GAS PRESSURE CONTROLLER 27889 - 1 Each
· Type: R100S 4" - ANSI 300# Equipped with Pilot P095-MPS and 3 Layer coating
· Serial No: 2007031951 2007
· DN 100 PN: Class 300#
· Ps/Pu max: 50 Bar PT-75 Bar
· Wd: 0.5 ----12 Bar
· Wds: 1.5 ---- 5.0 Bar
· Ts : -20/60 Deg C
· Flow Rate 5000 Nm3/Hr
· Flow Direction Left to Right
· In let Operational Pressure 25 Bar Out pressure Set pressure: 0.4 Bar
· Media: Natural Gas Fluid
· Standard: EN 334
· DIN-DVGW: NG-4301AU0385
· Directive: 97/23EC b+D
· Client Ref: 606893
· Make: Gorter - Honeywell
Material specifications (standard) Part Material Valve body A352-LCC (QT) (1�?DN25 S355N) Guide bushing S355 or Equal Bottom flange A352-LCC (1�?DN25 S355) Special materials upon request. Part Material Diaphragm NBR with nylon reinforcement Silencer Metal foam (CvNi) Dynamic O-rings Viton Static O-rings NBR Pilot body S355N or equal Classification acc. DIN 3380 / EN334 Accuracy class / Pa �?3 bar : RG 2.5 / SG 10 lock-up pressure class Pa > 3 bar : RG 1 / SG 2.5 Lock-up pressure zone SZ = 2.5 DIN-DVGW registered & CE marked Note: All pressures listed are overpressures. technical specifications DN A C L oB Qn = capacity in mn3/h Pe = inlet pressure in bars Pa = outlet pressure in bars Cg = flow coefficient d = relative density (air=1) Te = temperature of the gas at the inlet of the regulator rn = density of the gas in normal conditions (with T=273 Kelvin) For natural gas with ρn = 0.83 kg/m3 d = 0.643 For gasses other than natural gas d = ρn gas/1.29 In case of a combination regulator and monitor, use the following serial thesis: Cg_tot = This Cg-tot can be filled in as Cg in one of the above mentioned formulas. The following formulas can be used to determine the capacity. Capacity calculation Dimensional sketch R100 General Type indication BAAI-R100 series Pressure class ANSI 300 and ANSI 600(*) Inlet pressure range 3 to 50 bar ANSI 300, 100 bar ANSI 600 Outlet pressure range 1-49.5 bar ANSI 300 1-60 bar ANSI 600 Min. pressure difference needed for correct operation 0.5 bar Operating temperature -20oC to + 60oC Ambient temperature -30oC to + 60oC (*) Other pressure classes up to ANSI 2500 are available. Flow coefficient Nominal size (inches/mm) Cg value R100 \ R100S \ R100(S)-M \ R100-M \ R100SO R100(S)-(SO) 1" 25 400 370 2" 50 2,000 1,210 3" 80 4,000 2,800 4" 100 6,760 4,970 6" 150 14,400 10,100 8" 200 27,100 19,700 10" 250 37,000 30,000 12" 300 48,000 38,500 Flow coefficient for R101S on request. Q n = for Pa �?0.5 Pe Q n = 13.94 d(Te + 273) .Cg. (Pe-Pa).Pa for Pa �?0.5 Pe 6.97 d(Te + 273) .Cg.Pe 1 1 1 Cg Monitor Cg Regulator 2 2 + Measurements (mm) and weights (kg) Nominal Size (inches/mm) Inches mm A B C L Weight 1" 25 260 230 75 216 50 2" 50 355 290 120 292 95 3" 80 415 350 150 356 160 4" 100 480 430 175 432 280 6" 150 640 625 240 559 690 8" 200 790 655 300 660 950 10" 250 1110 655 320 838 1250 12" 300 1400 521 320 838 1600 10" and 12" are top entry design
|