1 |
Current-To-Pneumatic Converter E69P-TI1V-JS / CS-E/FN-A E69F SERIES PREFIX: Field Mounted. Enclosure Provides NEMA Type 4 Environmental Protection. T HOUSING: Threaded Cover - Explosionproof I INPUT SIGNAL AND IMPEDANCE: 4 To 20, 4 To 12, Or 12 To 20 mA dc (170 ohm Input Impedance) As Specified 1 OUTPUT SIGNAL: 0 To 35 psi, 0 To 240 kPa, Or 2.4 bar or kg/cm² V LEVER ASSEMBLY KIT: Universal For Non Foxboro Valves Used With P25, P50, P110, And Other Actuators J OPTIONAL MODEL SUFFIX(ES) INCLUDED: Explosionproof Junction Box R OPTIONAL MODEL SUFFIX(ES) INCLUDED: Adjustable Filter Regulator Without Gauge CS-E/FN-A Electrical Classification FM Certified Nonincendive FM Certified Nonincendive For Class I, Groups A, B,C, And D, Division 2 And Class II, Group G, Division 2. Also Suitable For Use In Ordinary Locations. Temperature Class T6. Input Signal 4 to 20mA |
FOXBORO |
E69P-TI1V-JS / CS-E/FN-A |