BBS  Email&MSN: [email protected]
  
Homepage   |   Power Generation   |   Project Financing    |   Equipments   |   Transmission   |   Financing-Ebook   |   Contact Us   |   Used Equipment   |   download   |   sitemaps   |   Spare Parts   |   Project-Equipment-Parts-Enquiry   |   Exclusive-Distributor   |   Exchange Link  

Mail List

E-mail:

Home > Used Equipment - 2 set GE 9E Combined cycle for sale


Google

2 set GE 9E Combined cycle for sale

GE 9E Combined cycle
1. The power plant was been installed in 2004, and put into
commerical running in Oct. of 2005.
2. Total running time is 1200 hours.
3. Fuel system is LFO and NG dual fuel system.
4. Output of gas turbine is 125MW, and steam turbine is 55MW.
5. All of the equipments related to generate electricity are available.

 

NSRD planned to carry out modificati
Used 9E Gas Turbine Combined Cycle Power Generation Equipments
The property right of the whole set of 9E GTCC power generation unit, which
considered a sale is completely and legally owned by Shenzhen Teweite Co, Ltd
The proposed unit includes the following equipments: one set of 9E Gas Turbine
Generation Unit, one set of HRSG Unit, one set of Steam Turbine Generation Unit
and its auxiliary equipments. The whole set of generation unit is presenting wonderful
working conditions and steady performance during operation. After quit operation, the
whole set equipments have had excellent and professional maintenance and remains
the good condition.
1. The GT Generation Unit
The GT generation unit started COD at August 1993, it was originally made by
General Electronic (GE), and the model number is MS-9001E (PG9171E) with
rotating speed of 3000RPM. GT is starting by electric motor, fuel types are light
diesel oil or heavy duty oil. The control system is MARK-V
Generator model number: 335X957, Installed Capacity: 143.4MVA, Voltage
Grade: 11.54KV, Frequency: 50HZ and Power Factor: 0.8. It is applied with
hydrogen cooling system and brush stationary excitation system.
ons for this unit from burning HFO to
natural gas at the beginning of 2010. So far, the natural gas forward skid is ready
for air inlet. Therefore this unit could burn natural gas after proper modification.
Up to GT Unit completely shut down, it has been safely running for 78,065 hours
with 56,127 hours burning heavy duty oil. The latest major overhaul was
completed at Nov 2006 with total operation hours of 68,246. The unit could still

running for more than 5000 hours until next overhaul under the condition for
running HFO.
Main GT Generation Unit capability as follow (under ISO performance
condition):
Operating Method Fuel Power Heat Loss Rate Efficiency Discharge Temperature
Natural
Gas
123.4 MW 10650 kJ/kWh 33.80% 539 °C
Light Oil 121.3 MW 10730 kJ/kWh 33.55% 539 Base Load 9 °C
Heavy
Duty Oil
117.2 MW 10968 kJ/kWh 32.82% 525 °C
2. HRSG
HRSG was made by US Company named DELTAK, and started COD at May
1995. Model number: FM9, Its specifications are: Outdoor Model, Horizontal
Type, Dual Pressure and Self-Deoxygenize. In order to improve the amount of
evaporation, it had been modified by Hangzhou Boiler Group Co., Ltd. by adding
two sets of evaporator tubes and two sets of economizer tubes.
Under the ambient temperature of 30°C, 1.013bar of atmospheric pressure and
70% of relative humidity, the GT steam parameter would be 40bar, 481°C and
180t/h by burning heavy duty oil.
In order to assort with burning natural gas from heavy duty oil, NSRD has
planned to carry out modifications to HRSG at the beginning of 2010. All the
heating surfaces will be newly changed. So far, modification schemes and
equipments producing have already completed by Hangzhou Boiler Group Co.,
Ltd. Under above mentioned performance condition, the modified HRSG will not
only guarantee the non-reduction of steam parameter required during generation,
but also added the new functions, which could supply low pressure steam and hot
water externally. HRSG’s capability as follow:

No Title Rate
1 Medium Voltage Evaporation Capacity 182t/h
Medium Voltage Steam Temperature 485°C
Medium Voltage Steam Pressure 41bar
2 Low Voltage Evaporation Capacity 21t/h
Low Voltage Steam Temperature 255°C
Low Voltage Steam Pressure 7bar
3 Hot Water Supply Flow Capacity 360t/h
How Water Supply Tem/Back Flow Tem 103°C/83°C
3. Steam Turbine Generation Unit�?BR>Steam Turbine was made by Harbin Electric Corporation, China and started COD
at May 1995. Model number: N50-4.05, rotating speed: 3000RPM. Its
specifications are: Medium Pressure, Single Cylinder, Axial Flow, Condensing
Type and total 18 grades.
Generator was made by Jinan Generator Company, China. It putted into operation
together with ST at the same time. Generator model number: WXBL054, Capacity:
75MVA, Voltage Grade: 10.5KV, Frequency: 50HZ, Power Factor: 0.8, it is
applied with air cooling system and non-brush excitation system. Generator stator
was been changed at March 2008.
In order to improve internal efficiency, ST was modified by Harbin Electric
Corporation, 1-5 grades of diaphragm plate has been changed to those with high
efficiency and also adopted with advanced and adjustable Blandon steam seal
technology.
January 2005, simulate types of electro hydraulic control system has been
modified into digital types, HRSG and ST generation unit are adopted with DCS
control system.
April 2007, steam extraction external supply modification has been carried out.

Extraction point came from the back of fourth grade with extraction pressure of
9bar, maximum extraction capacity is 70t/h.
Up to ST completely shut down, the whole unit was with a total operation of
66461 hours. Under ISO performance condition during GT burning heavy duty oil,
the ST generation unit’s power output was 52MW.
NSRD has calculated the efficiency for whole set of combine cycle generation
unit, which is 47.5% under ISO performance condition by burning heavy duty oil.
4. Main Transformer:
So far, the main transformers applied into GT generation unit and ST generation
unit were all made by Baoding Tianwei Group.
The main transformer of GT generation unit dispatched from manufactory at May
1993, Model Number: SEP7-150000/110, Rated Capacity: 150000KVA, Rated
Voltage: 121/11.5KV, Frequency: 50HZ Cooling Method: ODAF and Outdoor
Type.
The main transformer of ST generation unit dispatched from manufactory at
March 2003, Model Number: SF9-75000/110, Rated Capacity: 75000KVA, Rated
Voltage: 121/10.5KV, Frequency: 50HZ Cooling Method: ONAN/ODAF and
Outdoor Type.
All the above mentioned descriptions will not be the guarantee for any of above
units and buyer must come to site to carry out inspection and testing by
themselves.

Appendix 1: Major Equipments List
No Device Name Manufactory Model Number Quantity
1 GT Generation Unit GE(US) MS-9001E 1 Set
2 GT Auxiliary Equipment GE(US) Assort with 9E 1 Set
3 HRSG DELTAK(US) FM 9 1 Set
4 HRSG Auxiliary
Equipment
Assort with HRSG 1 Set
5 Steam Turbine Harbin Electric
Corporation
N50�?.05 1 Set
6 ST Auxiliary Equipment Harbin Electric
Corporation
Assort with ST 1 Set
7 ST Generator Jinan Generator
Company
WXBL054 1 Set
8 GT Main Transformer Baoding
Tianwei Group
SFP7-150000/110 1 Set
9 GT Main Transformer
Exit Switch
Siemens
(Hangzhou)
Company
110KV 1 Set
10 ST Main Transformer Baoding
Tianwei Group
SF9-75000/110 1 Set
11 ST Main Transformer
Exit Switch
Siemens
(Hangzhou)
Company
110KV 1 Set
12 Combined Cycle Control
System
ABB (Beijing) DCS 1 Set
13 Unit Electric
Distribution Equipment
Assort with Units Some
14 Unit Protection
Equipment
Assort with Units Some

Appendix 2: Spare Part List
No Device Name Model Quantity Stock Sum Currency
GT Generation Unit
1 Circuit Breaker 218A4387P32 10 3,238.21 USD
2 Flame Detector 261A1812P013 9 24,948.00 USD
3
Integrated Circuit
Model / Circuit
Board
Some 69,278.03 USD
4
Diode / contactor
/ Transmitter
Some 57,838.09 USD
5
Seal Assembly
Oil Seal
Some 73,651.60 USD
6
Vacuum Steam
Drum
Some 52,387.50 USD
7
Electric Engine
(Hydraulic
Pressure Donkey
Pump)
334A7743P001 1 Set 2,980.30 USD
8
Sealing
Ring/Plug
Board/Gasket
Some 9,558.30 USD
9
Surge Preventing
Valve
RCA509203 1 Set 3,773.00 USD
10
Rotating Guide
Vane
329A3338G001 1 Set 295,915.40 USD
11
Air Compressor
1st Grade Stator
178C6255G009 1 Set 190,080.00 USD

Blade
12
Air Compressor
2nd Grade Stator
Blade
178C6255G010 1 Set 157,217.50 USD
13 Bearing Shell S155D5847G0002 1 Set 60,280.00 USD
14
17 Grades Stator
Blade (104/ Set)
178C6247P1 1 Set 111,372 USD
15
17 Grades
Movable Blade
(56/Set)
109E5134P001 1 Set 100,999 USD
16
Exhaust Stator
Blade
EGV1(104/Set)
178C6248P1 1 Set 111,372 USD
17
Exhaust Stator
Blade
EGV2(104/Set)
178C6249P1 1 Set 111,372 USD
18 Oil Catch Some 8939 USD
19
Water to Water
Heat Exchanger
SL-240 1 Set 58260 USD
ST Generator Unit
1 Sealing Ring P54-100C9-300 2 Sets 1480 USD
2
Oil System
Components
HTC Some 21736 USD
3 Steam Sealing Ring HTC Some 3135 USD
4 Bearing 118.051Z-1 1 Set 12330 USD
5 Bearing Z109.06.04.24 1 Set 1356 USD
6 Thrust Bearing Z109.08.04-1 1 Set 20715 USD
7 Bearing Shell 1#-4# Shell 1 Set 1665 USD
8 Main Oil Pump Gear 106.405Z 1 Set 4578 USD

Type Coupling
9 Special Bolt Some 14899 USD
10
Magnetic Valve
/Block
Some 13410 USD
HRSG
1
Whole HRSG
Heating Surface and
Modified Parts
Assort with GT
9E
1 Set 4143934 USD
2
Attemperator and
Adjusting Valve
FISHER 1 Set 13567 USD
3
High Pressure Water
Feed Pump Body
4×11CS 1 Set 43,849 USD

REF. Daniel Dang1020140605





Copyright©2006-2013 Leda Greenpower Beijing ICP Reg. No: 10010978
   Fax:0086-10-84161062  E-mail:
[email protected]
[email protected]   Google