Homepage   |   Power Generation   |   Top Spare parts   |   spare parts   |   China OEM Equipment and Spare Parts   |   Project Financing    |   Equipments   |   China Small EPC Contractor   |   Transmission   |   Financing-Ebook   |   Contact Us   |   Used Equipment   |   download   |   sitemaps   |   Project-Equipment-Parts-Enquiry   |   供货商Supplier   |   Exchange Link   |   Breaking News  
Mail List

E-mail:

Home > China OEM Equipment and Spare Parts > Power Project - 1200GF20-T GAS GENERATOR SET-L12V

Buyer     Inquiry Basket     Supplier     Register


1200GF20-T GAS GENERATOR SET-L12V

GAS GENERATOR SET                               1200KW /1000rpm

1739012737311.jpg

GENSET SPECIFICATIONS

 V-12,4-Stroke-Cycle-gas                                                                                                                                                                        

Bore--------------------------------------------------200mm

Stroke------------------------------------------------255mm

Displacement------------------------------------------96.1L

Aspiration-------------------------------------turbocharger

Control----------------------Electronic Speed governing

Rated Speed---------------------------------------1000rpm

Rated power (Prime)-----------------------------1200kW

1200GF20-T gas generating set are powered by model L12V200ZLT-2 gas engine produced by our company. Complying with National Standard “GB2820 General Specification for Industrial Frequency Diesel Generating Sets(eqv ISO 8528)�?and with reference to “IEC34-I�?rotary generator standard, the sets are equipped with high quality alternator of both home & abroad and self-made control panel according to customers requirement.

This genset have the features of accurate voltage regulating, good dynamic performance, less voltage waveform distortion, high efficiency, compact structure, easy to maintain, low speed, reliable and long-life operation and cost-effective.

The genset can either transfer electricity directly to load or be combined in a power station with two or more than two sets. They can be used as normal and stand-by power in oil field, factory, resource development base, etc.

Main Features                                                                      

Engine Design

- Designed by   AVL, Austria

- Intellectual   Property belong to CNPC JICHAI POWER COMPANY LIMITED

- Triaxiality   Finite Element Analysis

- Longer   Stroke, More displacement

- Low Speed   (1000RPM), More Reliable

- Advanced   World Standard Performance

Generator

- Brushless   Excitation

- AVR

- Better   Insulation and Protection

Safety

- Low Oil   Pressure Auto Stop Protection

- Over Speed   Auto Stop Protection

- Explosion   Proof

- High Coolant   Temperature Alarm

- Low Coolant   Level Alarm

- High Oil   Temperature Alarm

- Complete   Electrical Protection

- Emergency Stop Device

Testing

- Strict   Inspection and Factory Test for Each Gen-set

- Start   Performance Test

- Load Test

-   Synchronization Test

- Safety   System Test

The Whole Equipment Supply

- Standard   Scope of Supply

- Optional   Equipment List

- Repairing   Tools

- Spare Parts

- Meet the   Requirement for All Accessories of Project.

Technical Support & Services

- Free   Technical Support and Training Service

- 24/7   Technical Service Tel Number

- Rapid Spare   Parts Supply

- After Sales   Service for Generator Set Lifetime

Property Parameter Table                                                          

Model

1200GF20-T

Engine   type

L12V200ZLT-2

Alternator   type

1FC   series (SIEMENS technology)

Rated   Power(Prime)  kW

1200

Rated   Speed        rpm

1000

Rated   Frequency     Hz

50

Rated   Voltage       V

6300V

Rated   PF 

0.8

Electrical   efficiency

�?/span>38.7%

Cooling   Method

Inter-cooling, With Horizontal Radiator

Emergency   genset function

Automatic Device

Control   Module

DSE8610

Weight             kg

20600

Dimension          mm

7500×2300×2800�?/span>Without   Horizontal Radiator�?/span>

*Rating and fuel consumption based on ISO Standard conditions (Ambient temperature at 25 degree Centigrade, Atmospheric pressure at 100kPa and Relative humidity at 30%). Site rating and fuel consumption should amend according to relative standard.

Main Specification of Engine                                                         

Model   of engine

L12V200ZLT-2

Rated   Power(kW)

1200

Rated   Speed(r/min)

1000

No. and   layout of cylinders

12-cylinder�?/span>60°Vee

Type

Four Strokes�?/span>V Type�?/span>Turbocharged Inter-cooling�?/span>Spark   Plug Ignition

Bore(mm)

200

Stroke (mm)

255

Total   displacement (L)

96.1

Specific   oil consumption (g/kW.h)

�?.6

Idle   Speed�?/span>r/min�?/span>

700

Gas   Pressure�?/span>kPa�?/span>

100�?/span>400

Heat   Rate�?/span>kJ/kW·h�?/span>

�?850

Exhaust Temperature

(Before   Turbocharger.�?span style="font-family: 微软雅黑, 'sans-serif'">�?/span>

�?50

Water   Outlet Temperature�?/span>�?span style="font-family: 微软雅黑, 'sans-serif'">�?/span>

�?5

Water   Inlet Temperature of Inter-cooler�?/span>�?span style="font-family: 微软雅黑, 'sans-serif'">�?/span>

�?5

Lube   Temperature�?/span>�?span style="font-family: 微软雅黑, 'sans-serif'">�?/span>

�?0

 

Main Specification of Alternator                                                     

Model of alternator

1FC series (SIEMENS technology)

Rated power(kW)

1000

Rated   PF

0.8

Rated voltage(V)

6300V

Rated speed

1000 r/min

Rated frequency(Hz)

50

Exciting method

Brushless

Wiring method

Three phase four wire, Y type connection

Insulation class

F

Class of protection

IP23

Cooling

A fan at the drive end draws the cooling   air

Bearing structure

Duplex bearing

Direction of rotation

Clockwise (facing to generator drive end)

 

Standard Scope of Supply                                                         


Cylinder block and Cylinder head assembly

-Cylinder block assembly

-Oil sump assembly

-Cylinder head assembly

Crankshaft connecting rod system

-Crankshaft assembly

-Piston and connecting rod assembly

-Torsional vibration assembly

-Coupling assembly

Inlet and Exhaust system

-Air filter

-Inlet System

-Exhaust System

-Valve mechanism

-Exhaust gas turbocharger

-Exhaust manifold

-Corrugated pipe

-Exhaust elbow

-Exhaust silencer

Lubricating System

-Main oil pump

-Pre-oil pump

-Oil filter

-Oil cooler

-Oil Centrifugal filter

-Pressure regulating valve and oil pipes.

Cooling System

- Horizontal Radiator (AC400V motor drive)

Starting System

- Starting motor

- DC 24V

Control / Monitoring and security systems

-Genset smart control module (auto parallel and load sharing)

-Monitor

-Security system

-Run/Auto/Stop control .

Alternator

-6 pole, drip proof, form wound type windings

Spares

-Normal repair tools

-Special spare parts

-Technical document

-Certificate of quality

Others

-Common base

-Battery charger


Optional Equipment                                                                  

Exhaust System

- Exhaust pipe and silencer

Preheating system

  - Oil heating   system

  -   Water heating system

Spare Parts and Tools

- Spare Parts for 2 years

- Repairing Tools

Others

- Change   control cable length according to site demand

- Installation Engineering Construction Service

- Maintenance   service

 

Item

Description

Model

Unit

Quantity

1200GF20-T Natural Gas Genset

Gas engine

H16V190ZLT-1

set

3

Generator

1FC series

set

3

Genset Control Panel

GPL1200A

set

3

Pre-lub oil


set

3

Battery Charger


set

3

Cooling System

Horizontal Radiator

set

3

Exhaust System

Exhaust pipe and silencer


set

3

Steel canopy

silence canopy


set

3

Remark:

Delivery date: Three months after contract valid or negotiation by both parties.

Terms of Payment: After contract, you should pay our company 30% of the contract amount andpayoff the other 70% before delivery.

Installation and commissioning: If customer needs our company to do the guiding installation andcommissioning, our company will arrange two engineers to do the field service. All the feesincluding the traffic, living condition and insurance in abroad will be provided by the customer, andcustomer should pay our engineers 200.00 dollars per day per person.






Statement: Any reference to the OEM part number or other OEM information is for the purpose of identification only and does not imply that the part was manufactured by the Original Equipment Manufacturer.

All the brands and trademarks in the whole domain of the website belong to their own owners and does not mean that we are their authorized partner or dealer. All the information in this website is only for reference, we do not assure its accuracy.

This statement supersedes all other claims and statements on all pages, files, pics and information within this whole web domain.

Copyright©2006-2019 Leda Greenpower Beijing ICP Reg. No: 10010978.   Fax:0086-10-84161062  E-mail: [email protected]

JingGongWangAnBei: 11010802035914 Hao