construction
o Conductor cross section mm2 :800
o Conductor design : 5 segments
o Conductor material : Annealed copper
o Type of screen : consists of metal screen layer and non-metal screen layer
o Screen cross-section mm2: 927(metal screen )
o Screen material : Electric aluminum ( metallic ) , super clean and super smooth semi-conducting XLPE ( compound )
o Material for metallic screen : Electric aluminum
o Thickness of XLPE insulation mm : 25.0
o Thickness of outer PE sheath mm : 5.0
o Outer diameter of cable mm : 116.4
o Minimum bending radius mm :2660( during installation );1995( installation ready )
o Weight of cable kg/rn :17.03kg/m
4.0 Electrical ratings of cable
a) Rated continuous current considering specified cable laying Amps: 1025 A ( direct buried trefoil formation laying at a depth 1.5 meters , soil temperature at 30 Celsius Degree , thermal resistivity 1.2 Cm/w )
b) Short time withstand current
o Of conductor KArms :114.5KA/1s
o Of screen kArms :66KA/1s
o Earth fault current kArms : 86.34KA/1s
o Dynamic short circuit withstand current kApeak : 86.34KA/1s
c) Screen/sheath losses per phase :1.76w/m
d) DC resistance at 20 Celsius Degree:
e) Of conductor Ohm/km :0.0221
f) Of screen Ohm/km :0.0443
g) AC resistance of conductor at 90 Celsius Degree Ohm/km :0.0311
h) Capacitance per phase 0.144 μF/km
i) Surge impedance nF/km :57.2Omega
j) Total cable losses at rated current, considering proposed screen earthing
o Per phase:25.41kw/km
o Dielectric losses per phase kW/km :0.4 kw/km
5.0 Tower sealing end termination Outdoor termination
5.1 Manufacturer : out door termination supplied by cable accessories manufacturer
5.2 Type designation :
5.3 Place of manufacturer :
INFORMATIVE DATA
1. Cable length from one end to the other tower gantry :
1.1 Maximum electric field strength at the conductor at 220 Kv (highest system voltage) kV/mm :7.23
1.2 Charging current per phase at 220 kV A/km :6.32
1.3 Inductance between conductors/per phase mH/km :0.5941
1.4 Inductance between conductor and screen : 0.05mH/km
1.5 Screen inductance :0.5441mH/km
1.6 Induced voltage on screen :0.0001 V/A.m
1.7 Electric stress at conductor screen :7.23KV/mm
1.8 Electric stress at insulation screen :3.23KV/mm
1.9 Circulating screen/sheath/armour/current : 0
1.10 Positive Sequence impedance per phase: 0.1881Omega/km
1.11 Negative Sequence impedance per phase: 0.1881Omega/km
1.12 Zero sequence impedance per phase: 0.5969Omega/km
1.13 Proposed cable laying
o laying in : Underground
o maximum ambient temperature °C :50
o arrangement of single phase cables : Trefoil formation or Flat formation
1.14 Total estimated length of single phase cable Metres: 500m
1.15 Bending Radius for pulling :2660mm
1.16 Bending Radius below terminal :2660mm
For more about Xlpe cables, ACSR, or other power cables, click here.