Transtormers Quantity
220/110/11 kV,100MVA 0
110/33/11 kV, 35MVA 2
11/0.433 kV, 500 KVA, Service Transformer 2
Steel structure and Conductors  /TD>
Steel Structure 1
Hardware (including Disc Insulators) and Connectors 1
Al. Conductors and Shieldwire 1
220 KV bwitcngear (Double Busbar, 2000A, 40kA (3s)) Quantity
Transformer Line Bay 2
Busbar Isolator, 3 pole, horizontal center-break, 1600A 2
Circuit Breaker, 3 pole, 2000A, 40 kA 1
Current Transformer, single phase, 800-400/1/1/1/1/1 A 3
Voltage Transformer, capacitive, single phase 1
Earthing Switch, 3 phase 1600A 1
Surge Arrester, single phase, 200 kV, 20 kA 3
Post Insulator 2
Feeder terminal kiosk 1
Overhead Line Bay 4
Busbar Isolator, 3 pole, horizontal center-break, 1600A 2
Circuit Breaker, 3 pole, 2000A, 40 kA 1
Current Transformer, single phase, 800-400/1/1/1/1/1 A 3
Line Isolator, 3 pole horizontai center-break, grounding switch 1600 A 1
Voltage Transformer, inductive 3
Earthing Switch, 3 phase 1600A 1
Surge Arrester, single phase, 200 kV, 20 kA 3
Line Trap , 0,5 mH, 1600A 0
Post insulator 3
Feeder terminal kiosk 1
Hassa Hissa Substation (220/110/33/11 KV)
Bus Coupler Bay 1
Busbar Isolator, 3 pole horizontal center-break, grounding switch 1600A 2
Circuit Breaker, 3 pole, 2000A, 40 kA 1
Current Transformer, single phase, 800-400/1/1/1/1 A 6
Post Insulator 4
Feeder terminal kiosk 1
110 kv switchgear (Duouble busbar, 2000A, 40kA (3s)) Quantity
Transformer Line Bay 4
Busbar Isolator, 3 pole, horizontal center-break, 1600A 2
Circuit Breaker, 3 pole, 2000A, 40 kA 1
Current Transformer, single phase, 1000-600/1/1/1/1/1 A 3
Voltage Transformer, capacitive, single phase 1
Earthing Switch, 3 phase 1600A 1
Surge Arrester, single phase, 200 kV, 20 kA 3
Post Insulator 2
Feeder terminal kiosk 1
Overhead Line Bay 4
Busbar Isolator, 3 pole, horizontal center-break, 1600A 2
Circuit Breaker, 3 pole, 2000A, 40 kA 1
Current Transformer, single phase, 1000-600/1/1/1/1/1 A 3
Line Isolator, 3 pole horizontal center-break, grounding switch 1600 A 1
Voltage Transformer, inductive 3
Earthing Switch, 3 phase 1600A 1
Line Trap , 0,5 mH, 1600A 0
Surge Arrester, single phase, 200 kV, 20 kA 3
Post Insulator 3
Feeder terminal kiosk 1
Bus Coupler Bay 1
Busbar Isolator, 3 pole horizontal center-break, grounding switch 1600A 2
Circuit Breaker, 3 pole, 2000A, 40 kA 1
Current Transformer, single phase, 1000-600/1/1/1/1 A 6
Post Insulator 4
Feeder terminal kiosk 1
Hassa Hissa Substation (220/110/33/11 KV)
33 kv switch gear (bingie busbar, GIS, 2000A, 31,5 kA (3s)) Quantity
Transformer Feeder (Incoming) 2
Position Switch (3 pole) 1600A 1
Circuit Breaker, 3 pole, 1600A 1
Current Transformer, 1600-800/1/1/1 A 3
Voltage Transformer 3
Surge Arrester, plug-in type, 30 kV, 10 kA, Discharge Class 3 3
Cable Compartment for plug-in SF6, Cable sealing ends 1
LV compartment w/ control and protection eq. as specified 1
Cable/Overhead Line Feeder 8
Position Switch (3 pole) 600A 1
Circuit Breaker, 3 pole, 600A 1
Current Transformer, 600-300/1/1/1 A 3
Voltage Transformer 3
Surge Arrester, plug-in type, 30 kV, 10 kA, Discharge Class 3 3
Cable Compartment for plug-in SF6, Cable sealing ends 1
LV compartment w/ control and protection eq. as specified 1
Capacitor Bank Feeder 1
Position Switch (3 pole) 600A 1
Circuit Breaker, 3 pole, 600A 1
Current Transformer, 200-100/1/1/1 A 3
Voltage Transformer 3
Surge Arrester, plug-in type, 30 kV, 10 kA, Discharge Class 3 3
Cable Compartment for plug-in SF6, Cable sealing ends 1
LV compartment w/ control and protection eq. as specified 1
Busbar Sectionalizer 1
Position Switch (3 pole) 2000A 1
Circuit Breaker, 3 pole, 2000A 1
Current Transformer, 2000-1000/1/1/1 A 6
LV compartment w/ control and protection eq. as specified 1
Capacitor Bank 1
33 kV Capacitor Bank, 5MVAr capacity 1
Hassa Hissa Substation (220/110/33/11 KV)
11kV Switcthgear (Single Busbar, GIS, 2500A, 31.5 kA (3s)) Quantity
Transformer Feeder (Incoming) 2
Position Switch (3 pole) 2500A 1
Circuit Breaker, 3 pole, 2500A 1
Current Transformer, 1500/1/1/1 A 3
Voltage Transformer 3
Surge Arrester, plug-in type, 30 kV, 10 kA, Discharge Class 3 3
Cable Compartment for plug-in SF6, Cable sealing ends 1
LV compartment w/ control and protection eq. as specified 1
Cable/Overhead Line Feeder 8
Position Switch (3 pole) 800A 1
Circuit Breaker, 3 po!e, 800A 1
Current Transformer, 800/1/1/1 A 3
Voltage Transformer 3
Surge Arrester, plug-in type, 30 kV, 10 kA, Discharge Class 3 3
Cable Compartment for plug-in SF6, Cable sealing ends 1
LV compartment w/ control and protection eq. as specified 1
Busbar Sectionalizer 1
Position Switch (3 pole) 2500A 1
Circuit Breaker, 3 pole, 2500A 1
Current Transformer, 2500/1/1/1 A 6
LV compartment w/ control and protection eq. as specified 1
Hassa Hissa Substation (220/110/33/11 KV)
 /TD>
Substation System Quantity
Substation Grounding 1
All material required to establish general grounding grid covering the switchyard and the service building. Grounding arrangement of the SS fence is included 1
Portable Maintenance Earthing Sets (220kV) 3
Power Cable Connections 1
33 kV XLPE, Cu, single core cable 1
11 kV XLPE, Cu, single core cable 1
11 kVXLPE, Cu, three core cable, 3x50 mm2 1
33 kV Cable Sealing End 1
11 kV Cable Sealing End 1
33 kV Cable Plug 1
11 kV Cable Plug 1
Low Voltage and Control cables 1
Cable Trays for Trenches and Basement 1
DC Auxiliary Supply System 1
110 V, 250 Ah station supply battery ,Nicad 2
110 V, 80 A station battery charger 2
110 V DC distribution panel with aut. transfer switch 1
48 V, 100 Ah station supply battery ,Nicad 2
48 V, 40 A station battery charger 2
48 V DC distribution panel with aut.transfer switch 1
AC Auxiliary Supply System 1
AC distribution panel, with aut. rapid change over 1
Light & Small Power Systems 1
Hassa Hissa Substation (220/110/33/11 KV)
Control and Protection Panels 1
220 kV OHTL feeder control panel 4
220 kV Bus coupler control panel 1
220 kV Transformer control and AVR panel 2
220 kV OHTL protection panel 4
220 kV busbar protection panel 1
220 kV bus coupler protection panel 1
220 kV transformer protection panel 2
110 kV OHTL feeder control panel 4
110 kV Bus coupler control panel 1
110 kV Transformer control and AVR panel 4
110 kV OHTL protection panel 4
110 kV busbar protection panel 1
110 kV bus coupler protection panel 1
110 kV transformer protection panel 4
Central Substation Control System 1
Workstation 1
Color LaserJet Printer 1
Data Logger 1
Communication interface 1
GPS Radio receiver 1
Common SCMS unit 1
Data Exchange System 1
Fault Monitoring System 1
Mini UPS 1
Extension of LDC (Load Dispatch Center) 1
Factory Acceptance Tests 1
Site Acceptance Tests 1
Training at site 1
Hassa Hissa Substation (220/110/33/11 KV)
Telecommunications Equipment 1
STM-4 ADD/DROP Multiplexer 2
Tributaries (set) for - Protection signaling to opposite station (3 signals per main (1+2)/per line feeder) - Micro SCADA to KLDC (RP570) - SCADA to LDC (2x64 kbit/s IEC 870-5-104) - SCADA to RCC (IEC 870-5-104) - Protection data to LDC (1x64 kbit/s IEC 8 1
FDF Cubicle with Patch cords 1
PAX + Telephone sets (2 analog, 4 digital trunk lines, 8 digital telephone sets) 1
Spare parts, tools and measuring equipment 1
Ancillary equipment 1
Training 1
Spare Parts and and Special Tools 1
1 Complete Bushing of each type (pcs) 6
1 Post Insulator of each type 4
1 silicone type MV surge arrester of each type 4
2 complete fan units of each type 4
1 therometer of each type 2
Oil level gauge of each type 2
Gas detecting relay of each type 1
1 gas sampling device each type 1
1 gas testing device of each type 1
1 pressure relieve device each type 1
1 oil flow relay of each type 1
1 piece of each type MCB's, aux. relays, contactors; heaters, lamps, push buttons and limit switches 1
1 compiete set of all gaskets used for each transformer (except main cover 2
1 silica gel breather of each size 2
1 universal spanner for operation of three-way cocks for each transformer unit 2
1 spanner for butterfly valves of each type 2
1 set of tap changer spares such as moving contacts, arcing contacts, 2
Fixed contacts, current limiting resistors etc. 2
1 set of special tools for tap changer inspection and maintenance incl. lifting 2
Device for complete OLTC insert (alt to De delivered by original OLTC manufacturer) 2
Hassa Hissa Substation (220/110/33/11 KV)
Civil Works Quantity
Preliminary Site Works 1
Site Investigation 1
Site Survey 1
Soil Investigation 1
Site Works 1
Cleaning, Excavating and Leveling of the land including any filling 1
Surrounding Drainage Ditch with suitable outlets to the natural stream 1
Temporary Access Roads 1
Surrounding Boundary Fence 1
Outdoor lightning, min 20 lux, 3 m. height 1
Dewatering system switchyard with oil seperator 1
Gatehouse and roll gate 1
Backfilling, grading and compaction 1
Outdoor Equipment Foundations 1
Cable Trenches including cover 1
Cable Ducts 1
Cable laying between station buildings and within the station area 1
Cable laying between the new station bidg. and the existing SS control bidg. 1
Hassa Hissa Substation (220/110/33/11 KV)
Control & MV Switchyard Building 1
Foundation and Substructure 1
Floor 1
Reinforce concrete structure frame and roofs 1
Windows and doors 1
Wall finishes 1
Trenches 1
Cabieways 1
Cable ladders and ducks and trays 1
Complete plumping 1
Hot and cold water supply system 1
Ground and overhead tanks 1
Ventilation and Air Conditioning system 1
Sewer and rain water and drainage systems 1
Suspended ceiling and false floor 1
Fixtures and fittings 1
Furniture (Office, Kitchen etc.) 1
Painting and Decoration 1
Lightning system 1
Fire Alarm/Fighting System 1