DPharp EJA-E Series Overview

EJA-E Pressure Transmitters

EJA110E Differential Pressure Transmitter
 
 
 

Carbon dioxide emissions is reduced by 30%.
 
    New
DPharp EJA-E Series
Low Power 1 to 5 V DC
with HART 7
The EJA-E range of transmitters is Yokogawa’s most recent evolution of the DPharp family of pressure transmitters, being released in 2012. It combines the ruggedness and success of the workhorse EJA-A range with the class-leading technology and performance of the EJX. It offers enhanced performance and reliability with built-in safety certification. Its small form factor and rugged materials provide the level of robustness that is expected from Yokogawa products.
 
 
  DPharp Highlights
DPharp series Catalog
EJA-E series General Specifications
EJA-E series User's Manuals
EJA-E series Drawings
Pressure Transmitters Technical Information
EJA-E series FOUNDATION fieldbus CFF/DD Files
EJA-E series PROFIBUS GSD/EDD Files
 

Selection Table

*Note: Large size font is recomended for viewing.
Model Application Type Capsule Measurement Span Maximum Working Pressure
kPa inH2O MPa psi

EJA110E
Differential
Pressure
Traditional-
Mounting*1
F
M
H
V
0.5 to 5
1 to 100
5 to 500
0.14 to 14 MPa
2 to 20
4 to 400
20 to 2000
20 to 2000 psi
16
16
16
16
2300
2300
2300
2300

EJA115E
Flow Integral
Orifice
F
M
H
1 to 5
2 to 100
20 to 210
4 to 20
8 to 400
80 to 830
16
16
16
2300
2300
2300

EJA118E
Differential
Pressure
& Liquid
Level
with 
Remote
Seals
Extended
Flush
Combination
M
H
2.5 to 100
25 to 500
10 to 400
100 to 2000
Based on Flange Rating

EJA120E
Draft
Range
Traditional-
Mounting*1
E 0.1 to 1 0.4 to 4 50 kPa 7.25

EJA130E
Differential
Pressure
& Liquid
Level
Traditional-
Mounting*1
M
H
1 to 100
5 to 500
4 to 400
20 to 2000
32
32
4500
4500

EJA210E
Liquid
Level,
(Closed
or Open
Tank)
Flush
Extended
M
H
1 to 100
5 to 500
4 to 400
20 to 2000
Based on Flange Rating

EJA310E
Absolute
(Vacuum)
Pressure*2
Traditional-
Mounting*1
L
M
A
B
0.67 to 10
1.3 to 130
0.03 to 3.5 MPa
0.14 to 16 MPa
0.2 to 2.95 inHg
0.39 to 38 inHg
4.3 to 500 psi
20 to 2300 psi
10 kPa
130 kPa
3.5
16
2.95 inHg
38 inHg
500
2300

EJA430E
Gauge
Pressure
Traditional-
Mounting*1
H
A
B
5 to 500
0.03 to 3.5 MPa
0.14 to 16 MPa
20 to 2000
4.3 to 500 psi
20 to 2300 psi
500 kPa
3.5
16
2000 inH2O
500
2300

EJA438E
Gauge
Pressure
with Remote
Seal
Flush A
B
0.06 to 3.5 MPa
0.46 to 16 MPa
8.6 to 500 psi
66 to 2300 psi
Based on Flange Rating
Extended A
B
0.06 to 3.5 MPa
0.46 to 7 MPa
8.6 to 500 psi
66 to 1000 psi

EJA440E
High
Gauge
Traditional-
Mounting*1
C
D
5 to 32 MPa
5 to 50 MPa
720 to 4500 psi
720 to 7200 psi
32
50
4500
7200

EJA510E
EJA530E
Absolute
& Gauge
Pressure*2
Direct-
Mounting
A
B
C
D
10 to 200
0.1 to 2 MPa
0.5 to 10 MPa
5 to 50 MPa
1.45 to 29 psi
14.5 to 290 psi
72.5 to 1450 psi
720 to 7200 psi
200 kPa
2
10
50
29
290
1450
7200
*1: Traditional-Mounting is 1/4NPT or Rc1/4 process connections (1/2NPT or Rc1/2 with process adapter).
*2: Measurement values in Absolute for Absolute Pressure Transmitter.
S.C.: BOSE748