Used Power Plant MAN-12mw
Item No | Description | QTY | Brand | P/N | Product Name | Delivery Time | Condition | Type |
---|
292 | Equipment Lists
12MW Gas Turbine Generator x3units
Condition: Never used
Manufacturing year: 2013
Turbine make: MAN
Generator make: ELIN MOTOREN (Austria)
Fuel: Dual fuel system(Liquid fuel or Gas)
(Turbine)
Make:MAN
Manufacturing year: 2013
Model: THM1304-12
Power at coupling: 12,000kW
Dual fuel system
Efficiency: 31.6 %
Heat rate:11,790 kJ/kWh
Turbine Speed: 9,000 rpm
Exaust gas flow: 49.1kg/s
Exaust gas temperature: 515 °C
NOx emissions:50 mg/Nm3(ref. to 15% O2dry)
CO emissions:<10 mg/Nm3
Max.cont. speed: 12100/9030 r/min
Trip: 12200/9482 r/min
Heavy duty type
Two shaft type
Stages: 2+2
Max.TIP speed:423/378 m/s
Rotor type: Salient poles/Cylindrical
(Generator)
Make: ELIN MOTOREN(Austria)
Manufacturing year: 2013
Model: HTM190E04
Cynchronous type
Capacity: 12MW
Voltage: 6600V
Frequency: 50Hz
Excitation : Brushless type (PMG)
Power factor:0.773
According to Standard : DS/EN 60034
Degree of Protection Outdoor IP: 56
Winding Temp. Detection : PT100 in each phase
Vibration Detectors Required : Yes, proximity type probes
Preformed for Portable Earthing Apparatus : Yes
Space Heater : Yes
Hazardous Area Classification : Ex II 3G Ex pz e ib IIB T3 Gc
Rated current:1312A
Direction of Rotation Facing Shaft End : CCW
Max. Allowable Cont. of Harmonics (THD) : 5%
Vibration Detectors Type: Proximity type
Cooling Method IC: IC8A1W7
Degree of Protection IP: 56
Max. Allowable Neg. Phase Seq. Current %: 9 %
Max. Allowable Cont. of Harmonics (THD) : acc. IEC 5 %; acc. References 0,2 %
Efficiency at 1/1 and 3/4 load %: 97,78; 97,79 - at cosphi 0,773
Field Current No Load A: 99
Field Current Rated Load A: 270
Dimension: Approximately 5000x3000x3100mm (LxWxH)
(Combustion chambers)
The number of chambers: 2
Type: V arrangement
Fuel Nozzle per Combustor:1
Adiabatic compression of air in an axial-centrifugal compressor
Max. Allawable Temp.Variation:50 degree
Low emission
Dry Low Nox
(Gearbox)
Low speed speeds
Temperature monitoring equipment attached
Velocity(m/s)
Sunwheel sleeve: 57m/s
Spindles sleeve 34m/s
L.S. Shaft sleeve: 19m/s , 11m/s
(Lubrication oil cooling system)
1x100% heat exchanger with 2x50% fans
(Air inlet system)
Table type filter with depth loading cartridges
Filtration class: Pre-filter: F6,
Fine-filter: F9 ( Static filter including anti-icing)
(Noise Emission)
All equipment is designed for Lp 85 dB(A) measured in 1 m distance and 1.5 m height
- Lp = 80*, 75*, 70* dB(A)
Meeting emission regulations In addition to the standard diffusion type combustor, a lean
premix combustor is available for the THM Gas Turbine family to meet stringent emission
regulations. The system limits and controls the maximum flame temperature by means of a
patented air bypass system over a wide power range. The combustor thus reduces the
formation of nitrogen oxides (NOx) and carbon monoxide (CO) significantly. The external
combustors allow easy access, maintenance and can be modified for use of other gaseous or
liquid fuels such as: Diesel, Kerosene or Methanol.
Individual arrangement With more than 20 million operating hours in different
environmental conditions, the THM gas turbine family offers various layouts to meet your
individual requirements, either as mechanical or generator drive.
(Complete package for outdoor installation)
- Fire detection
- CO2 fire-fighting system -
- Gas leakage detection �?.
(Air compressor)
Stages:10+1
Type: Axial/Radial
Max. TIP speed: 374m/s
(Starting motor)
Type: AC Asynchronous motor
Make: LEROY SOMER
Model: FLSD 280
Rating:180nom./350max.Kw
(Instrument air pressure)
Design pressure: 11Mpag
Max. 10barg
Nominal: 9 barg
Min 7.5barg
(Electrical & Control System )
For installation in control room SIMATIC based automation system for control,
operation & monitoring
Data recording system:
- for recording and storage of engine parameters
- online data access
Control and protection for generator including Voltage regulator (AVR)
Variable speed drive for gas turbine starter motor
Low voltage switchgear for motor controls (MCC)
- for emergency lube oil pump
- for unit control system emergency power supply | | Used Power Plant | MAN-12mw | used power plant, equipment, spare parts, prior to sales, or just as information, not accurate or not for specific plant only. | | | |
Pubdate: 2022/4/26 16:56:22 |
|
Click add item to inquiry basket Click Copy Shared Links | Inquiry Basket |
Pageviews: 1
|
|
Statement: Any reference to the OEM part number or other OEM information is for the purpose of identification only and does not imply that the part was manufactured by the Original Equipment Manufacturer.
All the brands and trademarks in the whole domain of the website belong to their own owners and does not mean that we are their authorized partner or dealer. All the information in this website is only for reference, we do not assure its accuracy.
This statement supersedes all other claims and statements on all pages, files, pics and information within this whole web domain.
|
|