BBS  Email&MSN: [email protected]
  
Homepage   |   Power Generation   |   Project Financing    |   Equipments   |   Transmission   |   Financing-Ebook   |   Contact Us   |   Used Equipment   |   download   |   sitemaps   |   Spare Parts   |   BBS-Blog   |   Exclusive-Distributor   |   Exchange Link  

Mail List

E-mail:

Equipments
     Gas turbine & spare parts  
       GE 9FA 255mw Gas Turbine Generator  
       GE Licensed MS9001E Series Gas Turbine plant  
       42MW GE Gas Turbine Generator  
       PG6581B Gas Turbine Series Generator Plants  
       PG6581B Gas Turbine Set Supply Scope  
       Gas Turbine Spare Parts  
       Gas Turbine Generator Site Inspection  
       Quotationon Used PG6551B gas turbine plant  
       2MW Gas Turbine Generator  
       7mw-Siemens-SGT200-Gas-Turbine-Cogeneration-unit  
       10MW Gas Turbine Generator  
       Used Gas Turbine Generator Plant  
       Technical-Specification-PG6581B-Gas-Turbine  
       Supply-Scope-of-PG6581B-Gas-Turbine  
       Budgetary Cost for 108MW Gas Turbine Plant  
       Siemens Gas Turbine Generator  
       ABB-Siemens-ALSTOM-Gas-Turbine-Spare-Parts  
     HFO Diesel generator & Marine HFO Engine  
       8x8735kw MAN 18V32/40 HFO Diesel power Proposal  
       8x 4.1mw MAN 9L32/40 hfo power plant proposal  
       10x5.5MW MAN 12V32/40 HFO diesel plant proposal  
       3mw-9mw MAN 18V32/40 HFO Diesel generator  
       6 units 5.5mw MAN 12V32/40 hfo diesel plant  
       3x3.5mw MAN 8L 32/40 hfo diesel generator plant  
       1MW diesel generator   
       1.5MW Diesel Generator Set  
       2M Diesel Generator Plant  
       Sample Diesel Power Plant Proposal 9x2mw  
       Diesel power Plant List  
       Used Diesel Generator  
       Diesel Generator Pictures  
       Bio diesel generator power plant MW  
       Sample Pack List for 10x2MW HFO diesel power Plant  
       10kw-4000kw-Cummins-MTU-diesel-generator-set  
       HFO-diesel-generator-sets-running-on-biodiesel  
     MTU Cummins Perkins Volvo Diesel Generator  
       List of MTU Cummins PERKINS diesel generator  
       Leroysomer Siemens, Marathon Generator  
       MTU-Cummins-Perkins-diesel-generator-spare-parts  
       Germany-Deutz-diesel-generator-and-spare-parts  
     Spare Parts for Steam Turbine Power Plants  
     Power Plant Generator  
       Air Cooled Power Generator  
     Steam Turbine  
       Extraction Condensing Turbine  
       Condensing Steam Turbine  
       Recovery Turbine  
       Extraction Turbine  
       Required Data for Quotation  
       Alstom-Licensed-330MW-Steam-Turbine  
       Quotation-50MW-condensing-steam-turbine  
       Quotation-30MW-Condesing-Steam-Turbine  
     Boiler  
     Hydro Turbine  
     Engineering Machinery  
       Truck Mounted Crane Crawler  
       Trailer Concrete Pump  
       China track Bulldozer  
       China Crane  
       Benz Truck and Lorry from China  
       China-heavy-industry  
       China-outstanding-buses-and-coaches  
     Cable&Wire  
     New Building Cargo Ships vessel Finance from China  
     Electric Motor  
     China Famous Equipments for Power Plant  
     Transformer in MVA  
       Germany Certificates  
       Required Data for Quotation  
       Transformer Reference  
       Sample Inquiry  
     Wind Turbine Generator  
     Oil-Well-Drill-Bit  
       Oil-Well-Drill-Bit-Main-Products  
       Drill-product-series  
       Other-oilfield-products  
       Kingdream Rock Bits Catalouge 2011  
       IADC-CLASSIFICATION-OF-KINGDREAM-BITS  
       ROCK-BIT-COMPARISON-CHART  
     Drilling-Rig-for-Oil-Gas-Mining  
       Main-products-Directory-introduction  
     Best-Diamond-Brand-Cemented-Carbide  
     China-famous-steel-producers   
     China Largest Steam Turbine Producer  
       Harbin-Electric-Group-Spare-Parts  
     China-Best-Largest-Steam-Turbine-producers  
     Ingersoll Rand Air Compressor  
     Leading-farm-machinery-and-engineering-mechanical  
     Sawblade  
     Pump and pump parts  

Diesel Generator Proposal

Power Plant Proposal

Home > Equipments > HFO Diesel generator & Marine HFO Engine - 10x2MW Biodiesel power plant project Design Specifications with HFO Diesel Generator sets


 

10x2MW Biodiesel power plant project Design Specifications with HFO Diesel Generator sets

 
 
10x2MW Biodiesel power plant project Design Specifications with HFO Diesel Generator sets
 
 
 
 
 
 
 
 
 
 
 
 
 
China National Electric Wire&Cable Imp./Exp. Corp.
NBo zhongceGroup
April. 2009

TABLE OF CONTENTS
1.      General
1.1    Project brief
1.2    DG set configuration
1.3    Standard & code
2.      Design Fundament
2.1    Civil Work
2.2    Fuel
2.3    Cooling Water
2.4    Electricity
3.      General Arrangement
3.1    Main building
3.2    Radiator
3.3    Oil storage
3.4    Separator and pump room
4.      System Specification
4.1    DG System
4.2    Governor system for DG
4.3    Oil storage
4.4    Fuel Circuit System
4.5    Lube Oil Circuit System
4.6    Starting Air Circuit System
4.7    Cooling Water Circuit System
4.8    Intake air and ventilation system
4.9    Exhaust gas and environmental impact mitigatory system
4.10 Steam System
4.11 Water soften system for exhaust gas boiler
4.12 Oil and water waste disposal system
4.13 Electrical System
4.13.1    H.V. system
4.13.2    L.V. system
4.13.2.1          L.V. power source for power plant
4.13.2.2          Emergency generator
4.13.2.3          DC panel
4.13.3    Control system
4.13.3.1          DG
4.13.3.2          Central control panel
4.13.4    Protection system
4.13.4.1          Diesel engine
4.13.4.2          DG electricity system
4.13.5 230kV electrical system
5.      Main equipments specifications
5.1    Diesel engine
5.2    Alternator
5.3    Heavy fuel oil separator module
5.4    Lube oil separator module
5.5    Exhaust Gas Boiler
5.6    Air compressor
5.7    Air Receiver
5.8    Diesel Generator
5.9    Radiator
5.10 S9-1000/6.6/0.44 Station transformer
5.11 Heavy Fuel Oil storage
5.12 Diesel Oil Storage
5.13 Buffer HFO Tank:
5.14 Daily Heavy Fuel Oil Tank
5.15 Daily Diesel Oil Tank
5.16 Sludge Oil Tank
5.17 Common Circulating & Booster module
5.18 HFO transfer pump
5.19 Diesel Oil transfer pump
5.20 Station batteries and battery charger panel
5.21 Oily water separator
6.      Drawings
6.1    Layout for 10X2MW HFO power plant
6.2    Fuel system
6.3    Lube oil system
6.4     Boiler and silencer arrangement
6.5     Steam and water recycle system
6.6     Starting air system
6.7     Oily water treatment system
6.8     Oily water separator
6.9     Single line drawing for power plant

 
1. General
1.1    Design input
INFORMATION REQUIRED FOR SELECTION / SIZING / DESIGN OF POWER PLANT
A SITE CONDITIONS
SITE METEREOLOGY VALUE
1) Altitude (m above Sea Level) 14 MSNM
2) Maximum Ambient Temp. (C)
3) Relative Humidity at Maximum Ambient (%)
4) Wet Bulb Temperature of the Area (C)
5) Environment (Dusty / Clean)
6) Presence of any Hazardous or ChemicallyActive Gases In Surrounding Air - NO
7) Soil Condition at site (normal, marshy, black cotton etc.)
8) Soil bearing capacity (< 15 tons/m2 or > 15 tons/m2)
9) Water table at site YES
 
B POWER REQUIREMENT (As discussed personally present conditions given)
1) Maximum Demand (kVA)
2) Minimum continuous process loads (kVA / kW) 20000KW
3) Grid Voltage and Frequency
Variation Percentage 230KV GRID TRANSSMITION LINE, 60HZ
4) Whether Independent Auxiliary Power Supply (415 V) available
5) Proposed Power Plant capacity (MW) 1MW GENERATOR X 20
 
C STEAM REQUIREMENT (IF ANY)
1) For process Steam (Quantity T/hr, pressure)
2) For air-conditioning / chillers etc (quantity T/hr., pressure)
3) For fuel heating only
4) Existing Boiler(s) details
 
D FUEL
1) Type of fuel to be used HPS / LSHS / FO / LDO / HSD / NG / BIOGAS
(Please provide specifications of fuel, in case of Gas Annexure IV shall be filled also)
BIODIESEL EN 14214
2) Approximate price of fuel at site USD $ 2.00
3) Design Viscosity of Fuel handling System (180 or 380 cSt at 50 C)
4) Fuel Handling and Storage Facility at site (If any for existing Generating Sets)
20TON BIODIESEL STORAGE
 
INFORMATION REQUIRED TO DETERMINE OPERATING PHILOSOPHY
A POWER PLANT OPERATION (Continuous / Base Load / Standby / Emergency / Peaking) 8 HOURS PEAK
 
B PARALLEL OPERATION
1) With grid (Yes / No )
2) Between proposed DG Sets (Yes / No)
3) With existing DG / TG Sets (Yes / No)
Details of existing DG /TG sets (if parallel operations req.)
i) Supplier / Model / Name plate details
ii) Rating (kVA / kW)
iii) Make / Model / Type of Governor
iv) Type of Excitation / AVR
v) Synchronization Facility
 
C SPECIAL REQUIREMENTS
1) Motor Starting Duty (If any)
(If yes, please provide details wherever possible)
2) Furnace application
(If yes, please provide details wherever possible)
3) Non-linear Thyristor Loads, if any
4) Any other non-standard loads, if any
5) Voltage requirement (3.3 / 6.6 / 11 kV) 380-415
6) Water Availability (Sufficient- Cooling Towers, Scarce - Radiators)
 
INFORMATION ABOUT THE CLIENT (PURCHASER / OWNER COMPANY)
1) Annual Turnover of the Company
2) Main Product and installed capacity
3) Location of the Site
4) Availability for proposed Power plant at site
5) Contact Person at Site
Address / Telephone / Fax #
6) Whether power requirement is for existing plant /expansion project / new project
7) Duty structure (EPCG / EOU / Project Import / IPP)
8) Project Implementation Schedule
(Power Out - month / year)
9) Mode of Financing the Project OWN
10) Type of Offer Required (Feasibility Study / Indicative / Budget / Firm)
11) Cost of existing Power
(a) From Grid including Max. Demand Charges
(b) Generated from other source (DG / TG etc.)
 
Additional Information
1. What is the current project stage? Please specify the expected schedule.
2. Is the fund for the project ready? If yes, where from?
3. What is the process for awarding EPC contractor? Negotiation or public tendering?
4. Why need Chinese equipments and EPC services?
5. What is your role for this project? Developer/owner/sponsor/investor/EPC contractor/agent/consultant?
6. What type of set you need? Brand new or used?
 
1.2    Project brief
At the requirement of the Buyer, the Seller will build a 10x2MW biodiesel Power Plant for Buyer operating with biodiesel in Panama.
The power plant consists of 10 sets of diesel generators with capacity of 2000KW per set.
 
1.3     DG set configuration
The specification outlines the scope of supply for each DG set;
The DG set is driven by diesel engine model GN8320ZD8 manufactured by NBo zhongceGroup, which is the largest middle speed engine manufacturer in China;
The engine will use biodiesel oil (380cSt/50�?as fuel.
 
1.4     Standard & code
The design is according to the Chinese standard & code, in line with ISO/IEC standard. The project is designed under the merit of “advanced technology, highly efficiency, safety, economy and practicality�?
The installation and the commissioning should be in line with the above standard & code.
 
2.      Design Fundament
2.1 Civil work:
The main building, control room and pump house above the ground all adopt steel structure. The under ground portion are reinforced concrete structure.
 
2.2 Fuel:
Biodiesel is the main fuel. If HFO is used, the HFO need to be heated by the steam that supplied by steam exhaust gas boiler.
 
2.3 Cooling water:
Radiator for each generator is arranged in power plant.
 
2.4 Electricity
One 1000kVA station transformer is used to supply 440V source for the power plant.
One 400KW diesel generator is supplied as power when the whole power plant is stopped.
 
3. General arrangement:
3.1 Main building
The main building will be arranged in 2 lines:
The first line (Control room) is for the electrical control room, switchgear room, water soften treatment room and air compressor, air receiver. The second floor is for steam exhaust gas boilers and silencers, boiler is hypaethral layout. The distance of the columniation is 6 m; the span is 8 m, length is 72M and height is 5 m;
The second line (Generator hall) is for DG, lube oil tank, lube oil separator, booster, etc, the span is 18m, length is 72m; there is a traveling double girder crane (10t) in the room.
a.      Control room
The total area of control room is 576 square meters with length of 66m, width of 8m and height of 5 m. The roof of the control room is of reinforced concrete construction, and is flat roof that is convenient for installing equipments on it. One silencer and its bracket with weight of 1.2 ton are arranged for each generator, total is 10 sets, and total weight for 10 silencers is 12 tons. An exhaust gas boiler with weight of 5 tons is arranged for every three generators, total is 3 boilers, and total weight for 3 boilers is 15 tons. For each boiler, girder for bearing the weight shall be arranged.
Inside the control room, there are HV switchgear room, LV control room, water soften treatment room and air compressor room. All HV and LV cables will be connected to switchgears or control panels through cable channels in the control room.
Double deck sound insulation glazing with length of 1800 mm, width of 1500 mm, and thickness of 8 mm is installed on the control room wall facing to the alternator end of the generator. The bottom of glazing shall be 800 mm above the ground.
Ventilation for the control room adopts air conditioner.
b.      Generator hall
The total area of steel construction main building is 1296 square meters with length of 72 m, width of 18m. The distance of the columniation is 6 m. A 10 tons double girder bridge crane with span of 16.5 m is installed in the generator hall. The installing height of columniation for crane railway is 7 m, and its total height is 9.6m. The maximum height of the main building is 12.8 m.
Main equipments in generator hall:
a.      10 sets of 2MW generators
Model: 2000GF1-1A; Rated power: 2000kW; Rated speed: 600r/min; Weight for each generator: 44 tons including diesel engine 25 tons, alternator 16 tons and engine frame base 2.8 tons.
b.      One set of 400kW emergency diesel generator
Model: 400GF; Rated power: 400kW; Rated speed: 1000r/min; Total weight: 8.5 tons
c.       1 set of fuel booster module
Weight for the fuel booster module; 2.3 tons.
d.      5 sets of lube oil separator modules
Weight for each lube oil separator module: 400kg.
 
3.2 Radiator
10 outdoor radiators are arranged besides the main building.
 
3.3 Oil storage
Total area for oil storage is 1254 square meters with length of 66 m and width of 19 m. The following oil storages are arranged:
a.      Two heavy fuel oil storages with volume of 1000 cubic meters, storage diameter of 11.5 m, height of 10.5 m, dry weight of about 80 tons and total weight of 1080 tons for each oil storage. The intensity of foundation shall be fully considered.
b.      One diesel oil storage with volume of 300 cubic meters, storage diameter of 7.6m, height of 8 m and total weight of 350 tons. The intensity of foundation shall be fully considered.
c.       Two buffer heavy fuel oil tanks with volume of 100 cubic meters, storage diameter of 5.73 m, height of 5 m and total weight of 120 tons.
d.      One daily HFO tank, one daily DO tank and one sludge oil tank with volume of 50 cubic meters, storage diameter of 3.82 m, height of 4.5 m and total weight of 55 tons for each oil tank.
Fireproofing wall with height of 1.6 m is arranged around the oil storage, earthing for avoiding thunder-strike shall be considered for the oil storage.
 
3.4 Separator and pump room
The total area of separator and pump room is 104 square meters with length of 13 m, width of 8 m, and height of 5 m.
Main equipments in the separator and pump room:
a.      Three set of separator modules;
b.      Two HFO transfer pumps and DO transfer pumps
 
4. System specifications:
4.1.     DG system:
According to the power capacity 20MW, the project plan configures 10 units of diesel engines and generators.
Rating of the D.G. set 
Under above mentioned site conditions
-----------------------------------------------------------------------------------------------
       Rating at       Alternator       Rating at
       engine         efficiency       alternator
       crankshaft                     terminal(MCR)
       KWm             ( % )        KWe         KVA(0.8 pf)
-----------------------------------------------------------------------------------------------
Nominal        2206             94         2000      2500
Running   
-----------------------------------------------------------------------------------------------
Note : COP rating will be 90 % of MCR
 
4.1.1.      2MW diesel engine:
Technical particulars for the diesel engine are as follows:
Number of cylinders                8
Arrangement of cylinders           In Line
Bore (mm) X Stroke (mm)           320 X 380
Type                                            4-stroke, direct injection, turbocharger, after cooler
Rotational speed                        600 RPM
Mean effective pressure            18 Bar
at rated power & speed
Mean piston speed                  7.6 m/sec.
Rotation seen from flywheel        Clockwise.
Swept volume per cylinder         30.578 litres
Combustion chamber volume        2.352 litres
Compression ratio                   13:1
Max. combustion pressure         125 bar
(at rated power/speed)
 
The engine should be capable of accepting a sudden load as per the guidelines in ISO-8528-5-1993(e). As per this standard, the maximum sudden load increase stages are
 
         Baseload %     Sudden load   increase to %
--------------------------------------------------------------------------------
1st Stage          0%          40                40%
2nd Stage             40%         30                  70%
3rd Stage       70%         20                  90%
4th Stage       90%         10                  100%
During each of the above-mentioned stages of sudden loading, the transient speed drop will be restricted to a maximum value of 10% of the rated speed. 
 
4.1.2.      Alternator
The Alternator is self-excited, brush-less type in two bearing construction with single shaft extension and IP 23 enclosure. The alternator is fitted with bearing temperature detectors.

Technical data of alternator

- Rated output kVA                                          2500 KVA
- Power factor                                             0.8 lag
- Max. Alternator output at site                   2000 KW
- Duty                                                         Continuous
- Rated speed                                               600 RPM
- Rated voltage                                          6600 V
- Efficiency at 100% load and 0.8 PF             �?4 %
- Direction of rotation                                 clockwise
- Number of poles                                             12
- Rated frequency                                             60 Hz
- Over-speed                                                    20% for 2 minutes
- Overload capacity and duration                10%, for max. 1 hr in every 12 hrs
- Insulation class                                         F
- Enclosure                                                IP 23
- Temp. rise class                                       F
- Excitation and AVR type                           Brush-less, AVR
- Connection                                              Star
 
4.2 Governor system for DG
Woodward 2301D digital control and UG15 actuator are adopted for load sharing and speed control of diesel generator.
The 2301D is a microprocessor-based digital control. The control is housed in a sheet-metal classis and consists of a single printed circuit board. The 2301D is configured using a computer with Woodward Watch Window software. The computer connects to the 2301D through a 9-pin connector (RS 232 port). The control operates from a 24Vdc supply. The actuator output, one analog input, and one analog output are configurable. The 2301D features dual dynamics and soft load transfer, to and from a bus. The 2301D includes one load sensor circuit, one actuator driver, one MPU speed sensor, one configurable analog output, one configurable analog input, eight discrete inputs and four discrete outputs. The 2301D operates within a range of �?0 to +70�?
The 2301D provides load sharing and speed control of diesel generator. The 2301D has four operating modes �?speed control, isochronous load sharing, droop base load, and isochronous base load.
Woodward UG-15 is a hydraulic powered electric actuator. The UG-15 provides the muscle for 2301D. The UG-15 takes a given electrical input signal and converts it to a proportional hydraulic output-shaft position to control engine flow.
 
4.3 Oil storage
There are two 1000m3 HFO storages, two 100m3 buffer HFO tanks, one 300m3 DO storage, one 50m3 daily HFO tank, one 50m3 daily DO tank and one 50m3 sludge oil tank. HFO separator double module and fuel pumps are installed in the separator and pump room.
Heavy fuel oil transported by fuel truck (about 30 ton) will be pumped to two HFO storages and two buffer HFO tanks. Two HFO transfer pumps are installed in the room, one is for standby. Filter and flow meter are also installed before the HFO transfer pumps. HFO in the two HFO storages can be transferred to the buffer HFO tanks by the two pumps.
Diesel oil transported by fuel truck (about 30 ton) will be pumped to DO storage and daily DO tank. Two DO transfer pumps are installed in the room, one is for standby. Filter and flow meter are also installed before the DO transfer gear pumps. DO in DO storage can be transferred to the DO daily tank by the two pumps.
For all HFO storages and tanks and sludge tank, steam coil pipes are installed inside and thermal insulations are provided outside.
Fuel temperature in HFO storage is recommended to be 50-60 centigrade degree, fuel temperature in buffer HFO tank to be 70-80 centigrade degree. The buffer HFO tanks are used for pre-separation of sludge and water contained in HFO and providing a suitable constant HFO temperature. Gravitational settling of water and sediment in HFO is an extremely slow process due to small density difference between HFO and the sediment. A large fuel oil surface area and a low viscosity are needed for the settling process. The volume of each buffer HFO tank is 100m3, which is enough for 24 hours continuous operation at rated load.
HFO in buffer HFO tank will be pumped to three separator modules. The separating capacity for each separator unit is 3000 kilogram one hour. When two separators work together, the separating capacity is 6000 kilograms one hour. For whole power plant, the maximum HFO consumption one hour is about 3000 kilograms. The clean HFO will be pumped to daily HFO tank, and the sludge oil will be pumped to sludge oil tank through the sludge oil pump installed on separator module.
Heavy fuel oil in daily HFO tank and diesel oil in daily DO tank will be pumped to booster module in generator main building.
 
4.4 Fuel Circuit system
4.4.1 Type of fuel:
The engines are suitable for operation on DO (Diesel Oil) / HFO (Heavy Fuel Oil or Furnace Oil with maximum viscosity 380 cSt at 50 deg. C.);
When starting or stopping the engine DO (Diesel Oil) is used as fuel. When the water temperature at inlet to engine exceeds 60 degree centigrade, and the HFO (Heavy Fuel Oil) is heated to the required temperature, the fuel can be changed from DO to HFO through a changeover oil tank.
Equipment fitted on the engine:
 
-      Individual fuel injection pump for each cylinder with fuel rack & linkages.
-      Individual injector fitted on each cylinder head.
-      High-pressure injection pipes
-      Main fuel rails for feeding and return.
-      High-pressure pipe connection for each cylinder
Equipment delivered loose:
 
1)                  Three HFO separator modules
2)                  Two fuel viscosity control modules (booster) consisting of:
Two electric motor driven fuel feed pump (one for working, one for standby);
Two electric motor driven fuel booster pump (one for working, one for standby);
One duplex type coarse filter;
One pressure-regulating valve;
One steam heater for HFO;
One flow meter for HFO;
One 3 way fuel changeover valve;
One viscometer & temp controller;
One emergency pressure safety valve;
One duplex type fine filter;
one mixing vessel with safety valve;
One pressure-regulating valve in fuel return;
3)   Complete interconnecting piping with flanges, fasteners, valves, non-return valves, bosses,        supports, etc as necessary.
Fuel consumption:
The hourly rate of fuel consumption per Kilowatt Power delivered at the crankshaft flange at rated power & speed (after running in of the engine & for engine with driven raw water, fresh water & lube oil pumps) is 198g/kWh, when engine operates at Maximum Continuous Rating (MCR).
 
FUEL CONSUMPTION (with 3 driven pumps)
====================================================
         GN8320ZD8           Consumption at  
                            (600 RPM)             engine Cr.shaft
                                                   g/kWh
====================================================
                100% Load              198.00
SITE       -----------------------------------------------------------------------------
          75% Load                202.00
CONDITION-------------------------------------------------------------------------
             50% Load                211.00
====================================================
The values are subject to a 3% tolerance and apply when burning fuel with a net calorific value of 10,200 KCal/Kg minimum.
CLIMATIC CONDITIONS
ISO Conditions
Air temp. to turbocharger inlet              25 deg. C
Atmospheric pressure                     750 mm Hg
Relative humidity                         60 %
Water temp. at charge air cooler inlet       25 deg. C
Site Conditions (Assumed)
Air temp. to turbocharger inlet              45 deg. C
Atmospheric pressure                     750 mm Hg
Relative humidity                         60 %
Water temp. at Radiator outlet             52 deg. C
 
The heavy fuel oil from daily HFO tank and diesel oil from daily DO tank will be pumped to the mixing vessel on the booster module through two fuel feed pumps. After heated by steam, the heavy fuel oil (or diesel oil) with constant viscosity about 12-15 cst will be pumped to fuel main pipe. The booster module is used for controlling viscosity and supplying fuel for generators. There are two booster modules installed in the main building, fuel-supplying capacity for each booster module is 5000 kilograms one hour (Maximum feed capacity is 10000kg one hour, return oil is 5000kg one hour), one works, one is for standby. The two fuel main pipes are connected with valve, which is used for emergency in case of one booster module failure.
Return oil from each generator will back to the mixing vessel through return main pipe, the two return main pipes are also connected with valve.
 
4.5  Lube oil circuit system
Oil sump capacity (ltr)
The engine is equipped with a dry sump attached to the bottom of the crankcase. The lube oil for the engine is stored in a separate tank positioned away from the engine. This arrangement offers much more reliability than the wet sump arrangement & also increases the time between oil changes by lube oil separator module.
The total oil capacity of this lube oil tank is 2000 ltrs.

Lube oil consumption

The average lube oil consumption is 1.6 g/kWh (+/- 0.2 g/kWh) at MCR at crankshaft for a well-run engine.
One lube oil separator module is arranged for two generators, total in the main building are five lube oil separator modules. Lube oil separator is used for cleaning lube oil and prolong usage time.
Equipment fitted on the Engine:
-      One engine driven lube oil supply pump
-      One engine driven lube oil transfer pump
-      One pressure-regulating valve
-   One lube oil thermostatic valve (option)
-      Complete interconnecting piping with flanges, fasteners, valves, non-return valves, bosses, supports, etc as necessary.
Equipment delivered loose:
-      10 tanks for lube oil (2000 ltrs capacity) with interconnections to the engine
-      10 electric motor-driven lube oil-priming pumps
-      10 manual lube oil-priming pumps
-      10 lube oil coolers
-           10 centrifugal lube oil filters (FLL75 bypass type)
-           10 lube oil duplex type filters
-           5 lube oil separator modules
-          Complete interconnecting piping with flanges, fasteners, valves, non-return valves, bosses,    supports, etc as necessary.
 
4.6 Starting air circuit system
The DG is started by the compressed air.
Two air compressors, two 2.5m3 air receivers and one top up are arranged for the power plant, the capacity of each air receiver is 2500 liters, which is enough for starting one generator 30 times without intermediate refilling of the receiver.
High-pressure compressed air about 3 Mpa from the air receivers will be sent to generators through air main pipe, and also be sent to exhaust gas boilers for cleaning chimney, to lube oil separator modules, HFO separator modules and booster modules through pressure reducers for control air.
Equipment fitted on the engine:
Compressed air starting equipment including:
-      One rotary distributor
-      One air-starting valve in each cylinder head
-      Connecting air piping on the engine
Equipment delivered loose:
-      Two air compressors
-          Two air receivers
-          One top up
-          Complete interconnecting piping with flanges, fasteners, valves, bosses, supports, etc as necessary.
 
4.7 Cooling water circuit system
Radiator made by GEA is arranged for each generator, and an electric water pump is arranged for the water circuit system.
Drawn by the electric water pump from the radiator, the cooling water flows to the air cooler, and to the injector cooling oil cooler and to the lube oil cooler, and then enters the inlet water main pipe and the turbocharger. The cooling water is discharged out through the outlet water main pipe. Finally the water is cooled in the radiator.
Equipment fitted on the engine:
-            One lube oil cooler
-            One injector cooler
-      One water-cooled charge air cooler
Equipment delivered loose:
-          10 radiators (outdoor, GEA)
-          10 electric water pumps
-          Complete interconnecting piping with flanges, fasteners, valves, bosses, supports, etc as necessary.
 
4.8 Intake air and ventilation system
The air intake system is equipped with air filtration (ABB type installed on the engine) to clean air.
For 10 diesel generators, air consumption is 125000m3/h. 10 axial-flow explosion-proof fans opposite to each generator are arranged for the main building on the engine side. Airflow capacity for each fan is 15870m3/h; total airflow capacity is 158700m3.
The axial-flow fans are used for supplying air for the generators and reducing temperature in the engine room through convection. The quantity of heat dissipated from the generators is about 4200 MJ/h. The air will be discharged through natural ventilation on the upper side of the main building.
 
4.9 Exhaust gas and environmental impact mitigatory system
Air pollution prevent
All diesel engines for the power plant are acquired international air pollution prevent certificate according to the provisions of Annex �?of the international Convention for the Prevention of Pollution, 1973, as modified by the Protocols of 1978 and 1997 relating thereto and of the Technical Code on Control of Emission of Nitrogen Oxides From Marine Diesel Engines.
Emission data as follows:
Applicable Nox emission limit (regulation 13 of Annex �?: 12.5g/kWh
Engine’s actual Nox Emission Value: 9.69g/kWh
Noise
The mechanical noise beside the diesel engine at a distance of 1 m is 112 dBA. The mechanical noise will be proofed and reduced by the main building.
The exhaust gas noise is reduced through a residential type silencer to 70dBA at a distance of 1 m.
The exhaust gas from diesel generator flows to exhaust gas pipe (DN400), pass a tee joint, and then divides two ways. One flows to silencer through a butterfly valve, another flows to exhaust gas boiler. When the exhaust gas boiler works, the butterfly valve for silencer will close and the butterfly valve for exhaust gas boiler will open, and then exhaust gas will vent from the chimney on the boiler. When the boiler cannot work normally or the boiler need to be stopped, the butterfly for boiler will close and the butterfly valve for silencer will open, and then exhaust gas will vent from the chimney on the silencer.
Three steam exhaust gas boilers are arranged for the power plant, each one will connect with three diesel generators. One exhaust silencer (Residential type) is fitted to the each generator.
Equipment fitted on the engine:
-      Lagged set of exhaust manifold with expansion bellows
-      One ABB turbocharger.
-      Exhaust outlet connection with expansion bellow.
Equipment delivered loose:
-          10 exhaust silencers
-          3 exhaust gas boilers
-          Insulation /lagging/cladding for exhaust ducting
-          Complete interconnecting piping with flanges, fasteners, t-joints, butterfly valves, bosses, supports, etc as necessary.
 
4.10 Steam system
Three exhaust gas boilers are arranged on the roof of control room. Heat exchange area for each boiler is 67 m2, steam capacity for each boiler is 700kg one hour at 170 degree centigrade and 0.7 Mpa. Steam from boilers will flow to steam main pipe and divide to separator and pump room, oil storage and main building through main steam distributor and steam distributors. The main steam distributor is located on the roof of control room, and other steam distributors are located beside the equipments need to be heated.
Equipments for steam system:
-          3 exhaust gas boilers
-          6 water feed pumps
-          4 Steam distributors
-          Insulation /lagging/cladding for steam pipes
-          Complete interconnecting piping with flanges, fasteners, t-joints, valves, bosses, supports, etc as necessary.
 
4.11 Water soften system for exhaust gas boiler
One water soften equipments are arranged for the power plant, water treatment capacity is 2000kg one hour.
The water soften equipment adopts resin exchanger treatment system.
Equipments for water soften system:
-          1 water soften equipment
-          2 water feed pump
-          One water tank
-          Complete interconnecting piping with flanges, fasteners, valves, bosses, supports, etc as necessary.
 
4.12 Oil and water waste disposal system
Oily water will be collected in an oily water pond through water channel in the power plant. An oily water separator module is arranged to separate oil from the oily water. The oily water treatment capacity for the separator module is 5 cubic meters one hour. The oil content for the treated water is 10 ppm, and can be drained directly. The oil separated from the oily water will be collected in the sludge oil tank.
 
4.13 Electrical system
4.13.1    H.V. system
Ten 2MW/6.6kV HFO generators will work in parallel and supply electricity to one 6.6KV bus-bar, and feed to one 25MWA/230kV main transformer through one outgoing panel.
One 1000kVA station transformer is used to supply 440V source for the power plant.
One 400KW diesel generator is supplied as power when the whole power plant is stopped.
 
6.6kV generator system
Ten 2MW/6.6kV diesel generators are arranged for the power plant. For each one generator, the standard configure includes one switchgear for generator output and potential transformer, one control and operation panel (COP) and one local control desk (LCD).
The neutral of the generator is earthed through resistor. As requirement of the protect system, two neutral resistor panels are configured for the power plant earthing system. Five Gen-set configure with a resistor connecting panel, which comprises of 5 knife switch to select the first feeding generator. Only one generator can connect to the resistor by the knife switch for the reason of the circumfluence current among generators. There has a zero sequence current transformer configured in the Gen-set switchgear, to protect the earthing fault in the cable between generator terminal and the CT.
All , ten generators are connected with a single bus-bar. A 6.6kV bus-bar PT panel is arranged for parallel operation. All 6.6kV H.V. panel adopt KYN28A-12 metal-enclosed removable switchgears, the switch for generator switchgear adopts VS1 vacuum circuit breaker (with truck), its rated current is 630A, and rated short-circuit breaking current is 31.5KA.
 
Generator HV panels
The generator connects to the bus-bar, by vacuum circuit breaker in the generator switchgear.
Major Components in generator switchgear:
1)                  3 pole truck type DC/AC 220V electrically operated motor energized VS1 Vacuum Circuit Breaker
2)                  Metering / Protection CT and PT
CT type: CT LZZBJ9-6.6 150/5A with two windings for each phase
Two CTs are installed in the generator switchgear. One CT is for current and power measuring (phase A and C) and excitation adjusting (phase B); another is for 2301D load sharing controller.
PT type: one REL-6.6 with two windings for each phase
One group of windings in potential transformers is star connected for measuring and protection system. Another group of windings is triangularly connected for single phase earthing protection.
3)                  Digital integrated relay
DMR-362 digital integrated relay is adopted for gen-set protection, which is used for alternator protection, switch control, monitoring, measuring and display.
The following functions and protection can be carried out on the relay:
-          Differential
-          Voltage locked over current
-          Reverse power
-          Over current
-          Single phase Earthing
-          Over voltage
-          Low frequency
-          Over frequency
-          Over load
-          Accurate measuring of all operation parameters such as power, voltage, current, frequency, power factor and others
-          Display the conditions of all switches
-          Running record and failure storage
4)                  Local / Remote control selector
5)                  VCB ON/OFF
6)                  DSSX25 kWh and kVarh meter
 
Potential transformer panel
Major Components in PT panel:
1)      Fixed PT installation truck with arrester.
2)      PT type: one REL-6.6 with two windings for each phase
One group of winding in potential transformers is star connected for measuring and protection system. Another group of winding is triangularly connected for single phase earthing protection.
 
4.13.2    L.V. system
The auxiliary equipments for generator include 10 radiators (33KWx10), 10 water pumps (18.5kWx10), 2 air compressor motors (18.5kWx2), 5 lube oil separator motors (2.2kWx5), 2 boosters (7.5kWx2) and one DC power source panel (4kW).
The auxiliary equipments for power plant include 2 HFO pump motors (18.5KWx2), 2 DO pump motors (18.5KWx2), 3 HFO separator modules (11kWx3), 6 boiler water feed pump motors (2.2kWx6) and one soft water pump motor (3kW).
The lighting and air conditioner system is about 30kW, all lighting equipments are considered during civil work.
The fire fighting system includes 2 fire-fighting pumps (22kWx2) and one water feed pump (7.5kW). All fire-fighting equipments are considered during civil work.
The maintenance system includes one 10T double girder bridge crane (10kW) and maintenance electrical boxes (total 50kW).
 
4.13.2.1  L.V. power source for power plant
Two L.V. power sources are arranged for power plant. One is supplied with a station transformer (1000KVA/6.6kV/0.44kV), another is supplied by a emergency diesel generator (400kW/0.44kV) when the whole power plant is stopped.
 
4.13.2.2   Emergency generator
The diesel generator is used as emergency power source for the power plant.
 
4.13.2.3   DC panel
The power supply of control plant, protection, signal, automatic device and trouble lighting adopts 200AH direct current electrical source system.
220/24V DC battery charger of suitable capacity along with Lead acid type rechargeable batteries (12 V DC) is used. Charger is fully automatic, with float and boost charging facility. One set of DC/DC transfer module with 60A capacity for 24V output.
Major Components in the DC panel
1)                  Source inspect and change over module
2)                  Chargers and booster module
3)                  12V batteries and battery detect unit
4)                  AC/DC ammeters, voltmeters
5)                  LCD operation screen

Protections provided for Chargers

6)                  Over load / short circuit / earth fault
7)                  Over voltage
 
4.13.3    Control system
4.13.3.1  DG
For each one generator, one control and operation panel and one local control desk are supplied.
 
Gen-set control and operation panel
The control and operation panel in the control room provides necessary Monitoring, Control and Protection functions for the DG set. It controls the Gen-set running according to the program set in PLC. All Gen-set’s running parameters such as voltage, current, power, power factor, frequency, and speed can be displayed on it.
Major Component in console
1)      Control PLC
2)      Speed Governor controller
3)      Automatic Voltage Regulator
4)      Engine Frequency Monitoring Unit
5)      Meters
Ammeters (3 nos.)
Voltmeter with selector switch
Power meter
Frequency meter
PF meter
Analog Excitation fundamental ammeter
Analog Excitation harmonics ammeter
Counter for running hours
6) Operation and indicators
Push buttons, change over switches
VCB engaged indication,
Engine start permission indication
Excitation change over switch
DG VCB ON/OFF
DG VCB Trip and alarm indication
Engine Idling/Rating
Engine start
Engine normal and emergency stop
7) AVR
The integral TWL-ND AVR is designed for the TFW generator specially. It configures with stability adjusting, voltage adjusting, and gen-set paralleling reactive power sharing adjusting.
Input capacity         AC 230V
Compare voltage      AC 100V from PT AC
Current signal         CT 5A from CT B
Max. Output           DC.100V, 10A
Trigger Type          Alternator exciter Remanence
Accuracy             ±1%
Am. Temp            -40~+60�?/DIV>
Reactive sharing      Auto regulating
8)                  T4500 auto synchronizer
SELCO T4500 auto synchronizer is designed for automatic synchronization between generator and bus-bar in a minimum of time by controlling the speed via the electric servomotor on the governor.
The T4500 measures the voltage across two phases on either side of the circuit breaker in order to obtain data on voltage, frequency and phase difference for closing the circuit breaker at exact phase accordance.
The synchronization function will become active when the difference between the bus voltage and the generator voltage is within limits. The voltage difference is selectable between 2% to 10%.
When the synchronization function is active, the T4500 will automatically adjust the speed of the generator through the governor in order to match the frequency to the bus-bar.
The T4500 will continuously adjust the generator speed until the frequency difference is within limits. When the voltage and frequency difference are within limits, the closing signal will be activated just before the next phase accordance, anticipating the circuit breaker make time. The T4500 compensates for this make time so that the circuit breaker will close exactly at zero phase.
Specifications for the T4500:
Circuit breaker operating time               20~200mS
Frequency difference                       0.1~1Hz
Voltage difference                         10%
Reference voltage                         110/100V with voltage matching
Operating Temp                           -20~+70�?/DIV>
Contact rating                              AC: 380V, 2A, 250VA; DC: 110V, 2A, 100W
Auto synchronization system is adopted between generators and network and among generators. Manual synchronization system is supplied for standby.
9)                  Load sharing
All generators can work in parallel; load can be equally shared among all generators automatically. Woodward programmable and configurable speed governor controller 2301D are adopted to control the engine, which can share or operate Gen-set in base load mode or isochronous mode.
Main functions on the control and operation panel:
-          Starting engine
-          Speedup
-          Speed-down
-          Generator switch ON/OFF
-          Voltage adjustment
-          Reactive power share
-          Synchronization
-          Voltage measuring changeover
-          Lube oil pressure
-          Water pressure
-          Voltage
-          Current
-          Frequency
-          Power
-          Excitation current
-          Speed
-          Alarm
 
Local Control Desk
Local Control Desk is provided for monitoring pressure and thermal parameters of the running engine. Also starting, stopping and speed control of engine is possible in local control operation mode. It is located near the engine.
Major Components in Local Control Desk
1)      Pressure gauges, switches
Lube oil filter inlet pressure
Lube oil filter outlet pressure
Lube oil in cylinder head inlet pressure
Cooling water pressure
2)      Temperature indication
Cylinders cooling water temperature scanner
   Cylinder cooling water outlet temperature measurement system with Cu50 thermo resistor for each cylinder and scanned by a multi-channel meter.
Engine exhaust temperatures scanner
   Pyrometric exhaust gas system with thermocouple for each cylinder and turbocharger, and scanned by a multi- channel meter.
Lube oil engine inlet /outlet temperature
Water engine inlet/outlet temperature
3)      Engine RPM indicator with cranking and over speed protection.
4)      Push buttons, indicating lamps, selector switches
- Common engine alarm
- Engine start permission
- Local / remote mode select
- Engine start / stop
- Flasher off
- Engine speed raise / low
- Emergency stop
 
4.13.3.2   Central control panel
A central control panel is installed in the control room, which is used for displaying signals for auxiliary equipments including oil storage level alarm, water level alarm, oil temperatures, steam pressure and others.
 
4.13.4    Protection system
4.13.4.1  Diesel engine
The diesel engine will stop automatically in case of the following failures:
-          Very low lube oil pressure
-          Very high water engine outlet temperature
-          Engine over speed
The diesel engine will alarm automatically in case of the following failures:
-          Low lube oil pressure
-          Low water pressure
-          High lube oil temperature
-          High water temperature engine inlet
-          Alternator bearing temperature high
 
4.13.4.2   DG electricity system
The generator adopts digital integrated relay protection system for monitoring and protection.
A DMR362 digital integrated relay is installed on generator switchgear, which is used for alternator protection, switch control, monitoring, measuring, display and SOE record.
The following functions are configured on the relay:
-          Differential current
-          Reverse power
-          Instant trip current
-          Voltage locked over current:
-          Over current
-          Over load
-          Earth failure
-          Over voltage
-          Under voltage
-          Low frequency
-          Over frequency
4.13.5 230kV electrical system
25MVA/6.6kV/230kV main transformer and all related equipment for 230kV electrical system are not included, and shall be provided by customer themselves.
 

5. Main equipments specifications
5.1 Diesel engine:
Model
GN8320ZD8
Type
Inline, four-stroke, direct injection, turbocharged, and after cooled
Quantity
10 sets
Rated power
2206kw
Rated speed
600r/min
Bore/stroke
300/380mm
Starting method
Compressed air
Cooling system
Open water cooling
Dimension
5620×1620×2760mm
Weight
25000kg
Manufacturer
NBo zhongceGroup Co., Ltd
Main parts of GN8320ZD8 Diesel Engine
a.      ABB turbocharger
b.      WOODWARD electrical governor
c.       GEA after cooler, lube oil cooler and radiator
d.      Flexible coupling
 
5.2 Alternator
Model
TFW-900
Type
Brush-less synchronous alternator
Quantity
10 sets
Rated power
2500KVA
Rated speed
600r/min
Rated voltage
6600V
Frequency
60HZ
Power factor
0.8 lagging
Insulation class
F/F
Excitation
AVR
Dimension
3480×2150×2150mm
Weight
16000kg
Manufacturer
NBo zhongceGroup
 
5.3 Heavy fuel oil separator double module
Model
KYDH309CD-23 module
Quantity
3 sets
Rating treatment L/h
3000
Centrifuge Temperature
90-98�?/DIV>
Light phase output pressure: MPa
0.2MPa
Separator motor
11kW
Sludge pump
1.5kW
Power source
3P/440V/60Hz
Overall dimensions LxWxH
2000x1800x2100mm
Weight
2000kg
Material medium
Heavy fuel oil (380CST)
Manufacturer
NBo zhongceGroup
 
5.4 Lube oil separator module
Model
KYDR203CD-23
Quantity
5 sets
Rating treatment L/h
1500
Light phase output pressure: MPa
0.2MPa
Motor power KW
3P/440V/60Hz/2.2kw
Overall dimensions LxWxH
1030x950x1600mm
Complete machine weight
380kg
Material medium
Lube oil (SAE40)
Manufacturer
NBo zhongceGroup
 
5.5 Exhaust Gas Boiler
Model
LFL67-0.7
Rate steam capacity:
700kg/H
Quantity
3 sets
Steam pressure:
7Bar
Steam temperature
170�?/DIV>
Safe pressure
0.75Mpa
Heating area
67m2
Boiler back pressue
Max. 220pa
Waste gas inlet temperature
350�?/DIV>
Waste gas outlet temperature
200�?/DIV>
Overall dimensions LxWxH
1824x2310x5318mm
Weight
5000kg
Manufacturer
NBo zhongceGroup
 
5.6 Air compressor
Model
VF-1.5/30
Type
Single row vertical, differential piston two-stage compression, air cooled
Exhaust capacity
Min. 1.5m3/min
Quantity
2 sets
Rating pressure
3MPa
Motor
Y108M-4/18.5kW
Overall dimensions
1650x800x1500mm
Weight
800kg
 
5.7 Air Receiver
Model
B2500
Quantity
2 sets
Working pressure
3Mpa
Volume
2500L
Overall dimensions
�?100x2890mm
Weight
1925kg
Manufacturer
NBo zhongceGroup
 
5.8 Diesel Generator
Model
400GF1-2
Quantity
1set
Power rating
400KW
Rated speed
1200rpm
Rated voltage
440V
Rated current
655A
Power factor
0.8 (Lagged)
Frequency
60Hz
Phase
3 phase 4 wires
Diesel engine
N8160ZD
Alternator
1FC5 454-6TA42-Z Siemens
Cooling method
Radiator
Dimension
5320×1668×1920
Net weight
8500Kg
Manufacturer
NBo zhongceGroup
 
5.9 Radiator
Model
V2.1-7/2.1/-4-4-S119-32D212
Quantity
10 sets
Heat exchange
1500kW
Exchange area
2x1384m2
Margin
24%
Fouling factor
0.00017m2K/W
Water flow quantity
61.88m3/h
Water inlet temperature
72�?/DIV>
Water outlet temperature
52�?/DIV>
Air flow
95.4M3/h
Design pressure
0.6Mpa
Fan speed
730r/min
Motor
11kWx3/400V
Volum
441dm3
Net weight
7500kg
Dimensions
7.5x3x3m
Manufacturer
 
 
5.10 S9-1000/6.6/0.44 Station transformer
Type
S9-1000/6.6/0.44
Rating
1000KVA
Primary Volts
6.6 KV
Secondary volts
0.44KV
Insulation level
Standard
Quantity
1 set
Manufacturer
Shandong Modern Dachi Electric Co. Ltd.
 
5.11 Heavy Fuel Oil storage
type
STH1000
Quantity
2 units
Diameter
�?1.5m
Bottom material
MS Plate 12mm
Shell material
MS Plate 12mm & 10mm & 8mm
Roof material
MS Plate 6mm
Volume
1000M3
Steam coil pipe(seamless pipe)
DN50
Heat-exchange area
30M2
Manhole Diameter
�?00
Level indicator
1 unit
Oil inlet (seamless pipe)
ND100
Oil outlet (seamless pipe)
ND80
Overflow (seamless pipe)
ND100
Drain (seamless pipe )
ND50
Dimension
�?1.5 x 10.5m
supplier
Provided by customer
 
5.12 Diesel Oil Storage
Type
STD300
Quantity
1 unit
Diameter
�?.6m
Bottom material
MS Plate 10mm
Shell material
MS Plate 10mm & 8mm & 6mm
Roof material
MS Plate 6mm
Volume
300M3
Manhole Diameter
�?00
Level indicator
1 unit
Oil inlet (seamless pipe)
DN80
Oil outlet (seamless pipe)
DN80
Overflow (seamless pipe)
DN80
Drain (seamless pipe)
DN50
Dimension
�?.6m x 8m
supplier
Provided by customer
 
5.13 Buffer HFO Tank:
type
STH100
Quantity
2 units
Diameter
�?.73m
Bottom material
MS Plate 10mm
Shell material
MS Plate 10mm & 8mm & 6mm
Roof material
MS Plate 6mm
Volume
100M3
Steam coil pipe(seamless pipe)
DN50
Heat-exchange area
6.5M2
Manhole Diameter
�?00
Level indicator
1 unit
Oil inlet (seamless pipe)
ND80
Oil outlet (seamless pipe)
ND80
Overflow (seamless pipe)
ND80
Drain (seamless pipe )
ND50
Dimension
�?.73 x 5m
supplier
Provided by customer
 
5.14 Daily Heavy Fuel Oil Tank
Type
STH50
Quantity
1 unit
Diameter
�?.82m
Bottom material
MS Plate 6mm
Shell material
MS Plate 6mm & 5mm & 4mm
Roof material
MS Plate 4mm
Volume
50M3
Manhole Diameter
�?50
Level indicator
1 unit
Steam coil pipe(seamless pipe)
DN25
Oil inlet (seamless pipe)
DN80
Oil outlet (seamless pipe)
DN80
Drain (seamless pipe)
DN40
Overflow Pipe (seamless pipe)
DN50
Heat-exchange area
6.5M2
Dimension
�?.82m x 4.50m
supplier
Provided by customer
 
5.15 Daily Diesel Oil Tank
Type
STD50
Quantity
1 unit
Diameter
�?.82m
Bottom material
MS Plate 6mm
Shell material
MS Plate 6mm & 5mm & 4mm
Roof material
MS Plate 4mm
Volume
50M3
Manhole Diameter
�?50
Level indicator
1 unit
Oil inlet (seamless pipe)
DN80
Oil outlet (seamless pipe)
DN80
Overflow (seamless pipe)
DN50
Drain (seamless pipe)
DN40
Dimension
�?.82m x 4.50m
supplier
Provided by customer
 
5.16 Sludge Oil Tank
Type
STH50
Quantity
1 unit
Diameter
�?.82m
Bottom material
MS Plate 6mm
Shell material
MS Plate 6mm & 5mm & 4mm
Roof material
MS Plate 4mm
Volume
50M3
Manhole Diameter
�?50
Level indicator
1 unit
Steam coil pipe(seamless pipe)
DN25
Oil inlet (seamless pipe)
DN80
Oil outlet (seamless pipe)
DN80
Drain (seamless pipe)
DN40
Overflow Pipe (seamless pipe)
DN50
Heat-exchange area
6.5M2
Dimension
�?.82m x 4.50m
supplier
Provided by customer
 
5.17 Common Circulating & Booster module
Model
KHVU-C-5.0-C
Fuel feed capacity
5 m3/h
Fuel circulating capacity
10m3/h
Fuel supply pressure
,
0.6Mpa
Fuel feed pressure
0.6Mpa
Max. fuel temperature
135�?/DIV>
Min. Fuel feed rate
50M3
Rated fuel temperature rise
4-5�?min
Viscosity before engine inlet
9-13 cSt
Viscosity deviation
±1.5cSt
Viscosity steady time
Max. 3.5 mins
Viscosity control accuracy
Max. 3%
Primary filter
80 mesh/inch2
Fine filter
Max. 10-30µ
Power source
3P 440V 60HZ
Power
17kW
Load
8kW
Dimension LxWxH
2600x1400x2100mm
Weight
2550kg
Manufacturer
NBo zhongceGroup
 
5.18 HFO unloading station
Type
HFO58
Quantity
1 set
Capacity
58M3/h
Outlet pressure
0.28Mpa
Motor power
18.5Kwx2
Manufacturer
NBo zhongceGroup
 
5.19 Diesel oil unloading station
Type
DO58
Quantity
1 set
Capacity
58M3/h
Outlet pressure
0.28Mpa
Motor power
18.5kWx2
Manufacturer
NBo zhongceGroup
 
5.20 Station batteries and battery charger panel
Model
PGD7-�?180-220
AC input voltage
440Vac±20%
DC output voltage
24V, 220V
DC output current
A
Storage battery capacity
300Ah
Accuracy of voltage regulation
Max. ±0.2%
Accuracy of current regulation
Max. ±0.2%
Ripple factor
Max. 0.1%
Power factor
Min. 0.93
Efficiency
Min. 95%
Noise
50dB
Dielectric strength
2000V 1 min without breakdown
Operation environment
Temperatur:-10 to 45�? Relative humidity:not greater than 90% at 20±5�?/DIV>
Interface
RS485, RS232 & RS422
High frequency rectifier module
Emerson HD22020 3pcs
PLC
SIEMENS S7-200
LCD display screen
HITECH PWS 5.7�?/DIV>
Rectifier module
Emerson HD2205 3pcs
Maintenance-free lead-acid battery
A400-180/12V 18 pcs
Overall dimensions (LxDxH)
800x800x2200mm 3pcs
Manufacturer
Zj Sanchen
 
5.21 Oily water separator
Model
LYS-5
Oily water treatment capacity
5.0m3/h
Emission standard
Max. 10 ppm
Working pressure
2.5bar
Pump and motor
Electric driven reciprocating pump/1.10 KW
Suction height of pump
6m
Power source
AC400V 50Hz
Oil drain control mode
Auto and manual
Oil collecting tank heating mode
Electric heating
Manufacturer
NBo zhongceGroup
 




Copyright©2006-2013 Leda Greenpower Beijing ICP Reg. No: 10010978
   Fax:0086-10-84161062  E-mail:
[email protected]
[email protected]