Diesel Engine Power Plant 200MW 2 stroke diesel engine power plant
The plant is the largest Diesel Plant in the World under one roof with four sets of 50 MW 2 Stroke Diesel Engines.
The total Plant area of 29 acres accommodates the Power Plant, Sewage Treatment Plant and Fuel Oil Installations.
−DGs sets are accommodated in the area of around 1.4 Acres.
Currently Low Sulphur (<1%) Heavy Stock (LSHS) used as fuel. However diesel can also be used as a fuel.
DG Building acoustically designed to contain noise pollution.
The plant also includes waste heat recovery systems to conserve energy and fuel efficient engines with modifications to further enhance efficiency.
The 200MW Diesel Powered Plant consists of ;
−4 nos. 51.48MW Hyundai-MAN B&W make Diesel Engines
−12 nos. ABB make Exhaust Gas Turbochargers
−4 nos. ABB make 11kV generators
−1 no. Wooden Cooling Tower, capacity 7800 cum/h
−4 nos. Thermax make Waste Heat Recovery Boilers, capacity 2 x 4.5 TPH and 2X11 TPH
−1 nos. Lehmyer Germany make Sewage Treatment Plant
The diesel engines operate on residual low sulphur heavy stock (<1.0% sulphur content) fuel
Equipment Description
Generator DG |
Generator Transformers |
Rating |
63,670 kVA |
Rating |
3 Phase / 52/ 68 MVA |
Voltage |
11 kV |
Voltage |
115/11 kV |
Power Factor |
0.8 |
Capacity HV/LV1/LV2 |
NA |
Cooling |
Air Water Heat Exchanger |
Cooling |
ONAN/ONAF |
Insulation Level |
Class F |
BIL (KVP) |
550/75 |
Frequency |
50 Hz |
Frequency |
50 Hz |
No. of Poles |
58 |
Connection & Symbol |
Ynd 11 |
Neutral Grounding |
NGR |
Neutral Grounding |
HV solidly grounded |
Rpm |
103.4 |
Type of conservator |
COPS |
Rotor Length |
6,025 mm |
Type of tank |
Conventional type |
Rotor Diameter |
9,425 mm |
Type of tap charger |
OLTC (BHEL M 111 500 Y 60 B/10193W) |
Cooling Equipments |
Heat Exchanger with fans |
Cooling Equipments |
Radiator with fans |
Excitation System |
Current �?470A |
Type of bushing |
HV �?145 kV, 800A OIP |
Voltage �?380V |
LV �?17.5 kV, 3150A |
Max continuous excitation current �?499A |
HV TO Neutral �?36 kV, 630A |
Temperature Rise |
Winding �?120 to 130 °C |
No load loss |
26 KW |
|
|
No load current |
1% |
|
|
Noise level |
- |
|
|
Load losses |
193.96 KW |
|
|
Temperature rise |
Oil �?70 °C & Winding �?80 °C |
|
|
Voltage variation |
Tap from +5% to -15% in step of 1.25% |
Station Transformers |
Unit Auxiliary Transformers |
Rating |
5.6/7.2 MVA |
Rating |
3 Phase/ 1.250 MVA |
Voltage |
110/6.9 kV |
Voltage |
11000/433 Volts |
Capacity HV/LV |
NA |
Capacity HV/LV |
NA |
Cooling |
ONAN/ONAF |
Cooling |
ANAN |
BIL (KVP) |
Data not available |
BIL (KVP) |
Data not available |
Frequency |
50 Hz |
Frequency |
50 Hz |
Connection & Symbol |
Ynd 11 |
Connection & Symbol |
Dyn1 |
Neutral Grounding |
NGT |
Neutral Grounding |
Solidly grounded |
Type of conservator |
AIR type |
Type of conservator |
NA |
Type of tank |
Conventional type (without Aircell) |
Type of tank |
NA |
Type of tap charger |
OLTC |
Type of tap charger |
Off-Load |
Cooling Equipments |
Radiator with fans |
Cooling Equipments |
Dry Type |
|
|
Temperature rise |
Winding �?70 °C |
|
|
Voltage variation |
Off Load Tap Charger |
Service Transformers
(No. 1 & 2) |
Type |
Dry Type, Class H |
Rating |
2.5 MVA |
Voltage HV/LV |
6.6/0.413 kV |
Frequency |
50 Hz |
Type of tap changer |
Off load |
Tap voltage |
165V at 6.6kV Side |
Winding connection |
Dyn11 |
Cooling method |
NA |
% impedance |
6.32% |
Temperature rise |
Winding �?70 °C |
WILL