New with warranty.
It can be change to combined cycle power plant ( CCPP )
If EPC is needed we can provide it too.
The price now is Euros 44M.
REF.:1020141021Shlomo
Siemens Gas Turbine and Generator Package
Hereafter find a simply list of materials available on site, delivered by Siemens according to Engineering,
Manufacture, Delivery and Technical Field Assistance Contract relating to GT/Generator package based on SGT 4000F
Gas turbine
Design data of model SGT5-4000F Frequency 50 Hz
Type of gas turbine (heavy duty, single casing, axial flow design)
Turbine comprising:
�?Compressor:
15 Stages
One variable-pitch inlet guide vane rows
Extraction ports behind− stationary blade 5− stationary blade 9
Compressor pressure ratio approx. 17
�?Ring combustor:
One Combustion Chamber
24 burners
One ignition devices per burner
�?Turbine
4 Stages
�?Bearings
2 Bearings (journal @ turbine end, thrust + journal @ compressor end)
�?Turning gear
Type hydraulic motor, speed 100 rpm
�?Mechanical control and protection system
�?Gas turbine instrumentation and actuation
Gas turbine systems:
�?Gaseous fuel package
One emergency stop valves
Two control valves (pilot + premix)
�?Lubrication oil system with lube oil tank
Lube tank Capacity approx. 16,5 m³ (Capacity of oil system approx. 15 m³)
Oil retention time approx. 8 min
Two oil mist extraction fans
Two Main oil pump type centrifugal 100 % capacity of one pump, drive AC motor
One emergency oil pump, type centrifugal, drive DC motor
One jacking oil pump, type vane pump, drive AC motor
One main oil filter, type duplex, capacity 2x100 %, filter mesh absolute 0.020 mm
One jacking oil filter, type cartridge, capacity 100 %, filter mesh absolute 0.020 mm
2 x 100% plate type heat exchanger.
�?Hydraulic clearance optimization (HCO) package
�?Hydraulic oil package for control system
Equipment for gas turbines:
�?Fuel gas flow metering for performance test only
�?Advanced compressor cleaning system (ACCS)
�?Set of tools for initial assembly and inspection
�?Set of major inspection tools and a set of standard tools
Air intake systems per gas turbine:
�?filter system, with pre- and high efficiency filter (multi-stage static filter)
Intake volume approx. 550 m³/s
Design pressure maximum/minimum +3000/-2200 Pa
Design temperature minimum -10 °C
Design temperature maximum +40 °C
Prefilter/Finefilter, number approx. 540, air flow per cell approx. 3650 m³/h, arrestance class acc. To
EN 779: 1993 − Finefilter F5 − Prefilter F9
Initial pressure drop system* approx. 580 Pa
Final pressure drop system between prefilter and GT compressor inlet (recommended filter change)
approx. 1000 Pa
�?inlet air filter house including weather hood, internal support structure, instrumentation, lighting, power
sockets, manhole, access ladders, platforms and doors
�?implosion doors (filter house)
�?anti-icing (warm water to air heat exchangers)
�?evaporative cooler
�?interconnecting duct work with expansion joint, damper and silencer
Exhaust gas systems per gas turbine
�?diffuser
Exhaust gas volume flow (at ISO-conditions) approx. 1535 m³/s
Design temperature minimum -10 °C
Design temperature maximum +40 °C
Design ambient temperature +15 °C
Design pressure minimum -2000 Pa
Design pressure maximum (diffuser) +5400 Pa
Design flue gas temperature (fuel gas operation) approx. 620 °C
Noise enclosure gas turbine:
�?Structural Steel with corrosion protection
�?Noise abatement panels galvanized
�?Internal service platforms and ladders galvanized
�?Doors with safety windows
�?Internal lighting including emergency lighting
Ventilation system per gas turbine enclosure:
�?Air intake openings with protective grills, dampers and silencers
�?Exhaust air handling unit on top of enclosure, equipped with back draft dampers, fans including
mechanical redundancy and silencers
Tight fitting noise enclosure for each of the following skids:
�?Fuel gas skid (ventilation system combined with the gas turbine
enclosure ventilation system)
CO2-Fire fighting system for each gas turbine unit, including (for GT enclosure, power control
containers (Inertgas) and skid enclosures as described):
�?Battery of high pressure bottles for CO2 and direction valve station
�?Piping system from bottle rack to spray nozzles inside the enclosures including supports
�?Fire detection and control system with local panel
Control System Gas Turbine
�?Turbine Controller
redundant automation processor for closed-loop control functions
I/O modules as per I/O
− Turbine Failsafe Protection and Trip System
failsafe system for protection and trip functions
− Turbine Function Group Automatic and Operational Protection System
redundant automation processor for open-loop, sequence control functions and operational
protection functions
I/O modules as per I/O
�?Turbine Operating / Monitoring / Engineering System
2 Operator Terminal with two 19�?LCD monitor, keyboard and mouse
Fault tolerant Application Server for operating, monitoring and engineering functions
2 Printer (A4, Color Laser)
Turbine Bus System
Application Bus and Automation Bus with all necessary network components
Turbine Analysis System Win_TS
Win_TS Analysis System hardware + peripherals
software for system basic functions
software for Gas Turbine Special Condition Monitoring
software for Gas Turbine Vibration Analysis
software for Gas Turbine Thermodynamic Calculations
I&C Cables, turbine related special I&C cables ( flame monitoring cable, bus cable)
I&C Software (system and application programs) on disks
Signal Interface (OPC-link) with Plant DCS
Ethernet terminal point (RJ45 or Sub-D) for exchange of 500 signals at most 1 TP for all
Signal Interface (hardwired) with Plant DCS
terminal points for exchange of 70 binary signals at most
terminal points for exchange of 30 analog signals at most
terminal point for exchange of bus clock synchronization signal
�?Generator protection cabinet (CHA)
�?Synchronization / Synchro-check equipment (CHA)
�?Gas detection system (CYQ)
�?2 Inverter for Siemens supplied turbine DCS in PCC (BRU)
�?Starting frequency converter (CJT) consisting of:
Line side and machine side B6C converter bridge
DC link between line side and machine side converter
Overvoltage protection on line side and machine side
Speed control
Compressor washing function
Boiler purge function (10 minutes)
Active power 4.0 MW, Rated apparent power 5170 kVA, Rated input voltage 1.8 kV, DC link current
1940 A, DC link voltage 2100 V
Thyristors: �?Type T1451N5200,�?Number per branch 1,�?Rated current 2020 A, �?Voltage rating factor
2.04
Smoothing reactor ( DC link): �?Rated current 1600 A, �?Starting current 1940 A, �?Inductivity 1.8 mH @
2.5 kA, �?Nominal insulation voltage Class H for 3 kV
Rated losses 48 kW
Degree of protection IP 30
Type of cooling Forced air
Required cooling air 4500 m³/h
Noise sound pressure level at 50 Hz power supply 75 dB(A)
Weight ( compact unit including DC link reactor) 2700 kg
�?Static excitation equipment (CJT) consisting of: 1
Fully controlled converter bridge type B6C
Redundant bridges 3 x 50 %
Disconnect switch for maintenance during operation
Equipment for rapid deexcitation
Line side overvoltage protection
DC side overvoltage protection
2 manual and 2 automatic controller
Power System Stabilizer
Starting frequency converter transformer with metal enclosure (IP23) (MBJ)
Static excitation equipment transformer with metal enclosure (IP23) (MKC)
Maximum cont. Excitation current IfN 1764 A, Excitation system nominal current IEN 1940 A, Ceiling
current IP (10s) 2646 A, Rated input voltage US 540 V, Ceiling voltage UP 625 V.
Thyristors: �?Type of Thyristors T1509N1800, �?Number of bridges 3 x 50%, �?Voltage rating factor 2.35
Voltage controller: �?Control accuracy 0.5 %, �?Control range (with generator connected to the grid) 95 ...
105 %, �?Setting range (manual) 0 ... 110 %, �?Controller dead band 0.1 %, �?Ceiling voltage factor 2.0, �?/DIV>
Excitation nominal response 3 s-1, �?Initial excitation time 10 ms.
Rated losses (without transformer) 10.5 kW
Type of cooling Forced air
Required cooling air 2500 m³/h
Noise sound pressure level at 50 Hz power supply 70 dB(A)
Weight 1100 kg
Degree of protection IP 30
Fuel gas system
- 2 Dust-liquid separator
o Vertical, dual stage,
1st stage: baffle plate
2nd stage: coalescer cartridge
MAWP: 44 barg
MAWT: +60°C
- Consumption metering system
o Orifice type, acc. to spec. of DGTI-2008-0131
10�?(DN250) ANSI 300
MAWP: 47 barg
consisting of:
Flow straightener, Inlet piping, Flow meter, High pressure calibration, Outlet piping, Thermowell,
Gasket, Dust cap for pressure connection
- Two Efficiency heater U-Tube bundle with trapped tube plate, carbon steel 10�?(DN250) ANSI
300 2/2-way
- Dust-liquid separator
o Vertical, dual stage,
1st stage: baffle plate
2nd stage: coalescer cartridge
MAWP: 44 barg
MAWT: +170°C
- Condensate tank Horizontal with two saddles 2,000 l, double wall
MAWP: atmospheric
MAWT: +60°C
- Final filter Vertical, single stage,Cellulose cartridge
MAWP: 44 barg
MAWT: +170°C
- 5 Shut-off valve, pneumatic actuated, Ball valve, flanged 10�?(DN250) ANSI 300
MAWP: 44 barg
MAWT: +170°C
- Pneumatic actuator Single action, spring return 10�?(DN250) ANSI 300 without control unit,
without reducing unit, without venting unit, without solenoid valves, etc.
Air-Cooled Generator Type: SGen5-1000A
Ratings: MVA: 328 kV: 20 kV
Frequency (Hz): 50 SCR: 0.50 RPM: 3000 pf: 0.85
For simple-cycle gas turbine and multi-shaft combined-cycle power plants the air-cooled
generator is Siemens standard.
The SGen5-1000A air-cooled generator for the SGT5-PAC 4000F can be supplied as Totally Enclosed
Water-to-Air Cooled (TEWAC) as standard generator Open Air Cooled (OAC) as a replacement special.
The SGen5-1000A air-cooled generator features:
− 165 - 350 MVA range (at 40°C cold gas condition)
− World class efficiency with low maintenance design
− Multi-zone, indirectly cooled stator windings
− Roebelled stator windings with brazed solid end connections
− Radially ventilated stator core attached to bed plate
− Global Vacuum Pressure Impregnated (GVPI) stator core and stator winding
− Core suspended on two axial springs
− Radially ventilated and cooled rotor winding
− Two low pressure “push�?fans mounted at each end of the rotor
− Weather and sound proof outer generator enclosure
− Coolers mounted on foundation beside bedplate and inside outer enclosure for a TEWAC
generator
− Overhung collector and brush holders
Generator mainly comprising of:
Bedplate
Spring mounted, GVPI, radially cooled stator core
Conventionally cooled stator winding with class F insulation
Rotor shaft forging including two shaft mounted ventilation fans
Radially cooled rotor winding with class F insulation
Inner enclosure covering and completing the ventilation circuit
6 High voltage leads at the top of the generator
2 Bearings supported in pedestals that are mounted on the bedplate
Overhung collector with collector ring assembly and brush holder
Fixators and grout for fixatores for mounting on foundation
Foundation bolts , nuts and washers
Axial and transvers anchors
Resistance Temperature Detectors (Platinum, 100 ohms at 0 degrees C):
12 duplex Slot RTDs embedded in the armature windings.
2 duplex RTDs in the generator warm air cooler inlet.
4 duplex RTDs in the generator cold air cooler outlet.
1 duplex RTD in the excitation cold air inlet.
1 duplex RTD in the excitation warm air oulet.
Thermocouples (Type K - chromel alumel):
1 triplex TC embedded in each bearing metal.
Rotor grounding brushes
Provision for vibration monitoring at bearings
Space heater
Current transformers :
Three (3) for each of the three phase line leads,
Four (4) for each of the three neutral leads.
Grounding equipment including grounding transformer, neutral tie, neutral cable and, grounding
resistor
All instruments wired to plugs or junction boxes
Generator Outer Enclosure including:
coolers (2 x 25 %) and liquid detector for a TEWAC unit
Rotor removal and installation tools
Low Voltage Switchgear
AC Switchgear
Rated insulation voltage 1000 V
Rated impulse withstand current (Ipk) 110 kA
Rated short time withstand current (Icw) 50 kA (1 s)
Rated voltage AC 400 V, +10%, -10%
System classification to IEC 60364 AC TN-C
Ambient temperature max. +35° C (daily mean temperature)
Surface treatment Frame parts: sendzimir galvanized
Enclosure: powder-coated, RAL 7035 Degree of protection acc. to IEC 60529 IP41 IP00 to cable
floor below
DC Switchgear
Control voltage (Us) DC 220 V
Current transformer secondary rating 1 A
Rated insulation voltage 1000 V
Rated voltage DC 220 V, +10%, -15%
System classification to IEC 60364 DC IT
Ambient temperature max. +35 °C (daily mean temperature)
Surface treatment Frame parts: sendzimir galvanized
Enclosure: powder-coated, RAL 7035 Degree of protection acc. to IEC 60529: IP41, IP00 to cable
floor below
Busbar rated short time withstand current (Icw) 10 kA
Rated breaking capacity acc. to IEC 60269 10 kA
Battery, Charger, DC/DC Converter, Inverter
The battery voltage ranges are as follows:
Number of cells 108
Design operating voltage 220 V
Rated voltage 216 V (2.00 V/cell)
Float charge voltage 241 V (2.23 V/cell)
Boost charge voltage (consumers disconnected) 259 V (2.40 V/cell)
Minimum discharge voltage 198 V (1.83 V/cell)
Battery Charger
AC input voltage 400/230 V ±10%
Input frequency 50 Hz, ±5%
Float charge voltage 241 V (at 2.23 V/cell)
DC output voltage setting range ±5%
Regulation error of output voltage ±1% on load variations 0-100 %, on frequency variations ±5%, on
input voltage variations ±10 %
DC output voltage ripple content <5% (pp) without battery
Permissible ambient temperatures 0...+40°C
Radio interference Class ”A�?according to EN55011
Degree of Protection IP 31
Cubicle colour RAL7035
DC-DC Converter
DC input voltage 220V DC +10% -15%
DC output voltage 26 V DC ±1%
DC output voltage ripple content 1% rms
Permissible ambient temperatures 0...+ 40° C
Radio interference Class ”A�?according to EN55011
Degree of protection IP 31
Cubicle color RAL7035
Inverter
DC input voltage 220 V DC
Permissible range of DC input variation +10%/-15% rated conditions
Bypass input voltage and frequency 1 x 230 V AC, ±10%, 50 Hz
Inverter output voltage 1 x 230 V AC, 50 Hz with deviation (static) ±1%, with deviation (dynamic)
±5%
Inverter output voltage setting range ±5%
Inverter output voltage harmonic content �?%
Overload capability 150% for 1 minute
Permissible ambient temperature 0...+40°C
Radio interference Class ”A�?according to EN 55011
Degree of Protection IP31
Cubicle colour RAL7035
Cooling method forced air (2 * 100%) |