SCOPE OF SUPPLY FOR 40MW HFO Gen-set |
|
|
|
|
|
|
|
|
SU: Supply by Supplier; CT: Prepare by Buyer; |
|
|
|
|
|
NO. | ITEM | SPECIFICATION | QTY. | UNIT | SCOPE | REMARKS |
SU | CT |
(A) | GENERATING SET 50Hz, 11KV |
(A-1) | HFO Engine | 7SETS MAN 10L3244 5400KW | 7 | units | �?/td> |
|
|
(A-2) | HFO Engine | 1 SET ROLLS-ROYCE BB3345 3500KW | 1 | units | �?/td> |
|
|
(A-3) | Flexible coupling | HGT | 8 | units | �?/td> |
|
|
(A-4) | Alternator with AVR | 11kV 50Hz | 8 | units | �?/td> |
|
|
(A-5) | Common base frame |
| 8 | units | �?/td> |
|
|
| Foundation bolts |
| 8 | units | �?/td> |
|
|
(A-6) | Local control desk |
| 8 | units | �?/td> |
|
|
| Pressure gauges |
|
|
|
|
|
|
| Temperature indicators |
|
|
|
|
|
|
| Exhaust temperatures |
|
|
|
|
|
|
| operate switches |
|
|
|
|
|
|
| Flasher |
|
|
|
|
|
|
(B) | DO FUEL OIL SYSTEM UNIT |
(B-1) | DO Storage Tank | 200m3 vertical | 1 | unit |
| �?/td> |
|
(B-2) | DO unloading unit |
| 1 | unit | �?/td> |
|
|
| DO unloading pumps | 58m3/h,2.5Bar | 2 | pcs |
|
|
|
| Strainers for DO pumps | Basket type | 1 | PC |
|
|
|
| Flow meter |
| 1 | PC |
|
|
|
| Piping and fitting |
| 1 | lot |
|
|
|
| Valves |
| 1 | lot |
|
|
|
| Gauges |
| 1 | lot |
|
|
|
| Underpan and frame |
| 1 | set |
|
|
|
| Control cabinet |
| 1 | set |
|
|
|
(B-3) | Daily service tank | 10m3 horizontal | 2 | unit |
| �?/td> |
|
(C) | HEAVY FUEL OIL (HFO) SYSTEM |
(C-1) | HFO Storage Tank | 600m3 | 2 | pcs |
| �?/td> |
|
(C-2) | HFO unloading unit |
| 2 | unit | �?/td> |
|
|
| Each including: |
|
|
|
|
|
|
| HFO unloading pumps | 58m3/h,2.5Bar | 2 | pcs |
|
|
|
| Strainers for HFO pumps | Basket type 30 mesh | 1 | PC |
|
|
|
| Flow meter |
| 1 | PC |
|
|
|
| Piping and fitting |
| 1 | lot |
|
|
|
| Valves |
| 1 | lot |
|
|
|
| Gauges |
| 1 | lot |
|
|
|
| Underpan and frame |
| 1 | set |
|
|
|
| Thermal oil heating circuit |
| 1 | set |
|
|
|
| Control cabinet |
| 1 | set |
|
|
|
(C-3) | HFO buffer tank | 200m3 vertical | 2 | units |
| �?/td> |
|
(C-4) | HFO daily tank | 200m3 | 1 | unit |
| �?/td> |
|
(C-6) | HFO purifier separator Unit |
| 4 | unit | �?/td> |
|
|
| Each including: |
|
|
|
|
|
|
| Centrifuge separator | SJ60 | 1 | Pcs |
|
|
|
| Separator preheater | Steam heater | 1 | Pcs |
|
|
|
| Transfer pumps | Screw type | 2 | Pcs |
|
|
|
| Strainers |
| 1 | Pcs |
|
|
|
| Three way valves |
| 1 | Pcs |
|
|
|
| Sludge tanker and frame |
| 1 | sets |
|
|
|
| Sludge pump |
| 1 | sets |
|
|
|
| Control water boost pump |
| 1 | sets |
|
|
|
| Control cabinet |
| 1 | sets |
|
|
|
(C-7) | HFO Booster Unit |
| 4 | unit | �?/td> |
|
|
| Each including: |
|
|
|
|
|
|
| Supply pump | Screw type | 2 | sets |
|
|
|
| Strainer | Basket type | 1 | PC |
|
|
|
| Flow meter |
| 1 | PC |
|
|
|
| Pressure regulating valve |
| 1 | PC |
|
|
|
| Auto recoil filter | 34μm | 1 | PC |
|
|
|
| Bypass filter |
| 1 | PC |
|
|
|
| Mixer and degas tanker |
| 1 | PC |
|
|
|
| Circulating pumps | Screw type | 1 | set |
|
|
|
| HFO heater | Steam heater | 1 | PCs |
|
|
|
| Viscosity sensor module |
| 1 | PC |
|
|
|
| Temperature controller |
| 1 | PC |
|
|
|
| Actuator valve |
| 1 | PC |
|
|
|
| Fuel pressure control valve |
| 1 | PC |
|
|
|
| Valves, gauges and fitting |
| 1 | lot |
|
|
|
| Underpan and frame |
| 1 | set |
|
|
|
| Control cabinet |
| 1 | lot |
|
|
|
(C-8) | Sludge oil tank | 30m3 | 1 | unit |
| �?/td> |
|
(C-9) | Sludge pump station |
| 1 | unit | �?/td> |
|
|
(C-10) | Oily water pond |
| 1 | unit |
| �?/td> |
|
(D) | Lubricating oil system unit |
(D-1) | Lubricating oil purifier separator Unit |
| 8 | unit | �?/td> |
|
|
(D-2) | Lubricating oil filling unit |
| 1 | set | �?/td> |
|
|
| Gear pump |
| 1 | Pc |
|
|
|
| Underpan and frame | with wheel | 1 | set |
|
|
|
| Control switch | CW and CCW control | 1 | set |
|
|
|
(D-3) | Lubricating supply oil unit |
| 8 | sets | �?/td> |
|
|
| Prelubricating oil pump | motor driven | 8 | Pcs | �?/td> |
|
|
| Labor prelubricating pump |
| 8 | Pcs | �?/td> |
|
|
| Lubricating oil cooler | Plate type | 8 | sets | �?/td> |
|
|
| Lubricating oil filter | Duplex type | 8 | sets | �?/td> |
|
|
| Pressure regulating valve |
| 8 | sets | �?/td> |
|
|
| Thermostatic valve | Thermosensive element driven type | 8 | sets | �?/td> |
|
|
|
|
|
|
|
|
|
|
(E) | Compressed air system unit |
(E-1) | Starting air compressor unit | Motor driven | 3 | units | �?/td> |
|
|
| Starting air compressor |
| 3 | sets |
|
|
|
| Pressure switch | Low pressure auto start | 3 | sets |
|
|
|
| Valve,piping and fitting |
| 3 | sets |
|
|
|
| Relief valves |
| 3 | sets |
|
|
|
| Control cabinet |
| 3 | sets |
|
|
|
(E-2) | Starting air compressor unit | Diesel engine driven | 1 | unit | �?/td> |
|
|
| Diesel compressor | For black out start | 1 | set |
|
|
|
| Valve,piping and fitting |
| 1 | set |
|
|
|
| Relief valve |
| 1 | set |
|
|
|
(E-3) | Air Receiver unit | 500L 30bar | 3 | PCs | �?/td> |
|
|
| Gauges and valves |
| 3 | sets |
|
|
|
| Relief valves |
| 3 | PCs |
|
|
|
| Control valve for turning | Safety lock for start | 3 | sets | �?/td> |
|
|
| High pressure air filter |
| 3 | sets | �?/td> |
|
|
(F) | Cooling system unit |
(F-1) | Radiator |
| 8 | units | �?/td> |
|
|
| Frame and expansion tank |
| 8 | sets |
|
|
|
(F-2) | Low Cooling water pump | Motor driven type | 8 | sets | �?/td> |
|
|
| Control cabinet |
| 8 | sets |
|
|
|
| HT water cooling pump | Engine driven | 8 | sets | �?/td> |
|
|
| HT thermostatic valve | Thermosensive element driven type | 8 | sets | �?/td> |
|
|
| HT water cooler | Plate type | 8 | sets | �?/td> |
|
|
| HT water expansion tank |
| 8 | sets | �?/td> |
|
|
| Valve, piping and fitting |
| 1 | lot | �?/td> |
|
|
(F-3) | Water soften device |
| 2 | units | �?/td> |
|
|
| Brine tank |
| 1 | sets |
|
|
|
| local control cabinet |
| 1 | sets |
|
|
|
| Water supply pump |
| 2 | sets |
|
|
|
| Water softeners |
| 1 | sets |
|
|
|
| Hydro booster tank |
| 1 | sets |
|
|
|
(F-4) | Soften water tank |
| 1 | unit |
| �?/td> |
|
(G) | Exhaust gas and steam system |
(G-1) | Exhaust gas silencer | 25dBA reduce | 8 | units | �?/td> |
|
|
(G-2) | Expansion bellow |
| 8 | sets | �?/td> |
|
|
(G-3) | exhaust boiler |
| 8 | units | �?/td> |
|
|
(G-4) | exhaust SCR |
| 8 | units | �?/td> |
|
|
(H) | Intake air system |
(H-1) | Air intake filter | On workshop wall | 8 | units |
| �?/td> |
|
(I) | 11kV Eectrical system |
(I-1) | Generator switchgear | KYN28A 630A | 8 | units | �?/td> |
|
|
(I-2) | Busbar PT panel | KYN28A | 1 | unit | �?/td> |
|
|
| Voltage transformer PT | 11/�?/span>3, 0.1/�?/span>3, 0.1/3 kV | 3 | Pcs |
|
|
|
| Surge arrester | 19/45 | 3 | Pcs |
|
|
|
| Fuse |
| 3 | Pcs |
|
|
|
| Voltage meter | with phase change switch | 1 | Pc |
|
|
|
| Busbar monitor |
| 1 | Pc |
|
|
|
(I-3) | Station TX panel | KYN28A 630A | 2 | unit | �?/td> |
|
|
| Each including: |
|
|
|
|
|
|
| VCB | VS1 630A 25KA | 1 | set |
|
|
|
| Protection, CT and PT | LZZJB9-11, REZ-11 | 3 | sets |
|
|
|
| Meters, indicators |
| 1 | lot |
|
|
|
| Protection digital relay | DMR 301P | 1 | Pc |
|
|
|
| Surge arrester |
| 3 | Pcs |
|
|
|
| Earthing knift switch |
| 1 | set |
|
|
|
(I-4) | Station TX | 2500kVA 11/0.4kV S11 | 1 | set | �?/td> |
|
|
| Connection mode | Dyn11 |
|
|
|
|
|
(I-5) | Power Plant Outgoing switchgear |
| 4 | units | �?/td> |
|
|
| Each including: |
|
|
|
|
|
|
| VCB | VS1 630A 25KA | 1 | set |
|
|
|
| Protection, CT and PT | LZZJB9-11, REZ-11 | 3 | sets |
|
|
|
| Meters, indicators |
| 1 | lot |
|
|
|
| Protection digital relay | DMR 301P | 1 | Pc |
|
|
|
| Surge arrester |
| 3 | Pcs |
|
|
|
| Earthing knift switch |
| 1 | set |
|
|
|
(I-6) | linkage panel |
| 1 | set |
|
|
|
(I-7) | Isolate panel with PT |
| 1 | set |
|
|
|
(I-8) | Switchgear & Control panel | KYN28A | 8 | units | �?/td> |
|
|
| VCB | VS1 630A 25kA |
|
|
|
|
|
| Protection, CT and PT |
|
|
|
|
|
|
| Meters, indicators |
|
|
|
|
|
|
| Protection digital relay | ICBU360 |
|
|
|
|
|
| PLC |
|
|
|
|
|
|
| AVR |
|
|
|
|
|
|
| Instrumentations |
|
|
|
|
|
|
| Operate switches |
|
|
|
|
|
|
| Synchronization control |
|
|
|
|
|
|
| Load-share device |
|
|
|
|
|
|
(I-9) | Remote control desk |
| 8 | units | �?/td> |
|
|
| Electrcial meters |
|
|
|
|
|
|
| Operate switches |
|
|
|
|
|
|
| Flasher |
|
|
|
|
|
|
(K) | 400V Eectrical system |
(K-1) | Outgoing panel | GCS-2500 | 1 | unit | �?/td> |
|
|
(K-2) | Station LV input panel | GCS | 4 | units | �?/td> |
|
|
| CT |
| 1 | lot |
|
|
|
| Meters, indicators |
| 1 | lot |
|
|
|
| MCCB | RMM | 1 | lot |
|
|
|
| CT |
| 1 | 8 |
|
|
|
| Meters, indicators |
| 1 | lot |
|
|
|
(K-3) | Plant transformer (1250kVA 11KV//0.4KV) |
| 1 | set |
|
|
|
(L) | Power Plant control |
(L-1) | Air compressor control box | KFT for remote control | 1 | units | �?/td> |
|
|
(L-2) | Gen-set Aux. Control Panel | KCT | 1 | units | �?/td> |
|
|
(L-3) | Fuel oil field power panel | XL-21 | 1 | unit | �?/td> |
|
|
(L-4) | Seperator power panel | XL-21 | 1 | unit | �?/td> |
|
|
(L-5) | Power plant aux. panel | with socket | 1 | units | �?/td> |
|
|
(L-6) | 400 Volt supply panel for fuel station |
| 1 | unit | �?/td> |
|
|
|
|
|
|
|
|
|
|
(M) | DC system |
(M-1) | DC control panel | PGD7-�?/span> | 1 | unit | �?/td> |
|
|
| DC charger | Emerson AC-DC charger DC 110V | 4 | sets |
|
|
|
| Battery monitor |
| 2 | set |
|
|
|
| Charger control module | PLC | 2 | set |
|
|
|
| Monitor HMI |
| 2 | set |
|
|
|
| DC charger | Emerson AC-DC charger DC24V | 4 | sets |
|
|
|
| DC-DC Convertor | Emerson DC-DC charger | 2 | sets |
|
|
|
(M-2) | Battery panel | 9x12VDC 150Ah + 2x12VDC 150Ah | 2 | unit | �?/td> |
|
|
(O) | Power plant ventilation and lighting |
(O-1) | Power plant ventilation |
| 1 | lot |
| �?/td> |
|
(O-2) | Lighting |
| 1 | lot |
| �?/td> |
|
(P) | Overhead Crane |
(P-1) | Overhead crane | 10T | 1 | set |
| �?/td> |
|
(Q) | Fire fighting system |
(Q-1) | Fire hose |
| 1 | lot |
| �?/td> |
|
(Q-2) | Portable chemical fire extinguishers |
| 1 | lot |
| �?/td> |
|
(Q-3) | Foam fire extinguishing systems |
| 1 | set |
| �?/td> |
|
(Q-4) | Valve and fitting |
| 1 | lot |
| �?/td> |
|
(R) | Installation material |
(R-1) | Valves, pipings, flange |
| 1 | lot | �?/td> |
|
|
(R-2) | Connection bolts and nut |
| 1 | lot | �?/td> |
|
|
(R-3) | Mechanial installation tools |
| 1 | lot | �?/td> |
|
|
(R-4) | Paint, electrical rod |
| 1 | lot | �?/td> |
|
|
(R-5) | Heat insulation rock wool & metal claddings |
| 1 | lot | �?/td> |
|
|
(R-6) | Power plant lightning protection |
| 1 | lot | �?/td> |
|
|
(R-7) | Earthling system |
| 1 | lot | �?/td> |
|
|
(R-8) | Lamps and lanterns,emergency lighting |
| 1 | lot | �?/td> |
|
|
(R-9) | HV cable,LV cable,control cables, wires & termination lugs |
| 1 | lot | �?/td> |
|
|
(R-10) | LV power cables termination lugs |
| 1 | lot | �?/td> |
|
|
(R-11) | HT power cables & termination kits |
| 1 | lot | �?/td> |
|
|
(R-12) | Cable tray, ladders, and support structures |
| 1 | lot | �?/td> |
|
|
(R-13) | Painting - cable tray, ladders, and support structures |
| 1 | lot | �?/td> |
|
|
(R-14) | Cable fireproofing materials |
| 1 | lot | �?/td> |
|
|
(R-15) | Test equipments |
| 1 | lot | �?/td> |
|
|
(S) | Commissioning consumptions |
(S-1) | Acid for piping wash | HCl | 1 | lot |
| �?/td> |
|
(S-2) | Engine lubricating oil | SAE 15WCD40 | 1 | lot |
| �?/td> |
|
(S-3) | Diesel oil |
| 1 | lot |
| �?/td> |
|
(S-4) | Grease | Lithium base 3# | 15 | kg |
| �?/td> |
|
(S-5) | Water |
| 1 | lot |
| �?/td> |
|
|
|
|
|
|
|
|
|
T | Spare parts Documents |
| 2 | set | �?/td> |
|
|
| special tools |
| 1 | set | �?/td> |
|
|