2200kW diesel generator set Technical specification |
| Adopted specifications and standards |
| GB/T2820 “Ac generator set driven by reciprocating internal combustion engine�?/td> |
GB1105.1 Internal combustion engine bench test methods Standard environmental conditions and calibration of power, fuel and oil consumption |
|
二� | Unit operating site environment requirements |
| air temperature | 0-45�?/td> |
Relative humidity | 60%�?5℃) |
atmospheric pressure | 100kPa |
altitude | �?000m |
Power calibration condition | Compliant with ISO-3046 standards |
|
|
Unit model and main technical parameters |
TYPE | KFS2800HB/KIPOR |
rated power/max power | 2200/2420kW |
rated voltage | 6600VAC |
rated current/max current | 245 A |
rated speed/frequency | 1500r/min / 50Hz |
Power factor | 0.8 |
Number of phases/lines | 3 / 4 |
Starting/speed regulation mode | 24VDC Electric motor/electronic speed regulation |
Electrical control system | 24VDC |
Installation mode | Diesel engine and generator are connected by SAE standard interface and installed on common base. The base of the unit is made of high-strength section steel, and a shock absorber is installed between the base and the equipment. |
Unit color | Factory standard |
|
|
Voltage and frequency performance |
Frequency deviation | �?% |
Steady-state frequency difference | �?.5% |
Transient frequency deviation | �?18%�?5% |
Frequency recovery time | �?0s |
Steady-state voltage difference | ≤�?% |
Transient voltage difference | �?35%�?25% |
Voltage recovery time | �?0s |
|
|
|
controller | Crowd intelligence controller |
Rated voltage of the control system | 24VDC |
Basic function | The control panel has three phase voltage, three phase current, power, frequency and other display devices, and has overload protection, short circuit protection. With speed, oil pressure, cooling water temperature and other engine parameters monitoring and protection, when the diesel engine speed is greater than 10% of the rated speed, when the oil pressure is lower than the specified value, when the cooling water temperature is higher than the specified value, the overspeed protector, low oil pressure switch, high cooling water temperature switch, switch action to send an alarm signal; When the speed of the diesel engine is greater than 15% of the rated speed, the diesel engine automatically stops, thus protecting the diesel engine. |
Monitoring alarm and shutdown protection function |
|
Diesel engine water temperature is too high alarm stop; |
Diesel engine speed is too high alarm stop; |
Overload protection of generator set; |
Generator set overcurrent protection; |
Generator short circuit protection. |
|
三� | Scope of supply |
| The attachment is as follows: 1. Diesel generator set with fan radiator. 2. The tank. 3. The battery. 4. Tools, spare parts, technical documents. 5. High voltage switchgear 6. Combine cabinets. 7. Dc cabinet. 8. Generator set control cabinet. |
| 2. One set of spare parts is delivered |
| 3.1 set/set of data (including equipment manual and certificate) |
7611*2900*3296mm 21250kg |