Name of New Equipment: | 320kW(400kVA) Open type Diesel generator engine: Weichai WP13D385E201 | Brand name of Equipment: | Weichai | P/N of Equipment: | WP13D385E201 | Industry: | Fluid Power Generation Industry | Summary Briefs on the equipment: | | Origin of Product: | | Original Packing: | | Warranty: | | Installation, commissioning service: | | Role: | | Already Sold or not: | | Time of first Sold: | | Already sold coutry or region: | | Rough budget or contract value: | 货币选择 | Payment Terms: | | File Link: | NO_File |
320kW(400kVA) Open type Diesel generator engine: Weichai WP13D385E201 Alternator: Shanghai Stamford GR314G controller: SmartGen HGM6110 TERMS AND CONDITIONS: * Trade terms: EXW China * Shipment port: Shenzhen port China * Destination port: any port as you require * Package: Plastic film * Year of manufacturer: 2023 full brand new * HS code of 400KVA diesel generator: 8502131000 * Country of origin: China * Payment term: 30% deposit by T/T before production, 70% balance by T/T before shipment * Delivery Time: Within 20 working days after receiving deposit * Warranty:1 year or 1,000 running hours quality warranty after delivery, whichever comes first. * Remark: The above quotation includes: muffler, 24V DC maintenance free battery,battery cable, battery charger, mains circuit breaker, shock absorber pad, factory test report, random data set, etc. *Quotation validity period: 15 days Output Power 400kVA Diesel Generator Set Specifications Diesel Generator Data Manufacturer: | Guangxi Dingbo Power Equipment Manufacturing Co.,Ltd | Genset model | DB-400GF | Type | Open type | Output power: | 400KVA/320KW | Rated current: | 525A | Rated voltage: | 440V | Rated speed | 1800rpm | Rated frequency | 60Hz | Power factor: | 0.8lag | Phase: | 3 phase 4 wire | Breaker capacity: | 630A | Stable voltage regulation rate | <±1% | Transient voltage regulation rate | <+20~-15% | Voltage recovery time | <15s | Voltage Volatility | <±1% | Frequency adjustment rate | <±1% | Transient adjustment rate | <±10〜-7% | Frequency stabilization time | <5s | Frequency Volatility | <1% | Noise level | 100dBA at 7 meters | Dimension (L x W x H): | 3050x1250x2100mm | Gross weight: | 2820kg | Includes: muffler, 24V DC maintenance free battery, battery cable, battery charger, mains circuit breaker, shock absorber pad, factory test report,random data set, etc. |
Main Technical Data of Diesel Engine: Manufacturer: | Weichai Power Co.,Ltd | Engine model | WP13D385E201 | Prime power: | 350KW | Standby power: | 385KW | Frequency: | 60 Hz | Speed: | 1800rpm | Cylinders no. & Type: | 6 cylinders, Inline, 4 stroke, diesel engine, water-cooled | Aspiration: | Turbocharged and aftercooled | Displacement: | 12.54L | Compression ratio | 16:1 | Governor | Electronic speed governor | Bore x Stroke(mm): | 127x165 | Start mode: | Electric start | Starter motor voltage: | 24V DC | Type Injection System: | Direct injection | Battery charger current | 70A | Oil flow | 190L/min | Oil capacity High | 36L | Engine Coolant Capacity | 25L | Coolant alarm temperature | 98 °C |
Main Technical Data of Alternator:
| Manufacturer | Shanghai Stamford Power Equipment Co.,Ltd |
| Alternator model | GR314G |
| Output power | 400kva |
| Rated Voltage: | 440V |
| Frequency | 60Hz |
| Speed: | 1800rpm |
| Wire connecting method | Y type, 3 phase 4 wire |
| Power Factor: | 0.8lag |
| Efficiency: | 95% |
| Regulator: | AVR KRS440B |
| Rotor: | Single/double bearing |
| Exciter type: | Brushless self excitation | Recovery time(Tr) | 1s |
| Waveform : TIF | <50 |
| Waveform : THF | <2% |
| Winding Pitch | 2/3 |
| Voltage regulation: | ±1.0% |
| Protection: | IP22 |
| Insulation class | H |
| Temperature rise grade: | H |
| Duty | Go�?/span>ti�?/span>uous |
| Altitude | <1000m |
| Rated power factor | 0.8lag |
| Overload | 110% rated load for 2 hour per 24 hour |
|
|
|
|
|
|
Operating Environment: Operating temperature: | -25°C〜70°C | Relative humidity: | 95% | Operating voltage: | DC24V(range: 8-35V) |
SmartGen Control System Model�?/span> HGM6110 Origin: China Automatic controller HGM6110 series automatic controller, integrating digital, intelligent and network techniques, is used for automatic control and monitoring system of genset. It can carry out functions of automatic start/stop, data measurement, alarm protection and three “remote�?(remote control, remote measure and remote communication). The controller uses LCD display, optional display interface including Chinese, English, Spanish, Russian, Portuguese, Turkey, Polish and French with easy and reliable operation. Below shut down causes are included: Low Coolant Level High coolant temperature Low oil pressure Low output frequency Electricity High output frequency Low output voltage High output voltage Low Fuel Level Emergency stop Main characteristics are as following: 132x64 LCD display with backlight, optional language interface (Chinese, English, Spanish, Russian, Portuguese, Turkey, Polish and French), push-button operation; Acrylic screen, improved wearable and scratch resistance property; Silica-gel panel and keys can well adapt to higher and lower temperature; RS485 communication port enables “three remote�?functions via MODBUS protocol; CANBUS port which can be connected to ECU with J1939, it not only can monitor frequently-used data (such as water temperature, oil pressure, speed and fuel consumption, etc.) but also can control start, stop, high speed and low speed (controller with CANBUS port is needed) via CANBUS port; Adapt to 3P4W, 3P3W, 1P2W and 2P3W (120V/240V), 50Hz/60Hz system; Can measure and display 3 phase voltage, 3 phase current, frequency, power parameter of mains/gens; Mains Generator Line voltage (Uab, Ubc, and Uca) Phase voltage (Ua, Ub, and Uc) Frequency Hz Phase sequence Line voltage (Uab, Ubc, and Uca) Phase voltage (Ua, Ub, and Uc) Frequency Hz Phase sequence Load Current �?/span>A,�?/span>�?/span>IC Each and total active power kW Reactive power kvar Apparent power kVA Power factor PF Ge�?/span>e�?/span>ato「accumulated energy kWh Output percentage with load % For mains, genset has functions of over/under voltage and loss of phase; For gens, genset has functions of over/under voltage, over/under frequency, over current and over power; Precision measure and display of parameters about engine; Temp. (WT) °C/°F Oil pressure (OP) kPa/psi/bar Fuel level (FL) % Fuel remains L Speed (SPD) r/min Battery Voltage (VB) V Charger Voltage (VD) V Accumulated running hours Accumulated start times Control and protection function: Automatic start/stop of genset, load transfer (ATS control) and perfect fault display and protection; With ETS, idle control, pre-heat control, speed raise/drop control, all of them are relay outputs; Parameter setting: Allow user to modify setting and store them in internal FLASH memory. The parameters cannot be lost even when power off. All of parameters can be set not only from the front panel, but also adjusted through USB interface (or RS485 interface) via PC; Multiple sensors of temperature, pressure and fuel level can be used directly, parameters can be defined by user; Multiple conditions of crank disconnect (speed, oil pressure, frequency) can be selected; With emergency start function; With flywheel teeth numbers automatic identification function; Power supply range: (8〜35)VDC, accommodating to different starting battery voltage environment; All parameters use digital modulation, instead of analog modulation using conventional potentiometer, having improved reliability and stability; With maintenance function. Types (date or running time) can be selected and actions (warning or alarm shutdown) can be set when maintenance time out; Event log, real-time clock, scheduled start & stop function (can be set as start unit once a day/week/month whether with load or not); Add rubber gasket between shell and controller screen, the waterproof can reach IP65; Controller is fixed by metal fixing clips; Modular design, flame-retardant ABS shell, pluggable terminal, embedded mounting, compact structure and easy installation.