Used Power Plant MTU-20V4000G43
Item No | Description | QTY | Brand | P/N | Product Name | Delivery Time | Condition | Type |
---|
664 | FOR SALE available
2500KW DIESEL GENESET 3 UNITS
Type:Package type(on one base plate)
Never used gensets
PRICE IS USD FOB per set
Engine manufacturer:MTU
Alternator manufacturer:Hyundai
Year:2011 x 2 units and 2008 x one uni
Fuel:Diesel
Hours: Test hours only
Can be run for testing
(Engine specification)
Engine model:20V4000G43
Engine type:4 stroke, water coolled
Aspiration type:Terbo charger,Intelcooler
Power:2740kWh
RPM:1800
Number of cylinders:20
Cylinder configuration:90 Vee
Bore:170mm
Stroke:210mm
Displacement:95.4liter
Compression ratio:16.4:1
Combustion system:Direct injection
Mean effective pressure:19.2bar
Mean piston speed:12.6m/s
Governor type:ADEC
Cooling system:Radiator
(Alternator specification)
Make:Hyundai(Korea)
Year:2011
Type:HFC7638-4P
Rated capacity:2500KW
Factor:0.8
Rated voltage:440V
Rated current:4100.5 A
RPM:1800
HZ:60
Brushless self exciting type
Poles:4
3Phases
Bearing:anti-friction bearing
Insullation class:F
Voltage adjustment range:plus minus 10%
Cooling type:air cooled
(Engine Dimension)
3586 mm x1613mm x2077mm
Weight:9864kg
(Techinical Data)
1.Combustion air/Exaust gas
-Combustion air volume flow:225m3/sec
-Exaust temperature after turbocharger:455
-Exaust back pressure(desgn/limit value:30/85 mbar
2.Fuel system
-Fuel specification:EN590,Grade Nr,
1/2-D(ASTM D975)
Class A2(BS 2869)
-Fuel consumption:
100% load:197g/kWh
75% load: 210g/kWh
50% load: 225g/kWh
25% load: 259g/kWh
No load:57.kg/hr
3.Lube oil :API CG-4 and ACEA
E2-96, SE 15W-40
4.Coolant system(High temperature)
-Coolant water capacity:205liter
-Coolant temperature(Engine outlet):100
-Coolant flow rate:94m3/h
5.Coolant system(Low temperature)
-Coolant water capacity(Intercooler):55liter
-Coolant temperature(Intercooler inlet):55
-Coolant flow rate:94m3/h
6.Noise
-Engine surface noise:115dB(A)
-Undamped exaust gas noise:128dB(A)
7.Engine protection(Alarm/Shutdown)
-Cooling water over temperature:102/104
-Intercooler over temperature:75
-Lubrication oil low pressure:3.9bar/3.6bar
-Lubrication over temperature:99/101
-Fuel over temperature:100
-Engine over speed: / 1950rpm
8 Control system
paralleling load sharing panels, MCB cabinets
9 Supply list
1.Engine+Generator(Including Start Panel, Steel stands) 3 sets
2. common type Control Panel one set
3. Fuel tank one set
4.Exhaust pipe 3 sets | | Used Power Plant | MTU-20V4000G43 | used power plant, equipment, spare parts, prior to sales, or just as information, not accurate or not for specific plant only. | | | |
Pubdate: 2022/4/26 16:56:25 |
|
Click add item to inquiry basket Click Copy Shared Links | Inquiry Basket |
Pageviews: 2
|
|
Statement: Any reference to the OEM part number or other OEM information is for the purpose of identification only and does not imply that the part was manufactured by the Original Equipment Manufacturer.
All the brands and trademarks in the whole domain of the website belong to their own owners and does not mean that we are their authorized partner or dealer. All the information in this website is only for reference, we do not assure its accuracy.
This statement supersedes all other claims and statements on all pages, files, pics and information within this whole web domain.
|
|