10.3.2 Request user data class 1 sequence of remote measure (801H) =000BH�?(802H) =002CH
10.3 EXAMPL
Links normal
10H Start byte
ABH Control field
OlH Links address
ACH Check sum
16H End byte
10.3.1 Request status of link
10H Start byte
49H Control field
OlH Links address
4AH Check sum
16H End byte
10H Start byte
4AH Control field
OlH Links address
4BH Check sum
16H End byte
68H Start byte
OEH L
OEH L
68H Start byte
A8H Control field
OlH Links address
09H Type identification
82H Variable structure qualifier
OlH Cause of transmission
OlH Application layer address
OlH Information object address
08H
OBH YC=000BH
OOH
2CH YC=000BH
OOH
56H Check sum
16H End byte
68H Start byte
09H L
09H L
68H Start byte
43H Control field
OlH Links address
2EH Type identification
OlH Variable structure qualifier
06H Cause of transmission
OlH Application layer address
OlH Information object address
02H
8AH S/E QU DCS/RCS
07H Check sum
16H End byte
68H Start byte
09H L
09H L
68H Start byte
80H Control field
OlH Links address
2EH Type identification
OlH Variable structure qualifier
07H Cause of transmission
OlH Application layer address
OlH Information object address
02H
8AH S/E QU DCS/RCS
44H Check sum
16H End byte
Note: S/E QU DCS/ ---8AH rise (close) select
---89H down (open) select
Control address (201H) step rise execute
68H Start byte
09H L
09H L
68H Start byte
43H Control field
OlH Links address
2EH Type identification
OlH Variable structure qualifier
06H Cause of transmission
OlH Application layer address
OlH Information object address
02H
OAH S/E QU DCS/RCS
87H Check sum
16H End byte
68H Start byte
OCH L
OCH L
68H Start byte
4AH Control field
OlH Links address
7DH Type identification
OlH Variable structure qualifier
06H Cause of transmission
OlH Application layer address
10H Information object address
10H
OOH Begin address
7FH
MH RAM data length <7
OOH
XH Check sum
16H End byte
Amend RAM data
68H Start byte
NH L
NH L
68H Start byte
88H Control field
OlH Links address
7EH Type identification
OlH Variable structure qualifier
07H Cause of transmission
OlH Application layer address
10H Information object address
10H
OOH Begin address
7FH
MH RAM data length<7
RAM data
XH Check sum
16H End byte
68H Start byte
NH L
NH L
68H Start byte
44H Control field
OlH Links address
7FH Type identification
OlH Variable structure qualifier
06H Cause of transmission
OlH Application layer address
10H Information object address
10H
OOH Begin address
7FH
MH RAM data length <7
RAM data
XH Check sum
16H End byte
7F00H Remote measure (YC) high byte address
7F01H Remote measure (YC) low byte address
7F02H Remote control (YK) high byte address
7F03H Remote control (YK) low byte address
RAM address mean of RAM data