ENGINE SPECIFICATIONS
V-16,4-Stroke-Cycle-Diesel
Bore: 190mm
Stroke: 215mm
Displacement: 97.53L
Aspiration: Turbocharged-After cooled
Speed Control: Electronic Speed governing
Rated Speed: 1200rpm
Rated power: 1845kW |
1700GF9 diesel generating set are powered by model H16V190ZLD-1 diesel engine. Complying with National Standard "GB2820 General Specification for Industrial Frequency Diesel Generating Sets(eqv ISO 8528)" and with reference to "IEC34-I" rotary generator standard, the sets are equipped with high quality alternator of both home & abroad and self-made control panel according to customers requirement.
H16V190ZLD-1 diesel engine is adopted advanced governor of American WOODWARD Company. The power performance, fuel economy and reliability of the diesel engine reach world advanced level by adopting world advanced electronic control technology and lean-burnt strategy.
This genset have the features of accurate voltage regulating, good dynamic performance, less voltage waveform distortion, high efficiency, compact structure, easy to maintain, low speed, reliable and long life operation and cost-effective.
The genset can either transfer electricity directly to load or be combined in a power station with two or more than two sets. They can be used as normal and stand-by power in oil field, factory, resource development base, etc.
MAIN FEATURES
Engine Design
- Designed by AVL, Austria
- Triaxiality Finite Element Analysis
- Longer Stroke, More displacement
- Low Speed (1200RPM), More Reliable
- Advanced World Standard Performance
-Meet to IMO2 emissions levels.
Generator
- Brushless Excitation
-AVR
- Better Insulation and Protection
Safety
- Low Oil Pressure Auto Stop Protection
- Over Speed Auto Stop Protection
- Explosion Proof
- High Coolant Temperature Alarm
- Low Coolant Level Alarm
- High Oil Temperature Alarm
- Complete Electrical Protection
|
- Emergency Stop Device
Testing
- Strict Inspection and Factory Test for Each Genset
- Start Performance Test
- Load Test
- Synchronization Test
- Safety System Test
The Whole Equipment Supply
- Standard Scope of Supply
- Optional Equipment List
- Repairing Tools
- Spare Parts
- Meet the Requirement for All Accessories of Project .
Technical Support & Services
- Free Technical Support and Training Service
- 24/7 Technical Service Tel Number
- Rapid Spare Parts Supply
- After Sales Service for Generator Set Lifetime |
Property Parameter Table
Model |
1700GF9 |
Engine type |
H16V190ZLD-1 |
Alternator type |
1FC series(SIEMENS technology) |
Rated Power kW |
1700 |
Rated Speed rpm |
1200 |
Rated Frequency Hz |
60 |
Rated Voltage V |
13500 |
Rated PF |
0.8 |
Cooling Method |
Forced Water Cooled, Horizontal radiator |
Weight kg |
21000 |
Dimension mm |
7150Ă—2180Ă—2421 |
*Rating and fuel consumption based on ISO Standard conditions (Ambient temperature at 25 degree Centigrade, Atmospheric pressure at 100kPa and Relative humidity at 30%). Site rating and fuel consumption should amend according to relative standard (The table at right side for reference )
Main Specification of Engine
Model of engine |
H16V190ZLD-1 |
Rated Power(kW) |
1845 |
Rated Speed(r/min) |
1200 |
No. and layout of cylinders |
|
Type |
Heavy duty, Four stroke, water cooled, turbocharged and after-cooled, reliable diesel engine. |
Specific oil consumption (g/kW.h) |
‘≤200 |
Specific oil consumption (g/kW.h) |
‘≤1.0 |
Bore(mm) |
190 |
Stroke (mm) |
215 |
Total displacement (L) |
97.53 |
Governor |
Electronic Governor |
Fuel Injection system |
High pressure direct injection system |
Starting mode |
24V DC electric starting motor |
Direction of rotation |
Counter-clockwise(facing to flywheel) |
Lubrication method |
Pressure and splash lubrication |
Manufacturer |
JC Power Equipment Company |
Main Specification of Alternator
Model of alternator |
|
Rated power(kW) |
1700 |
Rated voltage(V) |
13500 |
Rated speed |
1200 r/min |
Rated frequency(Hz) |
60 |
Type |
Battery charging alternator,6 pole, drip proof, form wound type windings, 2/3 Pitch, 125°C Temperature rise. |
Exciting method |
Brushless |
Insulation class |
H |
Class of protection |
IP23 |
Cooling |
A fan at the drive end draws the cooling air |
Coupling |
Elastic |
Voltage regulator |
3 phase sensing with volts/Hz. |
Voltage regulation |
Less than +/-0.5% in steady state and less than +/- 0.5% with 3% speed change. |
STANDARD SCOPE OF SUPPLY
Cylinder block and Cylinder head assembly
-Cylinder block assembly
-Oil sump assembly
-Cylinder head assembly
Crankshaft connecting rod system
-Crankshaft assembly
- Piston and connecting rod assembly
-Bumper assembly
-Coupling assembly
Inlet and Exhaust system
-Air filter
-Inlet System
-Exhaust System
-Valve mechanism
-Exhaust gas turbocharger
-Exhaust manifold
-Corrugated pipe
-Exhaust pipe
-Exhaust elbow
-Exhaust silencer
Fuel system
-Feed pump
-Duplex Fuel filter
-Fuel cooler
-Fuel injection Pump
-Fuel injector
-Improve pressure of oil pipe
-Fuel tank(8 hour)
Lubricating System
-Main oil pump
-Pre-oil pump |
-Oil filter
-Oil cooler
-Oil Centrifugal filter
-Pressure regulating valve and oil pipes.
Cooling System
-Cooling fan and Driven device
- Radiator
-Enhanced high ambient temperature (45°C) Cooling system
Starting System
- Starting motor
- Electric-Hydraulic Governor
Monitoring and security systems
-Monitor
-Security system
-Run/Auto/Stop control .
Alternator
-Battery charging alternator
-6 pole, drip proof, form wound type windings
-2/3 Pitch
-125°C Temperature rise.
Spares
-Normal repair tools
-Special spare parts
-Technical document
- Certificate of quality
Others
-Common base
-Battery charger
-Oversize batteries |
OPTIONAL EQUIPMENT
Fuel System
-Fuel tank for 12 hours
-Fuel tank for 24 hours
-Fuel tank for 48 hours
Cooling System
-Horizontal Cooling Radiators and Cooling Fan, or Cooling Tower
-Pre-heating device for high and low temperature coolant
-Water softening device
Alternator
-Other brand alternator
Spare Parts and Tools
-Spare Parts for 1 years use
-Repairing Tools
-Lub oil for commissioning
Others
--Bulk materials for the first unit(s) maintenance.
-Change control cable length according to site demand
-Steel generator container
|
-Installation Engineering Construction Service
-Maintenance service
Factory equipment
-Speed and Voltage adjust.
-Engine cycle crank
-24VDC operation
-Digital indication for mechanical and electrical parameters(RPM, DC volt, operating hours, Volts, Hz, Amps, kW, kVA, Kw-hr, PF, etc.)
-Warning/shutdown events indication Protective programmable relaying functions(Generator phase sequence, 27/59, 81o/u, 32, 32RV, 50/51 with appropriate PT’s and VT’s)
-Communications capabilities (Modbus RTU)
-Digital I/O module.
-Generator main breaker.
-Digital voltage regulator
-Generator temperature monitoring and protection.
|
Certification